| Literature DB >> 35235233 |
Patrick N McDermott1, Michael D Sigler2, Ian P Lake1, Danielle Lack2.
Abstract
Primary barrier design for linac shielding depends very sensitively on tenth value layer (TVL) data. Inaccuracies can lead to large discrepancies between measured and calculated values of the barrier transmission. Values of the TVL for concrete quoted in several widely used standard references are substantially different than those calculated more recently. The older standard TVL data predict significantly lower radiation levels outside primary barriers than the more recently calculated values under some circumstances. The difference increases with increasing barrier thickness and energy, and it can be as large as a factor of 4 for 18 MV and concrete thickness of 200 cm. This may be due to significant differences in the beam spectra between the earlier and the more recent calculations. Measured instantaneous air kerma rates sometimes show large variations for the same energy and thickness. This may be due to confounding factors such as extra material on, or inside the barrier, variable field size at the barrier, density of concrete, and distal distance from the barrier surface. In some cases, the older TVL data significantly underestimate measured instantaneous air kerma rates, by up to a factor of 3, even when confounding factors are taken into account. This could lead to the necessity for expensive remediation. The more recent TVL values tend to overestimate the measured instantaneous dose rates. Reference TVL data should be computed in a manner that is mathematically consistent with their use in the calculation of air kerma rate outside barriers directly from the linac "dose" rate in MU/min.Entities:
Keywords: TVL; linac; primary barrier; transmission
Mesh:
Year: 2022 PMID: 35235233 PMCID: PMC8992934 DOI: 10.1002/acm2.13574
Source DB: PubMed Journal: J Appl Clin Med Phys ISSN: 1526-9914 Impact factor: 2.102
Tenth value layer (TVL) data for concrete
| NCRP151/IPEM75 | Karoui and Kharrati (2013) | IAEA47 | Jaradat and Biggs (2007) | |||||
|---|---|---|---|---|---|---|---|---|
| Energy (MV) | TVL1 (cm) | TVLe (cm) | TVL1 (cm) | TVLe (cm) | TVL (cm) | TVL1 (cm) | TVL2 (cm) | TVL3 (cm) |
| 4 | 35 | 30 | 29.66 | 27.59 | 29.0 | 36.5 | 26.5 | 27.5 |
| 6 | 37 | 33 | 33.91 | 33.07 | 34.3 | 40.0 | 31.5 | 34.5 |
| 10 | 41 | 37 | 41.40 | 40.18 | 38.9 | 50.5 | 39.0 | 40.0 |
| 15 | 44 | 41 | 43.80 | 42.85 | 43.2 | 53.0 | 43.0 | 44.0 |
| 18 | 45 | 43 | 46.72 | 45.22 | 44.5 | 58.0 | 44.0 | 48.0 |
Abbreviations: IAEA47, IAEA Report No. 47; IPEM75, IPEM Report No. 75; NCRP151, NCRP Report No. 151.
12° opening half angle, distal distance from barrier wall is 0.3 m.
FIGURE 1Relative dependence of barrier transmission on field size (length of the side of the equivalent square) for beams with d w = 0.3 m based on the Jaradat and Biggs (JB) data for tenth value layer (TVL). Values are normalized to a field size of 9.3 cm (half opening angle of 3°). This is for a concrete thickness of 150 cm. Low‐energy beams show the largest field size dependence. The barrier transmission is up to two to three times larger for the largest field sizes compared to a 9.3 × 9.3 cm2 field
FIGURE 2The ratio of the barrier transmission for the Jaradat and Biggs (JB) tenth value layer (TVL) data relative to the NCRP Report No. 151 (NCRP151) data as a function of the thickness of the concrete. The JB data are for half beam opening angle 14° and d w = 0.3 m. The JB computed barrier transmission is larger than for NCRP151 for energies of 6 MV and above. The ratio increases with increasing concrete thickness. The ratio is as high as a factor of 4 for 18 MV and concrete thickness of 200 cm. The ratio is less than 1 for 4 MV and can be as small as 0.4 for a concrete thickness of 200 cm
FIGURE 3A modified version of Figure 3 from Rijken et al. showing a graph of the log of the 10 MV measured instantaneous dose rates (IDR) (in μSv/h) versus concrete thickness (in mm) for 27 barriers. The field size is 40 × 40 cm2 and all measured data have been normalized to a distance from the isocenter of 6 m and a dose rate at isocenter of 6.6 Gy/min. The predicted values of the IDR are also shown. The solid curve is for NCRP Report No. 151 (NCRP151), the dashed curve for IPEM Report No. 75 (IPEM75), and the dot dashed curve is for IAEA Report No. 47 (IAEA47). The red curve for the Jaradat and Biggs (JB) data (12° half opening angle, d w = 0.3 m) and the blue curve for the Karoui and Kharrati (K2) data have been added to the graph. There is a large spread in the IDR for different barriers of the same thickness. Although the NCRP prediction curve goes through the center of the measured values, it is clear that in many cases it significantly underestimates the measured IDR. The JB tenth value layer (TVL) data always overestimate the measured IDR
Comparison between measured and predicted instantaneous dose rates (IDR)
| Barrier | Thickness (cm) | Distance (m) | Energy | Rep rate (MU/min) | NCRP151 (mrem/h) | JB (mrem/h) | K2 | Measured (mrem/h) | Measured/NCRP151 | Measured/JB | Measured/K2 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Northwest (interior wall), Lenox | 183 | 8.3 | 15 | 706 | 33 | 67 | 45 | 58 | 1.8 | 0.86 | 1.3 |
| 10 | 585 | 9.9 | 29 | 20 | 22 | 2.2 | 0.75 | 1.1 | |||
| 6 | 572 | 2.6 | 3.2 | 2.1 | 5.3 | 2.0 | 1.6 | 2.5 | |||
| Northeast | 183 | 8.0 | 15 | 706 | 23 | 48 | 32 | 38.5 | 1.7 | 0.80 | 1.2 |
| 10 | 585 | 6.8 | 20 | 14 | 16 | 2.4 | 0.80 | 1.2 | |||
| 6 | 572 | 1.7 | 2.1 | 1.4 | 3.3 | 2.0 | 1.6 | 2.4 | |||
| Roof, Lenoxb | 168 | 6.0 | 15 | 706 | 141 | 283d | 187 | 155ds | 1.1 | 0.55 | 0.83 |
| 10 | 585 | 47 | 135 | 88 | 67 | 1.4 | 0.49 | 0.76 | |||
| 6 | 572 | 14 | 15 | 11 | 15.2 | 1.1 | 1.0 | 1.3 | |||
|
SL2 (34 × 34 cm2) | 216 | 6.6 | 18 | 499 | 5.9 | 17 | 10 | 8.5 | 1.5 | 0.51 | 0.85 |
| 6 | 485 | 0.20 | 0.27 | 0.17 | 0.30 | 1.5 | 1.1 | 1.9 |
Abbreviations: JB, Jaradat and Biggs; K2, Karoui and Kharrati; NCRP151, NCRP Report No. 151.
”Distance” is the distance from the target to a point 0.3 m beyond the distal surface of the barrier, except for roof.
Lenox corrected for measured concrete density.
For northeast wall a correction factor for the brick façade has been included.
For d w = 1.0 m.
SL2 there is a steel laser mounting plate approximately 1 cm thick: B ∼ 0.8 for both 18 and 6 MV.