| Literature DB >> 36097587 |
M Justo Alonso1, T N Moazami2, P Liu3, R B Jørgensen2, H M Mathisen1.
Abstract
In this study, concentrations of pollutants: formaldehyde, carbon dioxide (CO2), and total volatile organic compounds (TVOC) and parameters: indoor room temperature and relative humidity (RH) were measured in 21 home offices for at least one week in winter in Trondheim, Norway. Eleven of these were measured again for the same duration in summer. Potentially explanatory variables of these parameters were collected, including building and renovation year, house type, building location, trickle vent status, occupancy, wood stove, floor material, pets, RH, and air temperature. The association between indoor air pollutants and their potential predictor variables was analyzed using generalized estimation equations to determine the significant parameters to control pollutants. Significantly seasonal differences in concentrations were observed for CO2 and formaldehyde, while no significant seasonal difference was observed for TVOC. For TVOC and formaldehyde, trickle vent, RH, and air temperature were among the most important predictor variables. Although higher concentrations of CO2 were measured in cases where the trickle vent was closed, the most important predictor variables for CO2 were season, RH, and indoor air temperature. The formaldehyde concentrations were higher outside working hours but mostly below health thresholds recommendations; for CO2, 11 of the measured cases had indoor concentrations exceeding 1000 ppm in 10% of the measured time. For TVOC, the concentrations were above the recommended values by WHO in 73% of the cases. RH was generally low in winter. The temperature was generally kept over the recommended level of 22-24 °C during working hours.Entities:
Keywords: CO2; Formaldehyde; General estimation equation; Low-cost sensor; RH; Room temperature; TVOC
Year: 2022 PMID: 36097587 PMCID: PMC9452402 DOI: 10.1016/j.buildenv.2022.109580
Source DB: PubMed Journal: Build Environ ISSN: 0360-1323 Impact factor: 7.093
Levels and recommendations for TVOC according to recommendations from WHO [32].
| Level | Recommendation | TVOC [ppm] |
|---|---|---|
| Outside quality classes | Not acceptable | >0.61 |
| 4 | Only temporary exposure | 0.2–0.61 |
| 3 | Harmless | 0.1–0.2 |
| 2 | 0.05–0.1 | |
| 1 | Target value | 0–0.05 |
EN 16798–1:2019 recommendations for CO2 concentrations above the outdoor level.
| Level | Category I | Category II | Category III | Remark |
|---|---|---|---|---|
| School (classroom) | 550 ppm | 800 ppm | 1350 ppm | Allowable ppm levels above outdoor levels |
| Office (landscape layout) | 550 ppm | 800 ppm | 1350 ppm | |
| Residential building (bedroom) | 380 ppm | 550 ppm | 950 ppm |
Summary of self-responded details of measured cases. The nomenclature corresponds to Type: Type of building where the measurements were performed, SDH: Semi-detached house, SFH: single-family house, A: Apartment, Floor: B: Basement, Room main use, Ba: Bathroom, K: Kitchen, S: Staircase, B: Bedroom, LR: Living room, HO: Home office, OK = open kitchen, K= Kitchen, Bdg. Loc: Building location in the city, CC: City centre, SNF: Suburban non-forested area, SF: suburban forested area, NV natural ventilation, EV: Exhaust ventilation, MV: Mechanical ventilation. Floor material: W-wooden flooring or cork; P-Parquets; C-carpet. Values in parentheses show summer status.
