Required water temperature in hotel plumbing to control Legionella growth.

Md Rasheduzzaman1, Rajveer Singh2, Charles N Haas2, Patrick L Gurian2.   

Abstract

Legionella spp. occurring in hotel hot water systems, in particular Legionella pneumophila, are causing serious pneumonic infections, and water temperature is a key factor to control their occurrence in plumbing systems. We performed a systematic review and meta-analyses of the available evidence on the association between water temperature and Legionella colonization to identify the water temperature in hotel hot water systems required for control of Legionella. Qualitative synthesis and quantitative analysis were performed on 13 studies that met our inclusion criteria to identify the effect of temperature. The Receiver Operating Characteristic (ROC) curve identified 55 °C as a cutoff point for hotel hot water temperature with an Area Under the Curve (AUC) value of 0.914. The odds ratios (OR) for detecting Legionella at temperatures >55 °C compared to lower temperatures from a meta-analysis of three studies was 0.17 [95% CI: 0.11, 0.25], which indicates a strong negative association between temperature and Legionella colonization. A logistic regression on results from multiple studies using both molecular and culture methods found a temperature of 59 °C associated with an 8% probability of detectable Legionella. Only two studies reported sufficiently detailed data to allow a model of concentration vs. temperature to be fit, and this model was not statistically significant. Additional research or more detailed reporting of existing datasets is required to assess if Legionella growth can be limited below particular concentration targets at different temperatures.
Copyright © 2020 Elsevier Ltd. All rights reserved.

Entities:  

Keywords:  Hot water systems; Hotel; Legionella; Premise plumbing; Temperature; Water heater

Mesh:

Substances:

Year:  2020        PMID: 32590203     DOI: 10.1016/j.watres.2020.115943

Source DB:  PubMed          Journal:  Water Res        ISSN: 0043-1354            Impact factor:   11.236


  6 in total

1.  Legionella pneumophila Risk from Cooling Tower Systems in China.

Authors:  Tian Qin; Dahui Zhao; Li Zhu; Hongyu Ren; Yinan Li; Xinjun Liu; Xiaopeng Li; Wei Li; Na Zhao; Jiao Lu; Di Liu; Yi Shi; Min Fang; Xuefeng Duan
Journal:  Appl Environ Microbiol       Date:  2021-11-24       Impact factor: 5.005

2.  Environmental surveillance of Legionella in tourist facilities of the Balearic Islands, Spain, 2006 to 2010 and 2015 to 2018.

Authors:  Antonio Doménech-Sánchez; Elena Laso; Clara I Berrocal; Sebastián Albertí
Journal:  Euro Surveill       Date:  2022-05

Review 3.  Legionellosis Caused by Non-Legionella pneumophila Species, with a Focus on Legionella longbeachae.

Authors:  Stephen T Chambers; Sandy Slow; Amy Scott-Thomas; David R Murdoch
Journal:  Microorganisms       Date:  2021-01-31

4.  Low Efficacy of Periodical Thermal Shock for Long-Term Control of Legionella spp. in Hot Water System of Hotels.

Authors:  Jhon J Molina; Magdalena Bennassar; Edwin Palacio; Sebastian Crespi
Journal:  Pathogens       Date:  2022-01-25

5.  Assessing Hotel Employee Knowledge on Risk Factors and Risk Management Procedures for Microbial Contamination of Hotel Water Distribution Systems.

Authors:  Brandon Leftwich; Samuel Opoku; Jingjing Yin; Atin Adhikari
Journal:  Int J Environ Res Public Health       Date:  2021-03-29       Impact factor: 3.390

6.  Dynamics of Legionella Community Interactions in Response to Temperature and Disinfection Treatment: 7 Years of Investigation.

Authors:  Luna Girolamini; Silvano Salaris; Maria Rosaria Pascale; Marta Mazzotta; Sandra Cristino
Journal:  Microb Ecol       Date:  2021-06-05       Impact factor: 4.552

  6 in total