A performance assessment of airborne infection isolation rooms.

Stefan A Saravia1, Peter C Raynor, Andrew J Streifel.   

Abstract

BACKGROUND: Airborne infection isolation rooms (AIIRs) help prevent the spread of infectious agents in hospitals. The performance of 678 AIIRs was evaluated and compared with construction design guidelines.
METHODS: The pressure differentials (DeltaP) between the isolation rooms and adjacent areas were measured, and ventilation and construction details were recorded for each room. Ultrafine particle concentrations were evaluated in the rooms, surrounding areas, and ventilation systems serving the rooms. Measurements were analyzed as a function of room parameters.
RESULTS: Only 32% of the isolation rooms achieved the recommended DeltaP of -2.5 Pascals (Pa) relative to surrounding areas. AIIRs with solid ceilings had an average DeltaP of -4.4 Pa, which was significantly higher than the average DeltaP of -2.0 Pa for rooms with dropped ceilings (P = .0002). Isolation room ultrafine particle concentrations were more highly correlated with particle levels in surrounding areas (R(2) = 0.817) than in the ventilation systems serving the rooms (R(2) = 0.441). Almost all ventilation filters serving AIIRs collected fewer particles than anticipated.
CONCLUSION: The results indicate that hospitals are not all maintaining AIIRs to correspond with current guidelines. The findings also support the contention that having tightly sealed rooms helps maintain appropriate pressure differentials.

Entities:  

Mesh:

Substances:

Year:  2007        PMID: 17577480     DOI: 10.1016/j.ajic.2006.10.012

Source DB:  PubMed          Journal:  Am J Infect Control        ISSN: 0196-6553            Impact factor:   2.918


  6 in total

1.  Transmission of pathogen-laden expiratory droplets in a coach bus.

Authors:  Xia Yang; Cuiyun Ou; Hongyu Yang; Li Liu; Tie Song; Min Kang; Hualiang Lin; Jian Hang
Journal:  J Hazard Mater       Date:  2020-04-12       Impact factor: 10.588

2.  Different types of door-opening motions as contributing factors to containment failures in hospital isolation rooms.

Authors:  Julian W Tang; Andre Nicolle; Jovan Pantelic; Christian A Klettner; Ruikun Su; Petri Kalliomaki; Pekka Saarinen; Hannu Koskela; Kari Reijula; Panu Mustakallio; David K W Cheong; Chandra Sekhar; Kwok Wai Tham
Journal:  PLoS One       Date:  2013-06-24       Impact factor: 3.240

Review 3.  Multidisciplinary Approach to the Diagnosis and In-Hospital Management of COVID-19 Infection: A Narrative Review.

Authors:  Giuliano Lo Bianco; Santi Di Pietro; Emilia Mazzuca; Aurelio Imburgia; Luca Tarantino; Giuseppe Accurso; Vincenzo Benenati; Federica Vernuccio; Claudio Bucolo; Salvatore Salomone; Marianna Riolo
Journal:  Front Pharmacol       Date:  2020-12-09       Impact factor: 5.810

4.  Monitoring of the environment at the transplant unit-hemato-oncology clinic.

Authors:  Ivanka Matoušková; Ondřej Holy
Journal:  Int J Environ Res Public Health       Date:  2014-09-12       Impact factor: 3.390

5.  Isolation anterooms: important components of airborne infection control.

Authors:  Shobha S Subhash; Gio Baracco; Kevin P Fennelly; Michael Hodgson; Lewis J Radonovich
Journal:  Am J Infect Control       Date:  2012-10-02       Impact factor: 2.918

Review 6.  Engineering Solutions for Preventing Airborne Transmission in Hospitals with Resource Limitation and Demand Surge.

Authors:  Hina Zia; Ritu Singh; Manu Seth; Armin Ahmed; Afzal Azim
Journal:  Indian J Crit Care Med       Date:  2021-04
  6 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.