Antonio Doménech-Sánchez1,2,3, Elena Laso1, Clara I Berrocal1, Sebastián Albertí2,3.
Abstract
BackgroundLegionnaires' disease is a respiratory illness often associated with hotels and travel. Spain is a major tourist destination and one of the European countries with most cases of Legionnaires' disease , both community- and travel-associated. However, the prevalence of Legionella in tourist facilities is unknown.AimThe present investigation aimed to survey the tourist facilities in the Balearic Islands, Spain, for Legionella prevalence.MethodsWe visited tourist facilities in the Balearic Islands in two different periods (2006-2010 and 2015-2018) and took water samples following national and international guidelines. Legionella was investigated by culture methods following international standards (ISO 11731:1998).ResultsWe evaluated 13,472 samples from 465 facilities. Bacteria of the Legionella genus were detected in 65.4% of the surveyed facilities. Contamination of the facilities was significantly higher during the second decade (54.5 vs 78.6%). The most frequent colonisers were L. pneumophila serogroup 2-14. We detected the pathogen in 15.9% and 6.9% of hot and cold water distribution systems samples, respectively. The Legionella contamination rate in cold water systems samples was higher when free chlorine levels were < 0.2 mg/L and at > 25 °C temperatures, while in the hot water systems samples, the contamination rate was higher at < 50 °C. Of the samples from hot tubs, 10.9% were contaminated.ConclusionLegionella prevalence in hotels in the Balearic Islands was high but the contamination rates depended on the installations. Corrective measures are still needed to improve Legionella control.Entities:
Keywords: Legionella; Legionnaires’ disease; cold water; hot water; hotel; surveillance; tourist; whirlpool
Mesh:
Substances:
Year: 2022 PMID: 35621000 PMCID: PMC9137269 DOI: 10.2807/1560-7917.ES.2022.27.21.2100769
Source DB: PubMed Journal: Euro Surveill ISSN: 1025-496X
Characteristics of Legionella contamination in the investigated facilities, Balearic Islands, Spain, 2006–2010 and 2015–2018 (n = 465 facilities)
| Parameter | Entire study | First period (2006–2010) | Second period (2015–2018) | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| n | % | log CFU/L | n | % | log CFU/L | n | % | log CFU/L | ||||
| Mean | Range | Mean | Range | Mean | Range | |||||||
