| Literature DB >> 23036479 |
Shobha S Subhash1, Gio Baracco, Kevin P Fennelly, Michael Hodgson, Lewis J Radonovich.
Abstract
Entities:
Mesh:
Year: 2012 PMID: 23036479 PMCID: PMC7135637 DOI: 10.1016/j.ajic.2012.06.004
Source DB: PubMed Journal: Am J Infect Control ISSN: 0196-6553 Impact factor: 2.918
Airborne infection isolation room (AIIR) anteroom requirements recommended by various organizations
| Organization | Recommendations for anteroom | Pressure recommendations |
|---|---|---|
| The Facility Guidelines Institute (2010) | Anteroom is not required for AIIRs; however, if anteroom is part of the design concept, it specifies requirements (Page 49, Section 2.1-2.4.2.3) Anteroom is required for combination AIIR/PE room that houses profoundly immunosuppressed patients with prolonged neutropenia (eg, patients undergoing allogenic or autologous bone marrow/stem cell transplants) who have an airborne infectious disease (Page 92, Section 2.2-2.2.4.5) | When an anteroom is provided for an AIIR, airflow shall be from the corridor into the anteroom and from the anteroom into the patient room (Page 65, Section 2.1-8.2.2.1) The airflow pattern for a AIIR/PE anteroom will either be from the anteroom to both the patient room and the corridor, or from both the patient room and the corridor into the anteroom (Page 172, Section 2.2-8.2.2.3) For other ventilation requirements refer to Part 6, ASHRAE 170 |
| ASHRAE170 Ventilation of Health Care Facilities, | Anteroom is not required by this standard. Some isolation rooms may be provided with a separate anteroom (Section 7.1, Part e) If the design criteria indicate that AIIR is necessary for PE patients, an anteroom should be provided. Rooms with reversible airflow provisions for purpose of switching between protective environment and AIIR functions shall not be permitted (Section 7.1, Part t) The AIIR described in this standard shall be used for isolating the airborne spread of infectious diseases, such as measles, varicella, or tuberculosis (Section 7.1, Part u) | For AIIRs pressure relationship to adjacent areas must be negative and shall have a minimum of -0.01 water gauge (-2.5 Pa) minimum outdoor ACH is 2 and minimum total ACH is 12 (Table 7-1, Section 7.2.1) For isolation anteroom no requirements are mentioned for pressure relationship to adjacent areas and no minimum outdoor ACH. However minimum total ACH is 10 (Table 7-1) |
| CDC/HICPAC Guidelines for Environmental Infection Control in Health-Care Facilities (2003) | Recommends negative pressure rooms or AIIRs with anterooms for patients with viral hemorrhagic fever (Page 12) AIIRs can be constructed either with or without an anteroom (Page 36) | AIIR with anterooms (Pages 37-38) Pressure differential of 2.5 Pa (0.01-in water gauge) measured at the door between patient room and anteroom ACH ≥12 (for renovation or new construction), 6 for existing areas Clean-to-dirty airflow |
| AIA Guidelines for Design and Construction of Healthcare Facilities (2006) | The anteroom concept should remain an option (ie, not required) and should be designed so as to prevent air from the patient room from escaping to the corridor or other common areas (A3.2.2.4[4]) Anteroom required when an immunosuppressed patient requires airborne infection isolation (protective environment/airborne infection isolation) (A3.2.3b, Page 44) | Anteroom for an AIIR/PE room can be ventilated with either of following airflow patterns (A3.2.3c, Page 44): Airflows from anteroom, to patient room and the corridor, or Airflows from the patient room and the corridor, into the anteroom Minimum total ACH is 10 (Table 2.1-2) Pressure differentials for AIIRs shall be a minimum of 0.01-in water gauge (2.5 Pa). Air movement relationship to adjacent areas is into the room. Minimum total ACH is 12. Minimum outdoor ACH is 2 (Table 2.1-2, Pages 130 and 132) |
| National Health Service (United Kingdom standard) Isolation facilities in acute settings (2005) | Isolation room is known as positive pressure ventilated lobby room. It is an enhanced single room with a positive pressure ventilated entry lobby and en-suite facilities (with extract ventilation) that enables the suite to be used for both source and protective isolation without need for switchable ventilation (Sections 1.6 and 2.9) | Isolation room pressure differential to corridor is nominally 0, ACH 10 Lobby/vestibule pressure differential with respect to corridor is +10 Pa, ACH 63 (for bed access lobby) and ACH 69 (for personnel access lobby) En-suite pressure differential to isolation room is negative, ACH 10 Ventilated lobby acts as barrier to contamination passing in or out of isolation room ( |
| Victorian Advisory Committee on Infection Control (Australian standard) Guidelines for the classification and design of isolation rooms in health care facilities (2007) | Recommends an anteroom for Class N (negative pressure) rooms. Negative pressure rooms are used for persons known or suspected to have infections requiring airborne precautions (eg, chicken pox, measles and infectious pulmonary and laryngeal tuberculosis) (Summary, Negative pressure gradient must be maintained from the room to the anteroom and the ambient air (Section 2.2) | The minimum differential pressure between the isolation room and adjacent ambient pressure areas should be 30 Pa if the room has an anteroom, and 15 Pa if the room does not have an anteroom. The gradient between successive pressure areas should not be less than 15 Pa (Section 5.2) Recommends ACH 12 for negative pressure rooms(Section 2.2) |
ACH, air change per hour; AIA, American Institute of Architects; ANSI/ASHRAE/ASHE, American National Standards Institute/American Society of Heating, Refrigerating, and Air-Conditioning Engineers/American Society for Healthcare Engineering of the American Hospital Association; CDC/HICPAC, Centers for Disease Control and Prevention/Healthcare Infection Control Practices Advisory Committee; PE, protective environment.