Inconsistent correlation between aerobic bacterial surface and air counts in operating rooms with ultra clean laminar air flows: proposal of a new bacteriological standard for surface contamination.

B Friberg1, S Friberg, L G Burman.   

Abstract

The relationship between surface contamination (cfus/m2/h) with particles carrying aerobic bacteria and corresponding air contamination rates (cfus/m3) was evaluated in operating rooms (OR) equipped with ultra clean vertical or horizontal laminar airflow (LAF). For the evaluation we collected data during strictly standardized sham operations using non-woven disposable or cotton clothing. Air contamination in the wound and instrument areas (Casella slit sampler) was related to the surface contamination rate (settle plates) in the same areas and in addition, on the patient chest. Typically, the mean surface counts were 20-70 cfus/m2/h and the air counts 1-2 cfus/m3 in disposable clothing experiments, whilst the use of cotton clothing resulted in higher counts of 100-200 cfus/m2/h (wound P > 0.05, patient P > 0.05, instruments P < 0.01) and 4 cfus/m3 (P < 0.02-0.001). In the vertical LAF, taking both disposable and cotton clothing operations together, the surface and air contamination rates (surface/air ratio SAR) were highly correlated (P = 0.02-0.004) and the ratio varied between 18:1 and 50:1 with a mean for wound air of 36:1. Using only disposable clothing in the vertical LAF, the number of significant correlations was reduced. With cotton clothing experiments in vertical LAF and in the horizontal LAF using disposable clothing, no significant correlation between surface and air contamination was found. The wide variation of SAR values and the inconsistent relationship between surface and air counts indicates that measurement of OR air contamination represents an unhelpful method for assessment of surgical site contamination in LAF units. We propose instead that colony counts on sedimentation plates is a clinically more relevant indicator of bacterial OR contamination in LAF units. In addition to the current bacteriological standard for ultra clean OR air of (< 10 cfus/m3) we suggest a corresponding standard for the surface contamination rate of < 350 cfus/m2/h.

Entities:  

Mesh:

Year:  1999        PMID: 10467542     DOI: 10.1053/jhin.1998.0598

Source DB:  PubMed          Journal:  J Hosp Infect        ISSN: 0195-6701            Impact factor:   3.926


  8 in total

1.  Field sampling of indoor bioaerosols.

Authors:  Jennie Cox; Hamza Mbareche; William G Lindsley; Caroline Duchaine
Journal:  Aerosol Sci Technol       Date:  2019-11-21       Impact factor: 2.908

2.  Analyzing the risk factors influencing surgical site infections: the site of environmental factors.

Authors:  Jose L Alfonso-Sanchez; Isabel M Martinez; Jose M Martín-Moreno; Ricardo S González; Francisco Botía
Journal:  Can J Surg       Date:  2017-06       Impact factor: 2.089

Review 3.  Microorganisms in Confined Habitats: Microbial Monitoring and Control of Intensive Care Units, Operating Rooms, Cleanrooms and the International Space Station.

Authors:  Maximilian Mora; Alexander Mahnert; Kaisa Koskinen; Manuela R Pausan; Lisa Oberauner-Wappis; Robert Krause; Alexandra K Perras; Gregor Gorkiewicz; Gabriele Berg; Christine Moissl-Eichinger
Journal:  Front Microbiol       Date:  2016-10-13       Impact factor: 5.640

4.  A Clinical Test to Measure Airborne Microbial Contamination on the Sterile Field During Total Joint Replacement: Method, Reference Values, and Pilot Study.

Authors:  John H Harp
Journal:  JB JS Open Access       Date:  2018-08-24

5.  Conversion of operating theatre from positive to negative pressure environment.

Authors:  T T Chow; A Kwan; Z Lin; W Bai
Journal:  J Hosp Infect       Date:  2006-12       Impact factor: 3.926

6.  The Influence of Surgical Staff Behavior on Air Quality in a Conventionally Ventilated Operating Theatre during a Simulated Arthroplasty: A Case Study at the University Hospital of Parma.

Authors:  Cesira Pasquarella; Carla Balocco; Maria Eugenia Colucci; Elisa Saccani; Samuel Paroni; Lara Albertini; Pietro Vitali; Roberto Albertini
Journal:  Int J Environ Res Public Health       Date:  2020-01-10       Impact factor: 3.390

7.  Evaluation of Air Contamination in Orthopaedic Operating Theatres in Hospitals in Southern Italy: The IMPACT Project.

Authors:  Maria Teresa Montagna; Serafina Rutigliano; Paolo Trerotoli; Christian Napoli; Francesca Apollonio; Alessandro D'Amico; Osvalda De Giglio; Giusy Diella; Marco Lopuzzo; Angelo Marzella; Simona Mascipinto; Chrysovalentinos Pousis; Roberto Albertini; Cesira Pasquarella; Daniela D'Alessandro; Gabriella Serio; Giuseppina Caggiano
Journal:  Int J Environ Res Public Health       Date:  2019-09-25       Impact factor: 3.390

Review 8.  How do we assess hospital cleaning? A proposal for microbiological standards for surface hygiene in hospitals.

Authors:  S J Dancer
Journal:  J Hosp Infect       Date:  2004-01       Impact factor: 3.926

  8 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.