| Hotelsa | n = 465 | n = 319 | n = 210 | |||||||||
| Not contaminated by Lspp | 161 | 34.6 | NA | 145 | 45.5 | NA | 45 | 21.4 | NA | |||
| Contaminated by Lspp | 304 | 65.4 | 2.68 | 0.5–5.6 | 174 | 54.5 | 2.84 | 1.3–4.9 | 165 | 78.6 | 2.51 | 0.5–5.6 |
| One single species/serogroup | 153 | 32.9 | 2.65 | 0.5–5.3 | 122 | 38.2 | 2.84 | 1.3–4.9 | 56 | 26.7 | 2.53 | 0.5–5.6 |
| LP1 | 50 | 10.8 | 2.83 | 0.9–5.0 | 39 | 12.2 | 2.86 | 1.3–4.7 | 17 | 8.1 | 2.54 | 0.5–5.1 |
| LP2–14 | 93 | 20.0 | 2.75 | 0.5–5.3 | 75 | 23.5 | 2.85 | 1.3–4.9 | 37 | 17.6 | 2.49 | 0.5–5.6 |
| LnP | 10 | 2.2 | 2.17 | 1.3–4.6 | 8 | 2.5 | 2.64 | 1.3–4.9 | 2 | 1.0 | 2.58 | 0.5–5.0 |
| Several species/serogroups | 151 | 32.5 | 2.74 | 0.5–5.6 | 52 | 16.3 | 2.82 | 1.3–4.9 | 109 | 51.9 | 2.54 | 0.5–5.6 |
| LP1 + LP2–14 | 76 | 16.3 | 2.56 | 0.5–5.6 | 20 | 6.3 | 2.77 | 1.3–4.9 | 61 | 29.0 | 2.49 | 0.5–5.6 |
| LP1 + LnP | 10 | 2.2 | 2.77 | 1.3–4.6 | 9 | 2.8 | 2.81 | 1.3–4.7 | 4 | 1.9 | 2.63 | 1.3–4.0 |
| LP2–14 + LnP | 22 | 4.7 | 2.84 | 0.5–4.7 | 16 | 5.0 | 2.78 | 1.3–4.7 | 10 | 4.8 | 2.58 | 0.5–4.6 |
| LP1 + LP2–14 + LnP | 43 | 9.2 | 2.68 | 0.5–5.1 | 7 | 2.2 | 3.04 | 1.3–4.9 | 34 | 16.2 | 2.58 | 0.5–5.1 |
| Samples | n = 13,472 | n = 7,113 | n = 6,359 | |||||||||
| Not contaminated by Lspp | 11,807 | 87.6 | NA | 6,311 | 88.7 | NA | 5,496 | 86.4 | NA | |||
| Contaminated by Lspp | 1,665b | 12.4 | 2.67 | 0.5–5.6 | 802b | 11.3 | 2.84 | 1.3–4.9 | 863 | 13.6 | 2.51 | 0.5–5.6 |
| LP1 | 567 | 4.2 | 2.70 | 0.5–5.1 | 269 | 3.8 | 2.87 | 1.3–4.7 | 298 | 4.7 | 2.54 | 0.5–5.1 |
| LP2–14 | 966 | 7.2 | 2.70 | 0.5–5.6 | 476 | 6.7 | 2.84 | 1.3–4.9 | 490 | 7.7 | 2.49 | 0.5–5.6 |
| LnP | 138 | 1.0 | 2.60 | 0.5–5.0 | 63 | 0.9 | 2.70 | 1.3–4.9 | 75 | 1.2 | 2.58 | 0.5–5.0 |
Lspp: bacteria of the genus Legionella; LP1: Legionella pneumophila serovar 1; LP2–14: L. pneumophila serovar 2–14; LnP: Legionella non-pneumophila ; NA: not applicable.
a Sixty-three hotels were visited in both periods.
b Six samples were contaminated by Legionella from two different groups.
Characteristics of Legionella contamination in the hot water distribution systems of investigated hotels, Balearic Islands, Spain, 2006–2010 and 2015–2018 (n = 453 hotelsa)
| Parameter | Hotels | Samples | ||||||
|---|---|---|---|---|---|---|---|---|
| n | % | log CFU/L | n | % | log CFU/L | |||
| Mean | Range | Mean | Range | |||||
| Circuits | ||||||||
| Number | n = 448 | n = 4,345 | ||||||
