Literature DB >> 34699543

Field evaluation of thermal and acoustical comfort in eight North-American buildings using embedded radiant systems.

Megan Dawe1, Caroline Karmann2, Stefano Schiavon1, Fred Bauman1.   

Abstract

We performed a post-occupancy assessment based on 500 occupant surveys in eight buildings using embedded radiant heating and cooling systems. This study follows-up on a quantitative assessment of 60 office buildings that found radiant and all-air buildings have comparable temperature and acoustic satisfaction with a tendency for increased temperature satisfaction in radiant buildings. Our objective was to investigate reasons of comfort and discomfort in the radiant buildings, and to relate these to building characteristics and operations strategies. The primary sources of thermal discomfort are lack of control over the thermal environment (both temperature and air movement) and slow system response, both of which were seen to be alleviated with fast-response adaptive opportunities such as operable windows and personal fans. There was no optimal radiant design or operation that maximized thermal comfort, and building operators were pleased with reduced repair and maintenance associated with radiant systems compared to all-air systems. Occupants reported low satisfaction with acoustics. This was primarily due to sound privacy issues in open-plan offices which may be exacerbated by highly reflective surfaces common in radiant spaces.

Entities:  

Mesh:

Year:  2021        PMID: 34699543      PMCID: PMC8547689          DOI: 10.1371/journal.pone.0258888

Source DB:  PubMed          Journal:  PLoS One        ISSN: 1932-6203            Impact factor:   3.240


1 Introduction

Energy consumption in US commercial buildings accounts for 18% of the country’s primary energy use, with 30% of that being HVAC related [1]. There is a need to reduce buildings’ energy use to achieve carbon emission goals. In parallel, the building industry is becoming increasingly aware that the indoor environment impacts our health and well-being. A typical person spends around 90% of their lives indoors [2]. This long exposure to indoor environments pushes us to rethink the design and operation of our most common spaces in order to address and support occupants’ well-being, performance, and health. Researchers and building professionals seek design strategies to simultaneously address the dual challenges of indoor environmental quality (IEQ) and energy use. Radiant heating and cooling systems are thermally controlled surfaces that exchange heat mainly through thermal radiation. Radiant systems are relatively new to North America, and an NBI study found Zero Net Energy commercial buildings often use radiant systems [3]. Within the larger family of radiant systems, embedded radiant systems such as thermally activated building systems (TABS) and embedded surface systems (ESS) operate at relatively low-temperature for heating and high-temperature for cooling. These systems have the potential to achieve significant energy savings [4]. Radiant buildings also have to meet the occupants’ needs for comfort and workspace quality. These objectives often remain difficult to address in the day-to-day operation of commercial buildings, primarily due to the limited understanding of human comfort and its in situ assessment. Radiant systems are commonly assumed to provide improved thermal comfort in comparison to all-air systems. Cited theories for improved thermal comfort include creating uniform thermal conditions in a space [4,5], reducing risk of unwanted air movement [6-9], and reducing or eliminating discomfort from hot or cold surfaces (i.e., radiant asymmetry) [9,10]. Karmann et al. completed a critical literature review to learn if spaces using radiant system provide better, worse, or similar thermal comfort compared to spaces using an all-air system [11]. Their review revealed a lack of studies based on occupant’s perception, while more studies relied on calculated thermal comfort. Considering the limited number of studies available and the small sample sizes for each study, their review could not establish a definitive statement on the effectiveness of radiant systems for thermal comfort. Aside from thermal comfort, little has been studied about the ways in which radiant systems affect space acoustics. Radiant systems are commonly installed on large acoustically reflective surfaces (e.g., ceilings or floors) that are kept exposed to maximize thermal radiation. In practice, exposed concrete surfaces can lead to increased reverberation and lower acoustic satisfaction, but this assumption requires validation from the field considering spaces experienced by building occupants.

