| Literature DB >> 35162557 |
Zhuona Zhang1, Xia Li1, Qin Wang1, Xiaoning Zhao2, Jin Xu3, Qinqin Jiang4, Sili Jiang4, Jiayun Lyu4, Shiqiang Liu4, Ling Ye5,6, Jun Yuan4, Wenru Feng4, Jiamin Xie5,7, Qiuling Chen5,8, Haoming Zou5,9, Dongqun Xu1.
Abstract
A cross-layer non-vertical transmission of severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2) occurred in a quarantine hotel in Guangzhou, Guangdong Province, China in June 2021. To explore the cross-layer transmission path and influencing factors of viral aerosol, we set up different scenarios to carry out simulation experiments. The results showed that the air in the polluted room can enter the corridor by opening the door to take food and move out the garbage, then mix with the fresh air taken from the outside as part of the air supply of the central air conditioning system and re-enter into different rooms on the same floor leading to the same-layer transmission. In addition, flushing the toilet after defecation and urination will produce viral aerosol that pollutes rooms on different floors through the exhaust system and the vertical drainage pipe in the bathroom, resulting in cross-layer vertical transmission, also aggravating the transmission in different rooms on the same floor after mixing with the air of the room and entering the corridor to become part of the air supply, and meanwhile, continuing to increase the cross-layer transmission through the vertical drainage pipe. Therefore, the air conditioning and ventilation system of the quarantine hotel should be operated in full fresh air mode and close the return air; the exhaust volume of the bathroom should be greater than the fresh air volume. The exhaust pipe of the bathroom should be independently set and cannot be interconnected or connected in series. The riser of the sewage and drainage pipeline of the bathroom should maintain vertical to exhaust independently and cannot be arbitrarily changed to horizontal pipe assembly.Entities:
Keywords: air supply; drainage; field simulation of SARS-CoV-2; quarantine hotel; transmission path
Mesh:
Substances:
Year: 2022 PMID: 35162557 PMCID: PMC8835679 DOI: 10.3390/ijerph19031532
Source DB: PubMed Journal: Int J Environ Res Public Health ISSN: 1660-4601 Impact factor: 3.390
The detection results of fluorescent microspheres of swab samples and air samples collected in different locations of different rooms in different time.
|
|
| |||||||||||
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
| floor drain, toilet lid and seat ring |
|
|
|
|
|
| ||||||
| Exhaust fan of bathroom |
|
|
|
|
|
|
| |||||
| air supply outlets of fresh air system and the air conditioning |
|
|
|
| ||||||||
| air sample (filter member) |
|
|
| |||||||||
| air sample (liquid) |
|
|
| |||||||||
| exhaust outlet of the roof |
| |||||||||||
| sewage pipe riser vent on the roof |
| |||||||||||
|
|
| |||||||||||
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
| air supply outlet of the air conditioning |
|
|
|
|
|
|
|
|
| |||
| table, door, bed |
|
|
|
|
|
|
| |||||
| air supply outlets of fresh air system |
|
|
|
|
|
|
|
| ||||
| air sample (filter member) |
|
|
|
|
|
| ||||||
| air sample (liquid) |
|
|
|
|
|
| ||||||
| exhaust outlet of the roof |
| |||||||||||
| sewage pipe riser vent on the roof |
| |||||||||||
Figure 1The changes of particle concentration over time at 0.5 μm (scenarios 1), PM10 (scenarios 2) in different rooms. (A) Scenarios 1; (B) scenarios 2.
Figure 2The schematic diagrams of vertical transmission in bathrooms and pipeline convergence. Yellow pipes indicate sewage pipes, white pipes indicate drainage pipes, blue pipes indicate exhaust pipes, and red dots indicate simulated viral aerosols.
Figure 3The layout of rooms in the hotel and schematic diagram of the transmission in the same layer. Blue arrows indicate fresh air from the outside, red arrows indicate the polluted air from rooms, and purple arrows indicate increasing contaminated air by toilet flushing.