| Not contaminated by Lspp | 225 | 50.2 | NA | 3,667 | 84.4 | NA | ||
| Contaminated by Lspp | 223 | 49.8 | 2.58 | 0.5–5.3 | 678 | 15.6 | 2.58 | 0.5–5.3 |
|
|
|
|
|
|
|
|
|
|
| LP1 | 43 | 9.6 | 2.81 | 0.9–5.0 | 204 | 4.7 | 2.62 | 0.9–5.1 |
| LP2–14 | 98 | 21.9 | 2.63 | 0.5–5.3 | 425 | 9.8 | 2.56 | 0.5–5.3 |
| LnP | 8 | 1.8 | 2.44 | 1.3–3.3 | 46 | 1.1 | 2.54 | 0.5–4.5 |
|
|
|
|
|
|
|
|
|
|
| LP1 + LP2–14 | 40 | 8.9 | 2.41 | 0.5–4.9 | 1 | 0.0 | 2.67 | 2.67 |
| LP1 + LnP | 1 | 0.2 | 2.16 | 2.16 | 0 | 0.0 | NA | |
| LP2–14 + LnP | 11 | 2.5 | 2.78 | 0.5–4.6 | 2 | 0.0 | 2.65 | 0.9–5.3 |
| LP1 + LP2–14 + LnP | 22 | 4.9 | 2.51 | 0.5–5.1 | 0 | 0.0 | NA | |
| Tanks | n = 397 | n = 3,098 | ||||||
| Not contaminated by Lsppa | 205 | 51.6 | NA | 2,594 | 83.7 | NA | ||
| Contaminated by Lspp | 192 | 48.4 | 3.01 | 0.5–5.6 | 504 | 16.3 | 3.01 | 0.5–5.6 |
|
|
|
|
|
|
|
|
|
|
| LP1 | 45 | 11.3 | 3.09 | 1.3–5.1 | 165 | 5.3 | 3.01 | 0.5–5.6 |
| LP2–14 | 86 | 21.7 | 3.01 | 1.3–5.6 | 292 | 9.4 | 3.03 | 1.3–5.6 |
| LnP | 7 | 1.8 | 2.71 | 1.3–4.6 | 44 | 1.4 | 2.93 | 0.5–5.0 |
|
|
|
|
|
|
|
|
|
|
| LP1 + LP2–14 | 31 | 7.8 | 2.96 | 1.3–4.9 | 3 | 0.1 | 3.20 | 2.9–3.2 |
| LP1 + LnP | 5 | 1.3 | 3.30 | 0.5–4.9 | 0 | 0.0 | NA | |
| LP2–14 + LnP | 13 | 3.3 | 3.01 | 1.3–4.7 | 0 | 0.0 | NA | |
| LP1 + LP2–14 + LnP | 5 | 1.3 | 3.00 | 1.1–5.0 | 0 | 0.0 | NA | |
| Total | ||||||||
| Number | n = 453 | n = 7,443 | ||||||
| Not contaminated by Lsppa | 181 | 40.0 | NA | 6,261 | 84.1 | NA | ||
| Contaminated by Lspp | 272 | 60.0 | 2.76 | 0.5–5.6 | 1,182 | 15.9 | 2.76 | 0.5–5.6 |
|
|
|
|
|
|
|
|
|
|
| LP1 | 45 | 9.9 | 3.00 | 0.9–5.0 | 369 | 5.0 | 2.80 | 0.5–5.1 |
| LP2–14 | 101 | 22.3 | 2.76 | 0.5–5.3 | 717 | 9.6 | 2.76 | 0.5–5.6 |
| LnP | 9 | 2.0 | 2.81 | 1.3–4.6 | 90 | 1.2 | 2.72 | 0.5–5.0 |
|
|
|
|
|
|
|
|
|
|
| LP1 + LP2–14 | 65 | 14.3 | 2.70 | 0.5–5.6 | 4 | 0.1 | 3.07 | 2.7–3.2 |
| LP1 + LnP | 6 | 1.3 | 2.96 | 1.3–4.6 | 0 | 0.0 | NA | |
| LP2–14 + LnP | 18 | 4.0 | 2.95 | 0.5–4.9 | 2 | 0.0 | 2.65 | 0.9–5.3 |
| LP1 + LP2–14 + LnP | 28 | 6.2 | 2.65 | 0.5–5.1 | 0 | 0.0 | NA | |
Lspp: bacteria of the genus Legionella; LP1: Legionella pneumophila serovar 1; LP2–14: Legionella pneumophila serovar 2–14; LnP: Legionella non-pneumophila.
a In five of the total 458 facilities, only the cold water distribution system was sampled these are therefore not included in this analysis of the hot water systems.