2 Background

Karmann et al. found few existing studies used occupant surveys to compare comfort in spaces with radiant systems to those with all-air systems [11]; therefore, Karmann et al. conducted a quantitative survey study to determine whether radiant systems provide higher satisfaction than all-air systems [12]. The study included 26 radiant buildings (1,645 occupant responses) and 34 all-air buildings (2,247 occupant responses) of comparable key characteristics (e.g., building size, year built, climate zones). 21 of the 26 radiant buildings (over 2/3 of the individual responses) used TABS or ESS. Fig 1 shows boxplots for occupant satisfaction by conditioning type. Temperature satisfaction is the only category that showed a difference in median between the two subsets. The difference in mean was statistically significant (p<0.001), and the Spearman’s ρ effect size of the difference (ρ = 0.14) was the largest observed in this study; however, the practical difference shall be considered as either negligible or small [13,14]. Karmann et al. [12] concluded that indoor environmental quality is the same with a tendency for increased thermal satisfaction in radiant buildings. Acoustical categories ranked as the lowest performing for both systems, and neither noise nor sound privacy satisfaction showed statistical or practical significant differences between the two subsets. A mixed effects model showed that 21% of the variance for sound privacy could be described by ‘between office type’ differences (e.g., private, open-plan, etc.), which is more than the variance explained by conditioning systems.
Fig 1

Boxplot for occupant satisfaction with workspace, temperature and acoustics in 60 radiant and all-air buildings.

The differences in mean values (radiant–all-air) statistical and practical significance (effect size) of this difference are indicated on the right.

Boxplot for occupant satisfaction with workspace, temperature and acoustics in 60 radiant and all-air buildings.

The differences in mean values (radiant–all-air) statistical and practical significance (effect size) of this difference are indicated on the right.

3 Objective

The quantitative analysis from (Karmann et al. 2017) was able to show trends and provide answers to the commonly asked questions comparing radiant to all-air systems. Yet, it was grounded only on aggregated answers to a post-occupancy survey and was detached from the idiosyncratic characteristics of each building. Further, the majority of thermal comfort evaluations in radiant spaces are in laboratory conditions or small-scale field studies, and reported comfort is based on calculated PMV-PPD which has very low prediction accuracy [15]. To expand on previous assessments, we selected eight TABS or ESS radiant buildings to further investigate reasons of thermal and acoustical satisfaction, and to uncover relations, if any, between occupants’ impressions to building characteristics and operation strategies. Our post-occupancy evaluation approach was to find shared themes across several buildings rather than to focus on the specific and unique outcomes of each individual building. We accomplished this through in-depth review of over 500 occupant surveys (including open-ended comments) and interviews of building operators to provide useful lessons learned and insight into occupant satisfaction in buildings using radiant systems. With this study, we want to provide insight into occupant satisfaction and perception that can help designers and building operators address or plan for improved occupant comfort and well-being in radiant buildings.

4 Methods

4.1 Building selection

For this study, we targeted office-type buildings located in different climates in North America and using embedded types of radiant system (i.e., TABS or ESS) for which occupant satisfaction surveys, building characteristic, and radiant design data was available or could be acquired. All buildings use the radiant system for cooling and heating. In buildings where only select spaces use radiant, we limited occupant surveys to those spaces. We selected these building systems because embedded systems have a much longer time constant than panel systems [16], and may have thermal comfort and acoustical issues. Moreover, we expect they would have the possibility of thermal storage (grid to building load flexibility), improved energy performance, and lower cost than radiant panel buildings. We intentionally included an array of buildings performing well or poorly in either or both occupant satisfaction or energy performance to better assess sources affecting comfort and the possible correlation to energy performance.