| ID | Construction year (renovation) | Type | Floor | Area (m2) | Maximum occupant density (m2/pers) | Room main use | Linked rooms | Bdg. loc | Ventilation | Wood Stove | Pets | Floor material | Trickle vent open? |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| A1 | 1952 (2007) | SFH | 2nd | 15 | 15 | HO | LR, B | CC | NV | Yes | Yes | P + C | No |
| A2 | 1900 (1995) | A | 3rd | 9.8 | 9.8 | HO | Ba | CC | NV + EV | No | No | W | No |
| A3 | 1900 (1995) | A | 2nd | 48 | 48 (24) | LR | K | CC | NV + EV | No | No | P + C | No |
| A4 | 2019 | SDH | 3rd | 15 | 15 | LR | S | SNF | MV | No | Yes | P + C | No |
| B5 | 1972 | SDH | 2nd | 5 | 5 | HO | B | SNF | NV | No | No | P | Yes |
| B6 | 1960(2000) | SFH | B | 4.5 | 4.5 | HO | LR, OK | SF | NV + EV | No | No | W | Yes |
| B7 | 1972 (2015) | A | 2nd | 40 | 40(8) | LR | OK | SNF | NV | Yes | No | W | No |
| B8 | 1890 (2019) | A | 1st | 15 | 15(5) | LR, B, OK | CC | NV | No | No | W | No | |
| C9 | 1970 (1997) | SDH | B | 32 | 32 | LR, K | B | SNF | NV | No | No | P | No |
| C10 | 1960(2000) | SFH | B | 4.5 | 4.5 | HO | LR, B | SF | NV + EV | No | No | P + C | Yes |
| C11 | 1964(2013) | SDH | 1st | 10.5 | 10.5 | B | Ba | SF | NV | No | No | W | Yes |
| D12 | 1947 (2013) | A | 1st | 38 | 38(9.5) | LR | OK | CC | NV | No | No | P | No |
| D13 | 1946 (2007) | MFH | 2nd | 18 | 18 (4.5) | LR | OK | SNF | NV + EV | Yes | No | P + C | No (Yes) |
| D14 | 1946 (2007) | MFH | 3rd | 8 | 8 | HO | B | SNF | NV | No | No | P | No |
| E15 | 1952 (2010) | SFH | 1st | 20 | 20 | HO | SF | MV | No | Yes | P | Yes | |
| E16 | 1989 | SHF | 1st | 23 | 23 (11.5) | B | SF | MV | No | No | W + C | Yes | |
| E17 | 1967 | SFH | 1st | 47 | 47(16) | LR | OK | SNF | NV | Yes | No | P | No |
| E18 | 1967 | SFH | 1st | 14 | 14 | B | SNF | NV | No | No | W | No | |
| F19 | 2019 | A | 3rd | 25 | 25 | LR, HO, OK | CC | MV | No | No | P | No | |
| F20 | 2019 | A | 3rd | 10 | 10 | B | LR | CC | MV | No | No | P | No |
| F21 | 1964 (2013) | SDH | 1st | 10.5 | 10.5 | B | SF | NV | No | No | P + C | Yes |
Properties of the low-cost sensors used.
| Sensor name | Parameter | Sensor type | Accuracy | Measurement range | Response time |
|---|---|---|---|---|---|
| Sensirion SCD30 [ | Relative humidity | Capacitive | ±3%RH at 25 °C | 0–100% | 8 s |
| Sensirion SCD30 [ | CO2 | Nondispersive infrared (NDIR) | ±30 ppm ± 3% (500–1500 ppm) | 400–10000 ppm | 20 s |
| Sensirion SCD30 [ | Temperature | 10 K NTC Thermistor | ± (0.4 °C + 0.023 x (T [°C] - 25 °C)) | −40 °C – 70 °C | >10 s |
| DART WZ-S formaldehyde module [ | Formaldehyde | Electrochemical sensor (MOS) | ≤0.02 ppm formaldehyde equivalent | 0.03–2 ppm | <40 s |
| Sensirion SVM30 [ | TVOC | Multi-pixel metal-oxide | 15% of MV | 0–60′000 ppb |
typ 1.3% accuracy drift per year.
Fig. 1Distribution of the RH during the measured time for each case, distinguishing summer and winter measurements. The color of the lines corresponds to the different cases and the line type to the ventilation strategy. (For interpretation of the references to color in this figure legend, the reader is referred to the Web version of this article.)
Fig. 2Distribution of the temperature during the measured time for each case (summer and winter are included where two rounds of measurements were performed).
