| Literature DB >> 31936699 |
Cesira Pasquarella1, Carla Balocco2, Maria Eugenia Colucci1, Elisa Saccani1, Samuel Paroni1, Lara Albertini3, Pietro Vitali4, Roberto Albertini1,5.
Abstract
Surgical staff behavior in operating theatres is one of the factors associated with indoor air quality and surgical site infection risk. The aim of this study was to apply an approach including microbiological, particle, and microclimate parameters during two simulated surgical hip arthroplasties to evaluate the influence of staff behavior on indoor air quality. During the first hip arthroplasty, the surgical team behaved correctly, but in the second operation, behavioral recommendations were not respected. Microbiological contamination was evaluated by active and passive methods. The air velocity, humidity, temperature, and CO2 concentration were also monitored. The highest levels of microbial and particle contamination, as well as the highest variation in the microclimate parameter, were recorded during the surgical operation where the surgical team behaved "incorrectly". Turbulent air flow ventilation systems appeared more efficient than in the past and very low air microbial contamination was reached when behavior was correct. Therefore, adherence to behavioral recommendations in operating theatres is essential to not undermine the effectiveness of the heating, ventilation, and air conditioning systems and employed resources.Entities:
Keywords: biological monitoring; hip arthroplasty; indoor air quality; microclimatic monitoring; operating theatre; particle counting; surgical staff behavior
Mesh:
Year: 2020 PMID: 31936699 PMCID: PMC7013425 DOI: 10.3390/ijerph17020452
Source DB: PubMed Journal: Int J Environ Res Public Health ISSN: 1660-4601 Impact factor: 3.390
Figure 1Diagram of the operating theatre showing the sampling points at the operating table, exhaust grille, and the entrance door.
Microbial air contamination values obtained via active (CFU/m3) and passive (IMA) sampling, and particle (≥0.5 µm) contamination at different sampling point during rest, correct, and not correct conditions.
| Operating Table | Exhaust Grille | Entrance Door | |||||||
|---|---|---|---|---|---|---|---|---|---|
| R | C | NC | R | C | NC | R | C | NC | |
|
| 2 | 13 | 74 | 3 | 23 | 44 | 4 | 29 | 93 |
|
| 0 | 2 | 8 | 0 | 6 | 8 | 2 | 4 | 16 |
|
| 1848 | 64,783 | 82,696 | - | - | - | - | - | - |
R = at rest; C = correct conditions; NC = not correct conditions; CFU = colony-forming units; IMA = Index of Microbial Air contamination.
Median values, averages, and standard deviation values of the microclimatic parameters.
| Air velocity [m/s] | Temperature [°C] | Relative Humidity [%] | CO2 [ppm] | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| OPERATING TABLE | Entrance Door | Operating Table Radiant | Operating Table | Exhaust Grille | Entrance Door | Operating Table | Exhaust Grille | Entrance Door | Operating Table | ||
|
| 0.023 | 0.135 | 20.69 | 20.26 | 20.50 | 19.98 | 65.60 | 67.10 | 66.00 | 410.39 |
|
|
| 0.031 | 0.134 | 20.68 | 20.27 | 20.49 | 19.98 | 65.57 | 67.05 | 66.00 | 411.99 | |
|
| 0.04 | 0.02 | 0.02 | 0.03 | 0.03 | 0.01 | 0.12 | 0.16 | 0.10 | 0.18 | |
|
| 0.051 | 0.093 | 21.28 | 20.94 | 20.98 | 20.50 | 64.30 | 66.20 | 65.20 | 505.91 |
|
|
| 0.069 | 0.095 | 21.27 | 20.93 | 20.97 | 20.51 | 64.21 | 65.98 | 65.16 | 506.31 | |
|
| 0.06 | 0.05 | 0.03 | 0.06 | 0.03 | 0.05 | 0.26 | 0.25 | 0.13 | 0.52 | |
|
| 0.19 | 0.092 | 21.53 | 21.22 | 21.21 | 20.78 | 63.80 | 65.80 | 64.71 | 522.50 |
|
|
| 0.15 | 0.11 | 21.50 | 21.20 | 21.20 | 20.80 | 63.60 | 65.70 | 64.70 | 520.52 | |
|
| 0.07 | 0.07 | 0.05 | 0.05 | 0.05 | 0.05 | 0.21 | 0.22 | 0.12 | 0.86 | |
Figure 2Air temperature values measured during the different operating theatre (OT) conditions (R, C, and NC) at the operating table, exhaust grille, and the entrance door.
Figure 3Air relative humidity values measured during different OT conditions (R, C, and NC) at the operating table, exhaust grille, and entrance door.
Figure 4CO2 concentration values measured during different OT conditions (R, C, and NC) at the operating table.