Literature DB >> 15236852

Containment testing of isolation rooms.

J P Rydock1, P K Eian.   

Abstract

Results from the tracer containment testing of four 'state-of-the-art' airborne infection isolation rooms, in a new hospital, are presented. A testing technician exited an isolation room several minutes after a small quantity of tracer gas was injected over the patient bed in that room. Easily measurable tracer gas concentrations were then found in the anterooms outside the patient rooms and corridor outside the isolation room suites. Containment factors for the isolation rooms and dilution factors in the anterooms and corridor were calculated, based on the measured tracer concentrations. These results indicate the desirability of evidence-based design standards and guidelines for assessing performance of airborne infection isolation rooms. The study also demonstrates that the tracer testing procedure yields comparable results for equivalent isolation room suites, suggesting good reproducibility of the testing method.

Entities:  

Mesh:

Substances:

Year:  2004        PMID: 15236852     DOI: 10.1016/j.jhin.2004.01.032

Source DB:  PubMed          Journal:  J Hosp Infect        ISSN: 0195-6701            Impact factor:   3.926


  6 in total

1.  Different types of door-opening motions as contributing factors to containment failures in hospital isolation rooms.

Authors:  Julian W Tang; Andre Nicolle; Jovan Pantelic; Christian A Klettner; Ruikun Su; Petri Kalliomaki; Pekka Saarinen; Hannu Koskela; Kari Reijula; Panu Mustakallio; David K W Cheong; Chandra Sekhar; Kwok Wai Tham
Journal:  PLoS One       Date:  2013-06-24       Impact factor: 3.240

Review 2.  Observing and quantifying airflows in the infection control of aerosol- and airborne-transmitted diseases: an overview of approaches.

Authors:  J W Tang; C J Noakes; P V Nielsen; I Eames; A Nicolle; Y Li; G S Settles
Journal:  J Hosp Infect       Date:  2010-12-30       Impact factor: 3.926

3.  Virus diffusion in isolation rooms.

Authors:  P H Kao; R J Yang
Journal:  J Hosp Infect       Date:  2005-12-15       Impact factor: 3.926

4.  Isolation anterooms: important components of airborne infection control.

Authors:  Shobha S Subhash; Gio Baracco; Kevin P Fennelly; Michael Hodgson; Lewis J Radonovich
Journal:  Am J Infect Control       Date:  2012-10-02       Impact factor: 2.918

5.  Airflow patterns through single hinged and sliding doors in hospital isolation rooms - Effect of ventilation, flow differential and passage.

Authors:  Petri Kalliomäki; Pekka Saarinen; Julian W Tang; Hannu Koskela
Journal:  Build Environ       Date:  2016-07-15       Impact factor: 6.456

6.  Hospital and community acquired infection and the built environment--design and testing of infection control rooms.

Authors:  J T Walker; P Hoffman; A M Bennett; M C Vos; M Thomas; N Tomlinson
Journal:  J Hosp Infect       Date:  2007-06       Impact factor: 3.926