Fig. 3Distribution of formaldehyde measurements for each house colored by the room's primary use. The dots or triangles in this figure show the single measurements aggregated by hour featured by the status of the trickle vent, and their coloring refers to the existence or not of the wood stove in the house.
Fraction of the time where measured formaldehyde surpasses the indicated limit on the specified duration. Results in parentheses show values considering only winter.
| ID | % Hours formaldehyde over 600 μg/m3 4 h [ | % Hours formaldehyde over 100 μg/m3 30 min [ | % Hours formaldehyde | |||
|---|---|---|---|---|---|---|
| %MT | %WH | %MT | %WH | %MT | %WH | |
| A1 | 0% | 0% | 10 %-(17%) | 0 %-(0%) | 8 %-(12%) | 0 %-(0%) |
| A2 | 0% | 0% | 2 %-(3%) | 2 %-(4%) | 1 %-(2%) | 0 %-(1%) |
| A3 | 0% | 0% | 6 %-(10%) | 1 %-(1%) | 2 %-(6%) | 0 %-(1%) |
| A4 | 0% | 0% | 5 %-(9%) | 1 %-(3%) | 4 %-(7%) | 1 %-(3%) |
| B5 | 0% | 0% | 14% | 29% | 12% | 25% |
| B6 | 0% | 0% | 3 %-(6%) | 4 %-(7%) | 1 %-(4%) | 1 %-(7%) |
| B7 | 0% | 0% | 10 %-(19%) | 10 %-(22%) | 9 %-(17%) | 7 %-(14%) |
| B8 | 7% | 0% | 87% | 77% | 76% | 61% |
| C9 | 0% | 0% | 20% | 17% | 15% | 14% |
| C10 | 0% | 0% | 2% | 3% | 2% | 4% |
| C11 | 0% | 0% | 7% | 6% | 5% | 5% |
| D12 | 0% | 0% | 8% | 0% | 7% | 0% |
| D13 | 0% | 0% | 27 %-(25%) | 7 %-(0%) | 17 %-(25%) | 7 %-(2%) |
| D14 | 0% | 0% | 25% | 1% | 21% | 0% |
| E15 | 0% | 0% | 0% | 0% | 0% | 0% |
| E16 | 0% | 0% | 0% | 0% | 0% | 0% |
| E17 | 0% | 0% | 11 %-(13%) | 11 %-(17%) | 8 %-(11%) | 10 %-(16%) |
| E18 | 0% | 0% | 4 %-(3%) | 6 %-(7%) | 3 %-(2%) | 2 %-(5%) |
| F19 | 0% | 0% | 3 %-(5%) | 2 %-(4%) | 3 %-(4%) | 2 %-(3%) |
| F20 | 0% | 0% | 6% | 4% | 5% | 4% |
| F21 | 0% | 0% | 1% (2%) | 2% (4%) | 1%(2%) | 1% (3%) |
Evaluation levels for formaldehyde.
| Exposure duration | Threshold value [μg/m3] | Rationale |
|---|---|---|
| 4 h | 600 | Accounts for sensory effect [ |
| 30 min | 100 | Conservative assessment of sensory irritation and the carcinogenic effects [ |
| 1 min | 110 | Accounts for odors [ |
The estimates for the most important predictor variables (β) for formaldehyde using GEE.
| Predictors | Season* | Trickle ventilation | Woodstove | Indoor air temperature | Relative humidity | |||
|---|---|---|---|---|---|---|---|---|
| Winter | Summer | Closed | Open | Yes | No | |||
| β | 0.32 | 0** | 0.31 | 0** | 0** | −0.28 | 0.05 | 0.03 |
| p-value | 0.01 | <0.001 | 0.01 | <0.001 | <0.001 | |||
A p-value less than 0.05 was considered statistically significant.
*Estimated based on houses measured both during the summer and winter (n = 11).
