Environmental cultures and hospital-acquired Legionnaires' disease: a 5-year prospective study in 20 hospitals in Catalonia, Spain.

Miquel Sabrià1, Josep M Mòdol, Marian Garcia-Nuñez, Esteban Reynaga, Maria L Pedro-Botet, Nieves Sopena, C Rey-Joly.   

Abstract

OBJECTIVE: To determine whether environmental cultures for Legionella increase the index of suspicion for legionnaires' disease (LD).
DESIGN: Five-year prospective study.
SETTING: Twenty hospitals in Catalonia, Spain.
METHODS: From 1994 to 1996, the potable water systems of 20 hospitals in Catalonia were tested for Legionella. Cases of hospital-acquired LD and availability of an "in-house" Legionella test in the previous 4 years were assessed. After the hospitals were informed of the results of their water cultures, a prospective 5-year-study was conducted focusing on the detection of new cases of nosocomial legionellosis and the availability and use of Legionella testing.
RESULTS: Before environmental cultures were started, only one hospital had conducted active surveillance of hospital-acquired pneumonia and used Legionella tests including Legionella urinary antigen in all pneumonia cases. Only one other hospital had used the latter test at all. In six hospitals, Legionella tests had been completely unavailable. Cases of nosocomial LD had been diagnosed in the previous 4 years in only two hospitals. During prospective surveillance, 12 hospitals (60%) used Legionella urinary antigen testing in house and 11 (55%) found cases of nosocomial legionellosis, representing 64.7% (11 of 17) of those with positive water cultures. Hospitals with negative water cultures did not find nosocomial LD.
CONCLUSIONS: The environmental study increased the index of suspicion for nosocomial LD. The number of cases of nosocomial LD increased significantly during the prospective follow-up period, and most hospitals began using the Legionella urinary antigen test in their laboratories.

Entities:  

Mesh:

Substances:

Year:  2004        PMID: 15636295     DOI: 10.1086/502346

Source DB:  PubMed          Journal:  Infect Control Hosp Epidemiol        ISSN: 0899-823X            Impact factor:   3.254


  11 in total

1.  Detection of legionella contamination in tabriz hospitals by PCR assay.

Authors:  Reza Ghotaslou; Fatemeh Yeganeh Sefidan; Mohammad Taghi Akhi; Mohammad Hussein Soroush; Mohammad Saeid Hejazi
Journal:  Adv Pharm Bull       Date:  2013-02-07

2.  A decision support system for preventing Legionella disease.

Authors:  Oya H Yüregir; Mustafa Oral; Olcay Kalan
Journal:  J Med Syst       Date:  2009-05-15       Impact factor: 4.460

3.  Environmental surveillance and molecular epidemiology of waterborne pathogen Legionella pneumophila in health-care facilities of Northeastern Greece: a 4-year survey.

Authors:  Ioanna G Alexandropoulou; Spyridon Ntougias; Theocharis G Konstantinidis; Theodoros A Parasidis; Maria Panopoulou; Theodoros C Constantinidis
Journal:  Environ Sci Pollut Res Int       Date:  2015-02-25       Impact factor: 4.223

4.  Reducing Legionella colonization in water systems with monochloramine.

Authors:  Brendan Flannery; Lisa B Gelling; Duc J Vugia; June M Weintraub; James J Salerno; Michael J Conroy; Valerie A Stevens; Charles E Rose; Matthew R Moore; Barry S Fields; Richard E Besser
Journal:  Emerg Infect Dis       Date:  2006-04       Impact factor: 6.883

5.  [Requirements for hygiene in the medical care of immunocompromised patients. Recommendations from the Committee for Hospital Hygiene and Infection Prevention at the Robert Koch Institute (RKI)].

Authors: 
Journal:  Bundesgesundheitsblatt Gesundheitsforschung Gesundheitsschutz       Date:  2010-04       Impact factor: 1.513

6.  Water Quality as a Predictor of Legionella Positivity of Building Water Systems.

Authors:  David Pierre; Julianne L Baron; Xiao Ma; Frank P Sidari; Marilyn M Wagener; Janet E Stout
Journal:  Pathogens       Date:  2019-12-13

7.  Distribution of Virulence Genes and Sequence-Based Types Among Legionella pneumophila Isolated From the Water Systems of a Tertiary Care Hospital in India.

Authors:  K Sreenath; Rama Chaudhry; E V Vinayaraj; A B Dey; S K Kabra; Bhaskar Thakur; Randeep Guleria
Journal:  Front Public Health       Date:  2020-11-23

8.  Evaluation of Recommended Water Sample Collection Methods and the Impact of Holding Time on Legionella Recovery and Variability from Healthcare Building Water Systems.

Authors:  Marisa B Hirsh; Julianne L Baron; Sue M Mietzner; John D Rihs; Mohamed H Yassin; Janet E Stout
Journal:  Microorganisms       Date:  2020-11-11

9.  Contamination of Hospital Water Supplies in Gilan, Iran, with Legionella pneumophila, Escherichia coli, and Pseudomonas aeruginosa.

Authors:  Masoumeh Ahmadi Jalali Moghadam; Hamidreza Honarmand; Sajad Asfaram Meshginshahr
Journal:  Interdiscip Perspect Infect Dis       Date:  2015-09-07

10.  Environmental surveillance of Legionella pneumophila in distal water supplies of a hospital for early identification & prevention of hospital-acquired legionellosis.

Authors:  Shihail Jinna; Ujjwala Nitin Gaikwad
Journal:  Indian J Med Res       Date:  2018-06       Impact factor: 2.375

View more

北京卡尤迪生物科技股份有限公司 © 2022-2023.