James J McDevitt1, Donald K Milton, Stephen N Rudnick, Melvin W First.
Abstract
In the event of a smallpox outbreak due to bioterrorism, delays in vaccination programs may lead to significant secondary transmission. In the early phases of such an outbreak, transmission of smallpox will take place especially in locations where infected persons may congregate, such as hospital emergency rooms. Air disinfection using upper-room 254 nm (UVC) light can lower the airborne concentrations of infective viruses in the lower part of the room, and thereby control the spread of airborne infections among room occupants without exposing occupants to a significant amount of UVC. Using vaccinia virus aerosols as a surrogate for smallpox we report on the effectiveness of air disinfection, via upper-room UVC light, under simulated real world conditions including the effects of convection, mechanical mixing, temperature and relative humidity. In decay experiments, upper-room UVC fixtures used with mixing by a conventional ceiling fan produced decreases in airborne virus concentrations that would require additional ventilation of more than 87 air changes per hour. Under steady state conditions the effective air changes per hour associated with upper-room UVC ranged from 18 to 1000. The surprisingly high end of the observed range resulted from the extreme susceptibility of vaccinia virus to UVC at low relative humidity and use of 4 UVC fixtures in a small room with efficient air mixing. Increasing the number of UVC fixtures or mechanical ventilation rates resulted in greater fractional reduction in virus aerosol and UVC effectiveness was higher in winter compared to summer for each scenario tested. These data demonstrate that upper-room UVC has the potential to greatly reduce exposure to susceptible viral aerosols. The greater survival at baseline and greater UVC susceptibility of vaccinia under winter conditions suggest that while risk from an aerosol attack with smallpox would be greatest in winter, protective measures using UVC may also be most efficient at this time. These data may also be relevant to influenza, which also has improved aerosol survival at low RH and somewhat similar sensitivity to UVC.Entities:
Mesh:
Substances:
Year: 2008 PMID: 18781204 PMCID: PMC2527528 DOI: 10.1371/journal.pone.0003186
Source DB: PubMed Journal: PLoS One ISSN: 1932-6203 Impact factor: 3.240
Figure 1Background decay rates and decay rates for UVC light with and without heat boxes.
a) ceiling fan is not operational; b) when ceiling fan is operational.
Equivalent Air Changes per Hour Due to UVC (ACHUVC) for Virus Aerosol Decay Tests with and without ceiling fan and heat boxes.
| Ceiling Fan Operational | ||
| No | Yes | |
|
| 7 | 92 |
|
| 16 | 87 |
Effective Air Changes per Hour Associated with Upper-Room UVC for Steady State Virus Aerosols.
| Condition | Replicate Trials (Air Samples) | Ventilation Rate, ACH | UVC Fixtures | Fraction of Infective Virus Remaining | ACHUVC | ||||
| Estimate | 95% Confidence Interval | Estimate | 95% Confidence Interval | ||||||
| Summer | 2 (20) | 2 | 1 | 0.087 | 0.062 | 0.120 | 18 | 15 | 30 |
| 1 (12) | 2 | 4 | 0.061 | 0.053 | 0.071 | 31 | 26 | 36 | |
| 3 (36) | 6 | 1 | 0.14 | 0.120 | 0.160 | 38 | 31 | 46 | |
| 3 (36) | 6 | 4 | 0.078 | 0.065 | 0.094 | 71 | 58 | 86 | |
| Winter | 2 (24) | 2 | 1 | 0.017 | 0.014 | 0.021 | 110 | 93 | 140 |
| 2 (24) | 2 | 4 | 0.003 | 0.002 | 0.005 | 580 | 410 | 830 | |
| 2 (24) | 6 | 1 | 0.038 | 0.032 | 0.046 | 150 | 120 | 180 | |
| 2 (24) | 6 | 4 | 0.006 | 0.004 | 0.008 | 1000 | 740 | 1400 | |
Figure 2Equivalent air changes due to UVC under steady state conditions with either 2 or 6 ACH, 1 or 4 UVC fixtures, or winter and summer conditions.
Figure 3Schematic diagram of aerosol chamber and equipment.
Note: for clarity ceiling fan is not shown, but is located in the center of the main chamber directly above the virus distributor. For decay and single fixture steady state experiments the fixture shown in the center of the wall on the left of the figure was used and for the four fixture steady state experiments the other four fixtures were used.