Characteristics of Legionella contamination in the cold water distribution systems of investigated hotels, Balearic Islands, Spain, 2006–2010 and 2015–2018 (n = 448 hotels)
| Parameter | Hotels | Samples | ||||||
|---|---|---|---|---|---|---|---|---|
| n | % | logCFU/L | n | % | log CFU/L | |||
| Mean | Range | Mean | Range | |||||
| Circuits | ||||||||
| Number | n = 447a | n = 3,306 | ||||||
| Not contaminated by Lspp | 299 | 66.9 | NA | 3,037 | 91.9 | NA | ||
| Contaminated by Lspp | 148 | 33.1 | 2.41 | 0.5–4.7 | 269 | 8.1 | 2.40 | 0.5–4.7 |
| One single species/serogroup | 120 | 26.8 | 2.68 | 0.5–5.6 | 268 | 8.1 | 2.42 | 0.5–4.7 |
| LP1 | 40 | 8.9 | 2.65 | 0.9–5.0 | 102 | 3.1 | 2.50 | 0.9–4.7 |
| LP2–14 | 67 | 15.0 | 2.70 | 0.5–5.6 | 146 | 4.4 | 2.39 | 0.5–4.6 |
| LnP | 13 | 2.9 | 2.70 | 0.5–5.1 | 20 | 0.6 | 2.13 | 1.3–3.9 |
| Several species/serogroups | 28 | 6.3 | 2.70 | 0.5–5.1 | 1 | 0.0 | 2.85 | 2.85 |
| LP1 + LP2–14 | 22 | 4.9 | 2.70 | 0.5–4.9 | 0 | 0.0 | NA | |
| LP1 + LnP | 1 | 0.2 | 2.89 | 2.89 | 0 | 0.0 | NA | |
| LP2–14 + LnP | 4 | 0.9 | 2.65 | 0.8–5.1 | 1 | 0.0 | 2.85 | 2.85 |
| LP1 + LP2–14 + LnP | 1 | 0.2 | 2.62 | 2.62 | 0 | 0.0 | NA | |
| Tanks | ||||||||
| Number | n = 344 | n = 1,048 | ||||||
| Not contaminated by Lspp | 317 | 92.2 | NA | 1,017 | 97.0 | NA | ||
| Contaminated by Lspp | 27 | 7.8 | 2.61 | 0.7–4.9 | 31 | 3.0 | 2.62 | 0.5–4.9 |
| One single species/serogroup | 25 | 7.3 | 2.47 | 0.5–5.1 | 31 | 3.0 | 2.62 | 0.5–4.9 |
| LP1 | 12 | 3.5 | 2.45 | 0.5–5.10 | 14 | 1.3 | 2.69 | 1.3–4.9 |
| LP2–14 | 9 | 2.6 | 2.47 | 0.5–4.9 | 11 | 1.0 | 2.40 | 0.5–3.5 |
| LnP | 4 | 1.2 | 2.52 | 0.5–4.6 | 6 | 0.6 | 2.87 | 1.3–4.2 |
| Several species/serogroups | 2 | 0.6 | 3.05 | 2.9–3.2 | 0 | 0.0 | NA | |
| LP1 + LP2–14 | 0 | 0.0 | NA | 0 | 0.0 | NA | ||
| LP1 + LnP | 1 | 0.3 | 2.9 | 2.9 | 0 | 0.0 | NA | |
| LP2–14 + LnP | 1 | 0.3 | 3.2 | 3.2 | 0 | 0.0 | NA | |
| LP1 + LP2–14 + LnP | 0 | 0.0 | NA | 0 | 0.0 | NA | ||
| Total | ||||||||
| Number | n = 448 | n = 4,354 | ||||||
| Not contaminated by Lspp | 288 | 64.3 | NA | 4,054 | 93.1 | NA | ||
| Contaminated by Lspp | 160 | 35.7 | 2.43 | 0.5–4.9 | 300 | 6.9 | 2.43 | 0.5–4.9 |
| One single species/serogroup | 126 | 28.1 | 2.63 | 0.5–5.6 | 299 | 6.9 | 2.43 | 0.5–4.9 |
| LP1 | 45 | 10.0 | 2.58 | 0.5–5.0 | 116 | 2.7 | 2.52 | 0.9–4.9 |
