| Literature DB >> 30186646 |
Maria A Kyritsi1,2, Varvara A Mouchtouri1,2, Anna Katsiafliaka1,2, Foteini Kolokythopoulou2, Elias Plakokefalos1, Vasileios Nakoulas1, George Rachiotis1, Christos Hadjichristodoulou1,2.
Abstract
Healthcare-associated Legionnaires' disease often leads to fatal respiratory tract infection among hospitalized patients. In this report, three cases of Legionnaires' disease among patients in two different hospitals (Hospital A and Hospital B) were investigated. After conducting an epidemiologic and environmental investigation, the water distribution systems (WDSs) were identified as the possible source of infection, as Legionella pneumophila serogroup 1 (Lp1) was isolated from both clinical and environmental samples. Patients received aerosol therapy with nebulizers during their hospitalization. Based on the results of the investigation, the hospitals' infection control committees reviewed their policies for Legionnaires' disease prevention and implemented control measures focusing on using sterile fluids for aerosol treatments.Entities:
Year: 2018 PMID: 30186646 PMCID: PMC6114232 DOI: 10.1155/2018/2570758
Source DB: PubMed Journal: Case Rep Infect Dis
Microbiological analysis results of environmental samples for Legionella spp. detection from Hospital A.
| Hospital A | |||
|---|---|---|---|
| Sampling date | Sampling point | Result | |
| Culture (cfu/L) | SBT§ | ||
| 26th April | Cardiology department: shower head | 2 × 103 | — |
| Cardiology department: nebulizer, swab | Negative | — | |
| Cardiology department: drinking-water fountain | 100 | — | |
| Cardiology department: cardiology ICU's‡ water distribution system | Negative | — | |
|
| |||
| 18th May | Cardiology department: storage room, bathroom | 3 × 103 | ST-1: 1,4,3,1,1,1,1 |
| Cardiology department: room 542, swab ( | Negative | — | |
| Cardiology department: room 548, nebulizer, swab ( | Negative | — | |
| Cardiology department: drinking-water fountain | 2.3 × 104 | — | |
| Internal medicine department: room 510 | Negative | — | |
| Boiler number 6 | Negative | — | |
| Water softener outlet | Negative | — | |
| Cooling tower number 1 | Negative | — | |
| Cooling tower number 3 | 100 | — | |
|
| |||
| 6th September | Technical staff offices: drinking fountain | 2 × 103 | — |
| Cooling tower 1 | 9.6 × 104 | — | |
| Cooling tower 3 | 1.6 × 105 | — | |
| Cooling tower 5 | 5.9 × 104 | — | |
| Boiler number 1 | Negative | — | |
| Boiler number 2 | Negative | — | |
| Cardiology department: drinking-water fountain, swab | Negative | — | |
| Cardiology department: room 542, shower | 100 | — | |
| Internal medicine department: room 510 | Negative | — | |
| Internal medicine department: storage room (stagnant line) | 7.5 × 103 | ST-1: 1,4,3,1,1,1,1 | |
| Cardiology department: storage room (stagnant line) | Negative | — | |
Colony-forming units per liter; §sequence-based typing; ˚Legionella pneumophila serogroup; ‡intensive care unit.
Microbiological analysis results of environmental samples for Legionella spp. detection from Hospital B.
| Hospital B | |||
|---|---|---|---|
| Sampling date | Sampling point | Result | |
| Culture (cfu/L) | SBT§ | ||
| 23th February | Neurology department | Negative | — |
| Patients' room | 103 | ST-1: 1,4,3,1,1,1,1 | |
| Patients' |
| ST-1: 1,4,3,1,1,1,1 | |
Colony-forming units per liter; §sequence-based typing; ˚Legionella pneumophila serogroup.