4.2 Occupant satisfaction survey

This study relied on occupant satisfaction data collected by the Center for the Built Environment (CBE) at the University of California, Berkeley [17,18]. The IEQ occupant satisfaction survey covers nine core categories including thermal comfort and acoustics [19]. It uses a 7-point Likert scale ranging from ‘very satisfied’ (+3) to ‘very dissatisfied’ (-3), with a ‘neutral/neither satisfied nor dissatisfied’ midpoint (0). Dissatisfied responses trigger branching questions targeting the source of the dissatisfaction. The survey does not include similar branching questions when an occupant expresses satisfaction; this was done as a method to minimize survey fatigue. The voluntary and web-based survey also includes fields for open-ended responses. The surveys are intended to gather long-term occupant experiences rather than “right now” surveys which might be paired with objective information such as environmental measurements and current system operation. The analysis uses the survey’s branching questions and open-ended responses to identify sources of satisfaction and dissatisfaction. The open-ended responses allowed us to also infer sources of satisfaction or dissatisfaction that were not captured within the branching questions. We reported some of these comments (as quotes) when they captured interesting insights about comfort conditions experienced in their space. We calculated the percentage of dissatisfied occupants across all buildings and per building for both temperature and acoustic satisfaction, considering the different satisfaction intervals described in standards and common definitions. The survey response rate depends on the willingness of occupants to provide feedback. Therefore, we did not establish a threshold for minimum response rate. We reported the response rate for each building and considered all occupant feedback as suggestive of trends, regardless of response rate achieved. The Institutional Review Board at the University of California, Berkeley approved this work (IRB-2010-05-1550). We administered all surveys online and consent was informed; participants provided their written consent online prior to advancing to the survey. The study did not include minors. We used R v.3.5.0 (R Development Core Team 2017) for all numerical analysis.

4.3 Building and radiant system characteristics survey

For each building in this study, we also collected data on the building’s characteristics, radiant design, and facility and system operations. Information collected includes type of radiant system, control strategy, temperature setpoints, zone sizes, ventilation strategy, window and shading design, presence of other HVAC systems, and more. The building manager, the facilities manager, or a member of the design team provided this information in an online survey. We used this information to detect any relationship between occupant satisfaction and building characteristics or radiant design. The data collection did not include physical measurements or occupant tracking information. The analysis relies exclusively on anonymous survey responses and selected interviews.

4.4 Building operator interviews

We interviewed the primary engineer and/or knowledgeable contacts with the building operation team for six buildings; contacts at two buildings did not respond to our requests. Five of these interviews took place by telephone, and one was conducted during a site visit. The goals of the interviews were to gain their perspective on: 1. occupant feedback for IEQ parameters; 2. the balance and synergies between energy performance and occupant thermal comfort; 3. lessons learned during commissioning and operation.

5 Results and discussion

The following sections provide aggregated findings based on occupant experiences in their spaces and suggestions for building designers and operators. Occupant satisfaction data is provided in S1 Dataset.

5.1 Description of the buildings

The eight buildings selected for the qualitative analysis use embedded radiant systems (either TABS or ESS) for both heating and cooling, are of varying sizes and design, and located in five different ASHRAE 90.1 climate zones in North America. Table 1 summarizes the building characteristics, including thermal comfort ranking, and Table 2 provides the HVAC, comfort, and energy concept for each building. As seen in Table 1, the buildings represent a range of occupant comfort and energy performance. Energy performance is categorized by annual Energy Use Intensity (EUI) which incorporates all energy sources and an ENERGY STAR Score, which normalizes energy use by key drivers, including building size, location, number of occupants, and operating hours, and number of computers. Buildings B4 and B5 performed the best in terms of thermal comfort satisfaction relative to the other six buildings. Interestingly, B2 and B6 were low performing buildings and had the highest annual Energy Use Intensity (EUI) by more than double the next closest building. All buildings are LEED certified, with many achieving Platinum certification. Four buildings were designed with supplemental cooling equipment, but it is unknown what portion of sensible and latent cooling these systems serve in operation and how that might impact thermal comfort.
Table 1

Building characteristics.