| LP2–14 | 68 | 15.2 | 2.68 | 0.5–5.6 | 157 | 3.6 | 2.39 | 0.5–4.6 |
| LnP | 13 | 2.9 | 2.56 | 0.5–4.6 | 26 | 0.6 | 2.30 | 1.3–4.2 |
| Several species/serogroups | 34 | 7.6 | 2.70 | 0.5–5.1 | 1 | 0.0 | 2.85 | 2.85 |
| LP1 + LP2–14 | 22 | 4.9 | 2.66 | 0.5–4.9 | 0 | 0.0 | NA | |
| LP1 + LnP | 3 | 0.7 | 2.96 | 0.7–5.1 | 0 | 0.0 | NA | |
| LP2–14 + LnP | 4 | 0.9 | 2.59 | 0.5–4.9 | 1 | 0.0 | 2.85 | 2.85 |
| LP1 + LP2–14 + LnP | 5 | 1.1 | 2.84 | 1.3–5.1 | 0 | 0.0 | NA | |
Lspp: bacteria of the genus Legionella; LP1: Legionella pneumophila serovar 1; LP2–14: Legionella pneumophila serovar 2–14 ; LnP: Legionella non-pneumophila.
a For some hotels not all the installations were sampled.
Figure 1Relationship between free chlorine levels in cold water distribution systems and Legionella contamination, Balearic Islands, Spain, 2006–2010 and 2015–2018 (n = 4,156 samples)a
Figure 2Relationship between the water temperature and Legionella contamination, Balearic Islands, Spain, 2006–2010 and 2015–2018 (n = 11,797 samples)
Characteristics of Legionella contamination in the hot tubs from the investigated hotels, Balearic Islands, Spain, 2006–2010 and 2015–2018 (n = 227)
| Parameter | Hotels | Samples | ||||||
|---|---|---|---|---|---|---|---|---|
| n | % | logCFU/L | n | % | logCFU/L | |||
| Mean | Range | Mean | Range | |||||
| Number | n = 227 | n = 1,675 | ||||||
| Not contaminated by Lspp | 126 | 55.5 | NA | 1,492 | 89.1 | NA | ||
| Contaminated by Lspp | 101 | 44.5 | 2.45 | 0.5–4.6 | 183 | 10.9 | 2.45 | 0.5–4.6 |
| One single species/serogroup | 76 | 33.5 | 2.37 | 0.8–4.6 | 183 | 10.9 | 2.37 | 0.8–4.6 |
| LP1 | 34 | 15.0 | 2.47 | 0.8–4.6 | 78 | 4.7 | 2.48 | 0.4–4.6 |
| LP2–14 | 35 | 15.4 | 2.31 | 1.3–3.8 | 85 | 5.1 | 2.40 | 1.3–4.3 |
| LnP | 7 | 3.1 | 2.14 | 1.3–3.7 | 20 | 1.2 | 2.53 | 1.3–4.6 |
| Several species/serogroups | 25 | 11.0 | 2.55 | 0.5–4.6 | 0 | 0.0 | NA | |
| LP1 + LP2–14 | 15 | 6.6 | 2.46 | 0.5–4.2 | 0 | 0.0 | NA | |
| LP1 + LnP | 4 | 1.8 | 2.70 | 2.0–3.7 | 0 | 0.0 | NA | |
| LP2–14 + LnP | 2 | 0.9 | 2.61 | 0.7–3.4 | 0 | 0.0 | NA | |
| LP1 + LP2–14 + LnP | 4 | 1.8 | 2.70 | 1.3–4.6 | 0 | 0.0 | NA | |
Lspp: bacteria of the genus Legionella; LP1: Legionella pneumophila serovar 1; LP2–14: Legionella pneumophila serovar 2–14; LnP: Legionella non-pneumophila.