| Literature DB >> 36166418 |
Xiaochun Wu1,2, Yan Zhang1,3,4, Fang Hou1,3,4, Huichao Wang2, Jianjie Zhou2, Wei Yu1,3,4.
Abstract
Indoor air pollution is complex and serious. In fact, an on-site investigation of an office building revealed that the concentration of three typical pollutants (CO2, VOCs, PM2.5) exceeded the Chinese standard. To identify a better control method to achieve good indoor air quality, an orthogonal experiment was carried out in an environmental chamber to compare the control time and energy consumption of four control methods (purifier+ and window+, purifier+ and window-, purified fresh air 240 m3/h and purified fresh air 400 m3/h) to meet the standard established for pollutants. The purifier+ and window+ method was found to be more effective in most conditions, with a control time reduced by 8.06% and energy consumption reduced by 11.91% compared with the traditional control method of purified fresh air 240 m3/h. This research highlights the optimal control strategy for the air quality in office buildings under different pollution conditions.Entities:
Mesh:
Substances:
Year: 2022 PMID: 36166418 PMCID: PMC9514625 DOI: 10.1371/journal.pone.0275157
Source DB: PubMed Journal: PLoS One ISSN: 1932-6203 Impact factor: 3.752
Orthogonal experiment condition and comprehensive evaluation result.
| Condition | Experimental factors | Experimental results | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CO2 | VOCs | Indoor PM2.5 | Outdoor PM2.5 | Control methods | Control time (min) | Energy consumption | Percentage of time | Percentage of energy consumption | Comprehensive evaluation | |||
| PM2.5 | CO2 | VOCs | ||||||||||
| 1 | 1000-(1) | 0.6-(1) | 0–35(1) | 0–35(1) | Purified fresh air240(1) | contrast | 0.059* a | 5.56% | 8.13% | 6.84% | 7.36% | 6.33% |
| 2 | 1000- | 0.6+(2) | 0–35 | 0–35 | purifier+ and window-(2) | 50 | 0.257 | 27.78% | 35.40% | 31.59% | 33.11% | 30.07% |
| 3 | 1000+(2) | 0.6- | 0–35 | 0–35 | purifier+ and window+(3) | 20 | 0.160 | 11.11% | 22.04% | 16.57% | 18.76% | 14.39% |
| 4 | 1000+ | 0.6+ | 0–35 | 0–35 | Purified fresh air400(4) | 60 | 0.590 | 33.33% | 81.27% | 57.30% | 66.89% | 47.71% |
| 5 | 1000- | 0.6+ | 36–75(2) | 0–35 | purifier+ and window- | 50 | 0.160 | 27.78% | 22.04% | 24.91% | 23.76% | 26.06% |
| 6 | 1000+ | 0.6- | 36–75 | 0–35 | purifier+ and window+ | 20 | 0.187 | 11.11% | 25.76% | 18.43% | 21.37% | 15.51% |
| 7 | 1000- | 0.6- | 76–115(3) | 0–35 | Purified fresh air240 | 13 | 0.031 | 7.22% | 4.21% | 5.72% | 5.11% | 6.32% |
| 8 | 1000+ | 0.6+ | 76–115 | 0–35 | Purified fresh air400 | 60 | 0.270 | 33.33% | 37.19% | 35.26% | 36.03% | 34.49% |
| 9 | 1000- | 0.6+ | 0–35 | 36–75(2) | purifier+ and window+ | 10 | 0.060 | 5.56% | 8.21% | 6.88% | 7.42% | 6.36% |
| 10 | 1000+ | 0.6+ | 0–35 | 36–75 | Purified fresh air240 | 60 | 0.584 | 33.33% | 80.44% | 56.89% | 66.31% | 47.46% |
| 11 | 1000- | 0.6- | 36–75 | 36–75 | Purified fresh air400 | 60 | 0.690 | 33.33% | 95.04% | 64.19% | 76.53% | 51.84% |
| 12 | 1000+ | 0.6- | 76–115 | 36–75 | purifier+ and window- | 180+ | 0.712+ | 100.00% | 98.07% | 99.04% | 98.65% | 99.42% |
| 13 | 1000- | 0.6- | 0–35 | 76–115(3) | Purified fresh air400 | 0+ | 0.039* | 5.56% | 5.37% | 5.46% | 5.43% | 5.50% |
| 14 | 1000+ | 0.6- | 0–35 | 76–115 | purifier+ and window- | 180+ | 0.726+ | 100.00% | 100.00% | 100.00% | 100.00% | 100.00% |
| 15 | 1000+ | 0.6+ | 36–75 | 76–115 | Purified fresh air240 | 60 | 0.271 | 33.33% | 37.33% | 35.33% | 36.13% | 34.53% |
| 16 | 1000- | 0.6+ | 76–115 | 76–115 | purifier+ and window+ | 35 | 0.192 | 19.44% | 26.45% | 22.95% | 24.35% | 21.54% |
| 17 | 1000- | 0.6- | 0–35 | 0–35 | Close the window | contrast | 0.251* | 5.56% | 34.57% | 20.06% | 25.87% | 14.26% |
Fig 1Flowchart of the methods section.
Fig 2Experimental platform and monitoring points.