Bldg. IDFunctionBuilding size (m2)Year built (original)(a)CertificationsLocationASHRAE climate zoneIEQ thermal satisfaction rank(b)EUI(c) (kWh/m2)ENERGY STAR Score(d)
B1Office4,8312003LEED Platinum, Living Building ChallengeSeattle, WAMixed-marine (4C)14th/263899
B2(e)Library<10,000≤ 2010 (renovated)LEED Gold-Mixed-marine (4C)26th/264861
B3(f)Office + Multi-purpose18,8592015 (1910)LEED Platinum, LEED EBOMSan Diego, CAWarm-dry (3B)17th/26 unknown Unknown
B4Office16,0162015LEED Platinum, Net zeroFremont, CAWarm-marine (3C)3rd/2675100
B5Office33,4452010LEED PlatinumGolden, COCool-dry (5B)9th/2611498
B6Office4,0882010 (1986)LEED PlatinumAtlanta, GAWarm-humid (3A)21st/26555NA(g)
B7Office + Lab1,5122012LEED PlatinumVictoria, BCMixed-marine (4C)12th/2615198
B8Office + Multi-purpose18,5812012LEED PlatinumSacramento, CAWarm-dry (3B)16th/26 unknown unknown

(a) In case the building was renovated, we indicated original year of construction in parenthesis.

(b) We ranked our buildings based on mean temperature satisfaction out of the 26 radiant buildings in the study [12].

(c) EUI: Annual Energy Use Intensity inclusive of all energy sources(from [20], converted to kWh/m2).

(d) ENERGY STAR Score yields a 1-to-100 percentile ranking, from [20].

(e) Building B2 requested to be anonymous (non-trackable), therefore we did not provide identifying information.

(f) Building B3 was ranked in IEQ thermal performance using the office portion only.

(g) Buildings must be at least 5,000 square feet to calculate an ENERGY STAR Score.

Table 2

Comfort and energy concept of the building.

Bldg. IDRadiant type(a)Radiant zone portion(b)Ventilation type(c,d)Ventilation distribution(c)Supplemental Cooling SystemHtg/Clg SetpointsSystem operationUnoccupied operation(c,e)Adaptive opportunities(f)Acoustic treatmentShading(c,g)
B1ESS (floor)80%MM (change-over)Overhead (DOAS)None20/26 °CConstant flow, variable temperature24/7 with setbackOperable windows, ceiling fans unknown i(o),e(o)
B2TABS (ceiling)100%MM (change-over)Underfloor (DOAS)Upsized DOAS23/26 °CConstant flow, variable temperature24/7 without setbackOperable windows, desk fans*Carpete(f)
B3ESS (floor)40%MM (unknown)Overhead (DOAS)None21/24 °CVariable flow, variable temperature24/7 with setbackOperable windows, desk fans*, ceiling fans unknown i(o)
B4TABS (floor) 51–75% MM (concurrent, change-over)Overhead (DOAS)Active chilled beams20/23 °CVariable flow, variable temperatureTurns on before occupancyOperable windows, desk fans*, heaters*, thermostatCarpet, wall panelsi(o)
B5TABS (ceiling)100%MM (unknown)Underfloor (DOAS)Fan coils and upsized DOAS22/26 °CVariable flow, constant temperatureTurns on before occupancyOperable windows, desk fans*, ceiling fansCarpet, tall partitions, white noise generatore(f)
B6ESS (ceiling) 76–100% MV (fully)Underfloor (DOAS) Unknown 21/23 °C unknown unknown Desk fans*, heaters*Carpeti(o)
B7TABS (floor)100%MM (change-over)Trickle vent (DOAS)Yes, only in conference rooms21/24 °CVariable flow, constant temperature24/7Trickle vent, thermostatVanAir doors(h)i(o)
B8TABS (ceiling)100%MV (fully)Overhead (DOAS)Considering adding heat pumps(i)21/24 °CVariable flow, constant temperatureTurns on before occupancyDesk fans*, heaters*, ceiling fansVertical ceiling panelse(f)

(a) Embedded surface systems (ESS), thermally activated building systems (TABS).

(b) Percent of building served by radiant system.

