| Literature DB >> 31066046 |
J L Darbyshire1, M Müller-Trapet2, J Cheer3, F M Fazi3, J D Young1.
Abstract
Excessive noise in hospitals adversely affects patients' sleep and recovery, causes stress and fatigue in staff and hampers communication. The World Health Organization suggests sound levels should be limited to 35 decibels. This is probably unachievable in intensive care units, but some reduction from current levels should be possible. A preliminary step would be to identify principal sources of noise. As part of a larger project investigating techniques to reduce environmental noise, we installed a microphone array system in one with four beds in an adult general intensive care unit. This continuously measured locations and sound pressure levels of noise sources. This report summarises results recorded over one year. Data were collected between 7 April 2017 and 16 April 2018 inclusive. Data for a whole day were available for 248 days. The sound location system revealed that the majority of loud sounds originated from extremely limited areas, very close to patients' ears. This proximity maximises the adverse effects of high environmental noise levels for patients. Some of this was likely to be appropriate communication between the patient, their caring staff and visitors. However, a significant proportion of loud sounds may originate from equipment alarms which are sited at the bedside. A redesign of the intensive care unit environment to move alarm sounds away from the bed-side might significantly reduce the environmental noise burden to patients.Entities:
Keywords: ICU environment; alarms; monitors; noise
Mesh:
Year: 2019 PMID: 31066046 PMCID: PMC6767712 DOI: 10.1111/anae.14690
Source DB: PubMed Journal: Anaesthesia ISSN: 0003-2409 Impact factor: 6.955
Figure 1A heat map of the frequency with which one of the five loudest noises above 35 dB originated from each 1 cm2 of the intensive care unit bay for the 249‐day study period, superimposed on a floor plan of the bay. The position and identifier for each of the four beds in the bay is shown, as well as the work bench position. The area of noise marked ‘1’ is outside the side room that was preferentially used, and shows where conversations between staff about the patient in the side room commonly took place. The areas of noise marked ‘2’ correspond to the positions of the telephones. This can be interpreted as a map of the ‘noisiness’ of areas of the bay. The grid lines are an artefact of the computational methods.
Figure 2A heat map of the average loudness of noises above 35 dB originated from each 1 cm2 of the intensive care unit bay for the 249‐day study period, superimposed on a floor plan of the bay. The position and identifier for each of the four beds and the work bench in the bay is shown.
Figure 3A heat map of the frequency with which one of the five loudest noises above 35 dB originated from each 1 cm2 of the intensive care unit bay between 19h00 and 20h00 for the 249‐day study period, superimposed on a floor plan of the bay. The position of each of the four beds in the bay is shown, as well as the work bench position. The grid lines are an artefact of the computational methods. The counts are considerably lower than in Fig. 1, as this plot only represents 1/24th of the data in Fig. 1.
Figure 4A heat map of the frequency with which one of the five loudest noises above 35 dB originated from each 1 cm2 of the intensive care unit bay between 04h00 and 05h00 for the 249‐day study period, superimposed on a floor plan of the bay. The position of each of the four beds in the bay is shown, as well as the work bench position.