Indoor and outdoor concentration distribution of CO2, VOCs, and PM2.5 in office buildings.
| Pollutants | Indoor pollutant concentration distribution | Concentration difference between indoor and outdoor | |
|---|---|---|---|
| Normal situation | Abnormal situation | ||
|
| The CO2 is commonly 400–600 ppm. | Many high values appeared in the conference room which can reach 1500 ppm, and 2000 ppm once occurred. | The indoor CO2 is higher than the outdoor CO2. |
|
| The VOCs in single-person office in summer exceeds the standard during non-working hours and significantly exceeds the standard throughout the day in winter. | The VOCs in single-person office in winter can reach up to 1.2 mg/m3. | - |
|
| The PM2.5 is commonly 20–90 μg/m3. | Abnormal values mostly appear in multi-person office during working hours in summer and autumn, which can reach 100–300 μg/m3. The concentration of PM2.5 also exceeded 100 μg/m3 in single-person room in winter. | In summer and autumn, the outdoor PM2.5 is higher than indoors (the concentration difference is about 35 μg/m3), but the indoor PM2.5 in winter is higher than outdoors (the concentration difference is about 70 μg/m3). |
a Due to equipment placement problems, outdoor VOCs monitoring data is unreliable.
Fig 3Comparison of the control methods under a single pollutant condition.
(A) Indoor CO2 exceeding the standard. (B) Indoor VOCs exceeding the standard. (C) Indoor PM2.5 at a good level. (D) Indoor PM2.5 at a light pollution level. (E) Indoor PM2.5 concentration when outdoor PM2.5 exceeds the standard. (F) Outdoor PM2.5 concentration when outdoor PM2.5 exceeds the standard.
Comparison of control time required for binary pollutants.
| Binary pollutants | Control method | Control time |
|---|---|---|
|
| purifier+ and window+ | 20 min |
| Purified fresh air | 40–60 min | |
| purifier+ and window- | - | |
|
| purifier+ and window+ | 25 min |
| Purified fresh air | 60 min | |
|
| purifier+ and window+ | 10 min |
| Purified fresh air | 35 min | |
| purifier+ and window- | 50 min | |
|
| purifier+ and window+ | 25 min |
| Purified fresh air 240 | 5 min/30 min | |
|
| Purified fresh air | 15 min |
| purifier+ and window- | 25 min | |
| purifier+ and window+ | - |
a The absence of a number after the purified fresh air means that there is little difference in the control time between the two air volumes.
Energy consumption levels required by the four control methods under the same IAQ control requirements.
| Control method | Energy consumption kW·h/10 min | Average energy consumption kW·h/10 min | |||
|---|---|---|---|---|---|
| CO2 | VOCs | Indoor PM2.5 | Outdoor PM2.5 | ||
|
| 0.029 | 0.021 | 0.032 | 0.021 | 0.026 |
|
| 0.071 | 0.071 | 0.025 | 0.071 | 0.060 |
|
| 0.072 | 0.072 | 0.080 | 0.061 | 0.071 |
|
| 0.120 | 0.035 | 0.073 | 0.120 | 0.087 |
Recommended control methods.
| Condition | CO2 | VOCs | Indoor PM2.5 | Outdoor PM2.5 | Recommended control methods | Minimum control time | Control methods for optimal energy consumption |
|---|---|---|---|---|---|---|---|
|
| 1000- | 0.6- | 0–35 | 0–35 | open the window | - | - |
|
| 1000+ | 0.6- | 0–35 | 0–35 | purifier+ and window+ | 20 min | |
|
| 1000- | 0.6+/ | 0–35 | 0–35 | purifier+ and window+ | 10 min | |
|
| 1000- | 0.6- | 36-75/ | 0–35 | purifier+ and window+/fresh air 240 | 8 min | purified fresh air |
|
| 1000- | 0.6- | 76-115/80 | 0–35 | fresh air 240 | 15 min | |
|
| 1000- | 0.6- | 0–35 | 36-75/ | purified fresh air /Purifier | - | purifier+ and window- |
|
| 1000- | 0.6- | 0–35 | 76-115/ | purified fresh air | - | purifier+ and window- |
|
| 1000+ | 0.6+ | 0–35 | 0–35 | purifier+ and window+ | 20 min | |
|
| 1000+ | 0.6- | 36–115 | 0–35 | purifier+ and window+ | 25 min | |
|
| 1000- | 0.6+ | 36–75 | 0–35 | purifier+ and window+/fresh air | 10 min/ | fresh air b |
|
| 1000- | 0.6+ | 76–115 | 0–35 | purifier+ and window+/fresh air | 15 min/ | fresh air |
|
| 1000- | 0.6+ | 0–35 | 36–115 | Purified fresh air 240 | 35 min | |
|
| 1000- | 0.6- | 36–75 | 36–115 | purifier+ and window- | 25 min/ | purified fresh air 240 |
|
| 1000- | 0.6- | 76–115 | 36–115 | purifier+ and window-/ | 25 min/ | purifier+ and window- |
|
| 1000+ | 0.6+ | 36–115 | 0–35 | purifier+ and window+ | 30 min | |
|
| 1000+ | 0.6+ | 0–35 | 36–75 | purifier+ and window+ | 30 min | |
|
| 1000+ | 0.6+ | 36–75 | 76–115 | purified fresh air 240 | 60 min |
a "Purified fresh air" means that the ventilation volume is not less than the rated fresh air volume in the HVAC system design standard.
b "Fresh air" means that the fresh air is induced without high efficiency filtration.