(c) Applies to the radiant zones of the building.

(d) MV: Mechanical ventilation (no operable windows), NV: Natural ventilation, MM: mixed-mode (type: change-over, concurrent, zoned).

(e) How the radiant system is operated during unoccupied hours.

(f) Adaptive opportunities may refer to fast-response actions that either affect groups (i.e., operable windows, ceiling fans) or individuals (i.e., desk fans, heaters). We used an asterisk to indicate opportunities supporting individual actions.

(g) Shading classification: i = internal, e = external, (f) = fixed, (o) = operable.

(h) Passive door ventilation with sound trap.

(i) Building operators are considering adding supplemental cooling to address added load from higher than designed occupant density.

(a) In case the building was renovated, we indicated original year of construction in parenthesis. (b) We ranked our buildings based on mean temperature satisfaction out of the 26 radiant buildings in the study [12]. (c) EUI: Annual Energy Use Intensity inclusive of all energy sources(from [20], converted to kWh/m2). (d) ENERGY STAR Score yields a 1-to-100 percentile ranking, from [20]. (e) Building B2 requested to be anonymous (non-trackable), therefore we did not provide identifying information. (f) Building B3 was ranked in IEQ thermal performance using the office portion only. (g) Buildings must be at least 5,000 square feet to calculate an ENERGY STAR Score. (a) Embedded surface systems (ESS), thermally activated building systems (TABS). (b) Percent of building served by radiant system. (c) Applies to the radiant zones of the building. (d) MV: Mechanical ventilation (no operable windows), NV: Natural ventilation, MM: mixed-mode (type: change-over, concurrent, zoned). (e) How the radiant system is operated during unoccupied hours. (f) Adaptive opportunities may refer to fast-response actions that either affect groups (i.e., operable windows, ceiling fans) or individuals (i.e., desk fans, heaters). We used an asterisk to indicate opportunities supporting individual actions. (g) Shading classification: i = internal, e = external, (f) = fixed, (o) = operable. (h) Passive door ventilation with sound trap. (i) Building operators are considering adding supplemental cooling to address added load from higher than designed occupant density.

5.2 Thermal comfort assessment

The thermal comfort assessment is based on qualitative feedback from occupant surveys, not calculated PMV-PPD.

5.2.1 Compliance with ASHRAE 55

The objective of ASHRAE Standard 55 is to have a “substantial majority (more than 80%) of the occupants” find their thermal environment “acceptable”; however, the advised method for verification is based on occupant survey asking about “satisfaction”. We used this method to verify compliance to the standard, but we note that this shift from ‘satisfaction’ (in the question/scale used) to ‘acceptability’ (in the intent) can be misleading. Furthermore, ASHRAE 55 modified its threshold for “acceptable” in the version ASHRAE 55–2017 [21], the standard suggests to include votes falling between ‘-1’ (‘slightly dissatisfied’) and ‘+3’ (‘very satisfied’), while in the 2013 version [22], it asked to include votes between ‘0’ (‘neither satisfied not dissatisfied’) and ‘+3’ (‘very satisfied’). The original dataset of 26 radiant buildings has 65% (17/26) of radiant buildings meeting the ASHRAE 55–2017 definition of acceptability [12], and 85% (22/26) meeting this definition if we consider 75% of occupant satisfied (instead of the ASHRAE threshold of 80%). Our subset of eight building is representative of the larger sample as 5/8 (62%) meet the ASHRAE 55–2017 definition of acceptability while 7/8 (85%) reach 75% of occupant satisfied for the same interval. Table 3 provides the results of the thermal comfort analysis considering all definitions. We bolded the text when the 80% criteria was met. We italicized the text for buildings which the response rate was less than the 35% (not recommended by the ASHRAE 55).
Table 3

Temperature satisfaction by building.

