| Literature DB >> 25019268 |
Sonia R Jurado1, Antônia D P Bankoff2, Andrea Sanchez3.
Abstract
This study evaluated the indoor air quality in Brazilian universities by comparing thirty air-conditioned (AC) (n = 15) and naturally ventilated (NV) (n = 15) classrooms. The parameters of interest were indoor carbon dioxide (CO2), temperature, relative humidity (RH), wind speed, viable mold, and airborne dust levels. The NV rooms had larger concentration of mold than the AC rooms (1001.30 ± 125.16 and 367.00 ± 88.13 cfu/m3, respectively). The average indoor airborne dust concentration exceeded the Brazilian standards (<80 µg/m3) in both NV and AC classrooms. The levels of CO2 in the AC rooms were significantly different from the NV rooms (1433.62 ± 252.80 and 520.12 ± 37.25 ppm, respectively). The indoor air quality in Brazilian university classrooms affects the health of students. Therefore, indoor air pollution needs to be considered as an important public health problem.Entities:
Mesh:
Substances:
Year: 2014 PMID: 25019268 PMCID: PMC4113862 DOI: 10.3390/ijerph110707081
Source DB: PubMed Journal: Int J Environ Res Public Health ISSN: 1660-4601 Impact factor: 3.390
Characteristics of the studied universities.
| Monitored Sites | Description |
|---|---|
| University A | Located in a suburban area |
| Surrounded by residences and industries | |
| Use of a blackboard and chalk | |
| Built in the 70s | |
| Presence of vegetation nearby | |
| University B | Located in a suburban area |
| Surrounded by residences and buildings | |
| Use of a blackboard and chalk | |
| Built in 2000 | |
| No presence of vegetation nearby | |
| University C | Located in a suburban area |
| Surrounded by residences and buildings | |
| Use of blackboard with chalk | |
| Built in the 70s | |
| No presence of vegetation nearby | |
| University D | Located in a central area |
| Surrounded by residences and buildings | |
| Use of a blackboard and chalk | |
| Built in the 70s | |
| Presence of vegetation nearby | |
| University E | Located in a suburban area |
| Surrounded by residences and buildings | |
| Use of a blackboard and chalk | |
| Built in the 90s | |
| No presence of vegetation nearby |
Indoor environmental quality parameters evaluated in classrooms.
| Pollutant/Parameter | NV | AC | Brazilian Recommended Values |
|---|---|---|---|
| Room temperature (°C) | 28.87 ± 0.57 | 25.87 ± 0.65 * | 23–26 (in summer) |
| Relative air humidity (%) | 65.00 ± 2.13 | 56.21 ± 1.70 * | 40–65 (in summer) |
| Wind speed (m/s) | 0.14 ± 0.01 | 0.09 ± 0.01 * | ≤0.25 |
| CO2 (ppm) | 520.12 ± 37.25 | 1433.62 ± 252.80 * | ≤1000 |
| Airborne dust (μg/m3) | 215.12 ± 68.20 | 659.22 ± 102.80 * | ≤80 |
| Viable fungi (cfu/m3) | 1001.30 ± 125.16 | 367.00 ± 88.13 * | ≤750 |
| I/O | 1.08 ± 0.21 | 0.45 ± 0.09 * | ≥1.5 |
I/O: indoor/outdoor fungi concentration ratio. Values are expressed as mean ± standard error. * p < 0.05.
Symptoms and absenteeism in students from NV and AC classrooms.
| Type | Naturally Ventilated ( | Air-conditioned ( |
|---|---|---|
| Eye irritation (%) | 26.0 | 24.0 |
| Nasal irritation (%) | 28.0 | 32.0 |
| Throat irritation (%) | 22.0 | 16.0 |
| Headache (%) | 18.0 | 20.0 |
| Difficulties to concentrate (%) | 23.0 | 25.0 |
| Fatigue (%) | 28.0 | 26.0 |
| Lethargy (%) | 23.0 | 17.0 |
| 12.0 | 9.0 |
Building-related symptoms according to the levels of airborne fungi, airborne dust (AD), and carbon dioxide in NV and AC rooms.
| Symptoms of SBS | ||||||
|---|---|---|---|---|---|---|
| NV | AC | NV | AC | NV | AC | |
| Eye irritation | 0.21 | 0.34 | 0.11 | 0.59 # | 0.12 | 0.24 |
| Nasal irritation | 0.33 | 0.36 | 0.20 | 0.52 † | 0.10 | 0.18 |
| Throat irritation | 0.21 | 0.43 | 0.27 | 0.56 † | 0.15 | 0.47† |
| Headache | 0.56 * | 0.36 | 0.11 | 0.57 * | 0.17 | 0.08 |
| Difficulties in concentration | 0.61 * | 0.23 | 0.13 | 0.61 * | 0.20 | 0.07 |
| Fatigue | 0.71 | 0.32 | 0.22 | 0.68 * | 0.18 | 0.11 |
| Lethargy | 0.59 | 0.15 | 0.19 | 0.68 | 0.48 | 0.49 |
* p < 0.001; # p < 0.01; † p < 0.05.
Perception of indoor climate by occupants of classrooms.
| ASHRAE Scale | NV | AC |
|---|---|---|
| –3 cold | 0.0% | 1.0% |
| –2 cool | 0.0% | 4.0% |
| –1 slightly cool | 3.0% | 25.0% |
| 0 neutral | 40.0% | 55.0% |
| +1 slightly warm | 21.0% | 7.0% |
| +2 warm | 29.0% | 8.0% |
| +3 hot | 7.0% | 0.0% |