** This variable was used as a reference variable.
Fraction of the MT in the different levels is defined by the WHO [32], presented in Table 2, and maximum consecutive hours in the worst levels (aggregated by 30 min). Parentheses show results considering only winter measurements.
| ID | Outside quality classes MT % | Level 4 MT % | Level 3 MT % | Level 2 MT % | Level 1 MT % | Maximum consecutive hours outside or level 4 |
|---|---|---|---|---|---|---|
| A1 | 6 %-(12%) | 74 %-(88%) | 9 %-(0%) | 6 %-(17%) | 5 %-(0%) | 163 |
| A2 | 2 %-(6%) | 77 %-(90%) | 11 %-(3%) | 5% -(17%) | 5 %-(1%) | 93 |
| A3 | 5 %-(2%) | 54 %-(52%) | 25 %-(39%) | 10 %-(17%) | 6 %-(1%) | 23 |
| A4 | 8 %-(14%) | 78 %-(86%) | 9 %-(0%) | 4 %-(17%) | 1 %-(0%) | 143 |
| B5 | 11% | 56% | 18% | 7% | 8% | 21 |
| B6 | 1 %-(3%) | 22 %-(33%) | 39 %-(29%) | 26 %-(18%) | 12 %-(17%) | 23 |
| B7 | 15 %-(20%) | 69 %-(70%) | 9 %-(5%) | 3 %-(1%) | 4 %-(4%) | 27 |
| B8 | 86% | 13% | 1% | 0% | 0% | 90 |
| C9 | 19% | 72% | 9% | 0% | 0% | 123 |
| C10 | 1% | 32% | 32% | 11% | 24% | 16 |
| C11 | 7% | 89% | 4% | 0% | 0% | 47 |
| D12 | 4% | 48% | 20% | 15% | 13% | 20 |
| D13 | 20 %-(43%) | 62 %-(57%) | 11 %-(0%) | 5 %-(0%) | 2 %-(0%) | 169 |
| D14 | 43% | 57% | 0% | 0% | 0% | 169 |
| E15 | 3% | 96% | 1% | 0% | 0% | 171 |
| E16 | 0% | 54% | 33% | 8% | 5% | 22 |
| E17 | 6 %-(8%) | 56 %-(44%) | 19 %-(28%) | 9 %-(9%) | 10 %-(11%) | 21 |
| E18 | 10 %-(0%) | 80 %-(48%) | 5 %-(28%) | 2 %-(14%) | 3 %-(10%) | 23 |
| F19 | 13 %-(8%) | 63 %-(53%) | 15 %-(24%) | 5 %-(9%) | 4 %-(6%) | 19 |
| F20 | 6% | 56% | 25% | 7% | 6% | 21 |
| F21 | 0% | 41% | 32% | 11% | 16% | 19 |
The estimates for the most important predictor variables (β) for TVOCusing generalized estimating equations (GEE).
| Log TVOC | Predictors | |||
|---|---|---|---|---|
| Trickle ventilation | Indoor air temperature | Relative humidity | ||
| Closed | Open | |||
| β | 0.32 | 0** | 0.10 | 0.06 |
| p-value | 0.05 | <0.001 | <0.001 | |
A p-value less than 0.05 was considered statistically significant.
** This variable was used as a reference variable.
Fig. 4Distribution of TVOC measurements for each house colored by the room's primary use. The dots or triangles in this figure show the single measurements aggregated by hour featured by the status of the trickle vent, and their coloring refers to the existence or not of the wood stove in the house.
The estimates for the most important predictor variables (β) for CO2 using GEE.
| Log CO2 | Predictors | |||
|---|---|---|---|---|
| Season* | Indoor air temperature | Relative humidity | ||
| Winter | Summer | |||
| β | 0.18 | 0** | 0.03 | 0.03 |
| p-value | 0.01 | <0.001 | <0.001 | |
A p-value less than 0.05 was considered statistically significant.
*Estimated based on houses measured both during the summer and winter (n = 11).
** This variable was used as a reference variable.