Bldg. ID# of occupant responses (response rate)Percentage reported for temperature satisfaction
% satisfied considering votes from (-1) to (+3)(a)% satisfied considering votes from (0) to (+3)(b)% satisfied considering votes from (+1) to (+3)(c)
B178 (62%) 89% ( e ) 67%63%
B228 (37%)64%39%32%
B3 ( d ) 23 (27%) 78% 61% 61%
B4 ( d ) 47 (4%) 96% 89% 79%
B5 ( d ) 41 (<1%) 93% 85% 73%
B691 (48%)76%53%46%
B736 (53%) 94% 75%64%
B8 ( d ) 207 (28%) 88% 72% 60%

(a) ‘Slightly dissatisfied’ (-1) is the lowest threshold for a positive vote for thermal acceptability in the ASHRAE 55–2017.

(b) ‘Neither satisfied not dissatisfied’ (0) is the lowest threshold for a positive vote for thermal acceptability in the ASHRAE 55–2013.

(c) The thermal comfort definition specifies a clear satisfaction statement.

(d) The buildings indicated in italic had a response rate lower than 35%.

(e) Bolden text for buildings that meets the ASHRAE 55 target of 80% satisfaction rate.

(a) ‘Slightly dissatisfied’ (-1) is the lowest threshold for a positive vote for thermal acceptability in the ASHRAE 55–2017. (b) ‘Neither satisfied not dissatisfied’ (0) is the lowest threshold for a positive vote for thermal acceptability in the ASHRAE 55–2013. (c) The thermal comfort definition specifies a clear satisfaction statement. (d) The buildings indicated in italic had a response rate lower than 35%. (e) Bolden text for buildings that meets the ASHRAE 55 target of 80% satisfaction rate. If we consider all eight radiant buildings in this dataset (independently from the response rate), three do not comply with any thermal comfort definitions, five buildings comply with ASHRAE 55–2017, two of which also comply with ASHRAE 55–2013, but no buildings were able to meet the thermal comfort definition based on satisfaction. If we only consider buildings that reached 35% response rate (B1, B2, B6, B7), two buildings comply with ASHRAE 55–2017, and no buildings were able to meet ASHRAE 55–2013 or the thermal comfort definition. The generally low compliance observed, despite the quality of the buildings analyzed, is aligned with the commonly observed low temperature satisfaction rate found in buildings [23]. Extending the interval to equate a negative response (‘slightly dissatisfied’) to a positive vote (‘acceptable’), as in the 2017 version, is questionable jump in regard to what occupants reported about their conditions.

5.2.2 Sources of satisfaction/dissatisfaction with thermal comfort

Occupants that expressed dissatisfaction with temperature, were asked to select any or all of 20 listed sources of discomfort. Given that this is a “check all that apply” question and there are a different number of occupants per building, we represented the results in two ways: Fig 2(A) shows the percentage of dissatisfied votes across all eight buildings (n = 173), and Fig 2(B) shows the percentage of dissatisfied votes per building. This was done so that conclusions were not informed only by buildings with large occupancy and portion of dissatisfied occupants. We considered two survey options as the same for these buildings: “thermostat is inaccessible” and “thermostat is controlled by other people”. Only one building allowed occupants to make direct changes to the thermostat setpoints, so all responses are interpreted as “lack of thermostat control”. An occupant’s vote was only counted once if both options were selected. The survey is not designed to distinguish between system types, so occupant responses are inclusive of supplemental systems.
Fig 2

(A) Percentage of dissatisfied occupants across all eight buildings (n = 173), and (B) percentage of dissatisfied occupants per building for each of the 19 potential sources of thermal discomfort (n by building).

The black diamond represents the average percent dissatisfied across each of the individual buildings.

(A) Percentage of dissatisfied occupants across all eight buildings (n = 173), and (B) percentage of dissatisfied occupants per building for each of the 19 potential sources of thermal discomfort (n by building).

