| Literature DB >> 31583125 |
Valerie Madera-García1, Alexis L Mraz2, Nicolás López-Gálvez1, Mark H Weir3, James Werner1, Paloma I Beamer1, Marc P Verhougstraete1.
Abstract
Legionella pneumophila (L. pneumophila), the causative agent of legionellosis, is an aquatic bacterium that grows in warm water. Humans are only presented with a health risk when aerosolized water containing L. pneumophila is inhaled. In mining operations, aerosolized water is used as dust control and as part of the drilling operations, a currently ignored exposure route. This study characterized L. pneumophila concentrations in the mine's non-potable water and the relationship between L. pneumophila and chlorine concentrations. These concentrations informed a quantitative microbial risk assessment (QMRA) model to estimate the infection risk to miners exposed to aerosolized water containing L. pneumophila. Fourteen water samples were collected from seven locations at a mine and analyzed for temperature, pH, chlorine, and L. pneumophila serogroup. Most samples (93%) tested positive for L. pneumophila cells. The faucet from the sprinkler system on the adit level (entrance to the underground mine levels) showed the highest concentration of L. pneumophila (8.35 × 104 MPN/L). Disability adjusted life years (DALYs) were estimated in the QMRA model and showed that the risk for all miners was significantly lower (p < 0.0001) with the ventilation system on than when the system was off. Our study showed that the use of a ventilation system at the adit level of the mine reduced the risk of infection with aerosolized L. pneumophila.Entities:
Keywords: DALYs (disability adjusted life years); Legionella pneumophila; QMRA; air quality ventilation; mining safety
Year: 2019 PMID: 31583125 PMCID: PMC6776080 DOI: 10.3390/w11081528
Source DB: PubMed Journal: Water (Basel) ISSN: 2073-4441 Impact factor: 3.103
Figure 1.Diagram of water distribution system and sampling sites at the studied mine.
Parameters used in the quantitative microbial risk assessment (QMRA) model.
| Label | Variable | Value | Unit | Distribution | Reference |
|---|---|---|---|---|---|
| Concentration of | 8.35 × 10−4 | Most probable number (MPN)/L | N/A | Results of this study | |
| Air partitioning coefficient | 10−5 | Unitless | N/A | [ | |
| Water volume released from the sprinkler system | 573 | L/s | N/A | Provided by the mine | |
| Fraction of aerosolized organisms | Mean: 0.0337 | Unitless | Normal | [ | |
| Area of the mine | 3.0 × 10−4 | L | N/A | Provided by the mine | |
| Volume of air removed by the ventilation fan | 5663 | L/s | N/A | Provided by the mine | |
| Concentration of | 4.65 × 10−4 | MPN/L | N/A | Results of this study | |
| Flow of water released from the jackleg drill | 573 | L/s | N/A | Provided by the mine | |
| Inhalation rate for male workers | Mean: 0.02333 | m3/min | Normal | [ | |
| Inhalation rate for female workers | Mean: 0.02083 | m3/min | Normal | [ | |
| Probability of the pathogen surviving to initiate infection in the host | −0.00599 | Unitless | N/A | [ | |
| Disability weight for Pontiac Fever (moderate) | Mean: 0.051 | Unitless | Triangular | [ | |
| Disability weight for Legionnaires′ disease (severe) | Mean: 0.125 | Unitless | Triangular | [ | |
| Disability weight for sequela (post-acute) | Mean: 0.217 | Unitless | Triangular | [ | |
Water and quality measurements and the concentration L. pneumophila in non-portable water sources.
| Sampling Location | Water temperature (°C) | Chlorine levels (mg/L) | Average Concentration of | Categories of Sampling Location by Mine Levels |
|---|---|---|---|---|
| Non-potable water tank | 23.6 | ND | 1.50 × 104 | Water Storage Level |
| Jackleg drill connection | 21.6 | ND | 4.65 × 104 | Adit Level |
| Sprinkler system | 21.1 | ND | 8.35 × 104 | Adit Level |
| Jackleg drill hose outside adit level | 30.9 | ND | 1.55 × 104 | Adit Level |
| Sink in hoist house | 19.0 | 0.05 | 2.50 × 104 | Exterior Level |
| Swamp cooler | 16.8 | 0.05 | 4.00 × 104 | Exterior Level |
| Jackleg drill hose in hoist house | 23.3 | ND | 2.50 × 104 | Exterior Level |
ND: Not detected.
Figure 2.Average L. pneumophila concentrations on water storage level (n = 1), adit level (n = 3), and exterior level (n = 3).
Figure 3.Moderate disability adjusted life years (DALYs) for male and female miners.
Figure 5.Sequela DALYs for male and female miners.