The black diamond represents the average percent dissatisfied across each of the individual buildings. The order of sources of thermal discomfort in Fig 2(A) follows that observed for the 26 radiant buildings [12], suggesting that the eight buildings selected for this assessment are representative. Across all eight buildings, 173 of 551 occupants expressed dissatisfaction with temperature. As seen in Fig 2(B), there is variability in the top source of discomfort between buildings. This is not surprising given that each building is unique. Regardless of the variability in votes between buildings, there are clear trends in sources that are always or rarely selected, as suggested by the average percent dissatisfied across each of the individual buildings (black diamond). Based on Fig 2, occupant open-ended responses, and building operator interviews, the following aspects appear to be related to thermal comfort in these buildings: The ability to quickly and individually change the thermal environment. The top two sources of discomfort are “lack of thermostat control” and “slow system response”. These results are not surprising given that TABS and ESS systems have high response times; if temperature setpoints are adjusted, it could take one hour up to several hours for those changes to be felt [16]. This is a primary reason why temperature setpoint changes is not a recommended control action to quickly address thermal discomfort in high thermal mass radiant system buildings. This is a concern regardless of the ability of radiant systems to be able to instantaneously extract part of the radiant load [24]. Additionally, the method used to modulate temperature setpoints and the placement of slab temperature sensors could further influence system response [25]. We do not have sufficient information to assess if radiant temperature control methods affected occupant comfort. Satisfaction was higher in buildings where occupants were equipped with fast-response adaptive opportunities that enable either group control (i.e., operable windows, ceiling fans) or personalized control (i.e., desk fans, heaters) of thermal conditions. Three buildings had occupants indicate “my area is colder than others” and “my area is hotter than others” in the same open-plan office area of the building, exemplifying that individual occupants feel differently in the same environment. In such spaces where centrally controlled temperature setpoints cannot satisfy all occupants, building designers operators should consider offering individualized control (e.g., personal fans and heaters) to address individual thermal preferences and comfort. “I don’t have much control over temperature. I usually run warm, so I like to have a fan.” “I love the operable windows.” “When it’s too hot or cold it can take up to 2–3 days to be corrected. If you are in a fair bit of discomfort that is a long time to wait.” We note that loose dress codes are also supportive of individual comfort and provide an additional source of adaptive opportunity to occupants. Building operators for three buildings mentioned that adaptive opportunities supported energy goals by providing comfortable conditions during shoulder seasons without heating and cooling in the same day. User-controlled air movement. Mechanically-supplied air in radiant buildings is generally for ventilation only and therefore at low velocity, but we know that increased air movement is preferred under neutral to warm temperature sensation [26]. There were 75% more complaints for “air movement too low” than for “air movement too high”, suggesting occupants desire more air movement. The nature of the survey is to provide feedback on overall occupant experience, so we cannot correlate the desire for air movement with temperature or system operation; we can only conclude that occupants often feel the desire for more air movement. For occupants that indicated air movement was too high or felt discomfort from drafts, their comments revealed it was commonly due to automated (non-user controlled) features such as automated windows, trickle vents, and ceiling fans operating at too low temperatures, which is unpleasant [27]. Manually operable windows and desk fans appear to provide the best user-controlled air movement and building designers and operators should consider including these features or allowing occupant adjustment to ceiling fan operation. “The windows often open for airflow or for (what I assume) is anticipated higher temperatures later in the day, often leaving our space too cold.” (Automated windows) “Overhead fans in the past have gone on way too early and it seems to be too cool.” Thermal comfort uniformity and overall temperature predictability. Radiant design resources and researchers commonly reference uniform thermal conditions as an expected positive thermal comfort outcome in radiant buildings. There are multiple terms used to express this condition, including temperature uniformity and thermal comfort uniformity, and multiple cited outcomes and benefits, including 1) having a small vertical temperature gradient [4,7,28], 2) having a uniform spatial distribution of temperature [28], or 3) having uniform thermal comfort conditions (i.e., PMV) throughout a conditioned space [7,29]. In this study, as we did not conduct temperature measurements in the buildings, we only assessed the uniformity of thermal comfort conditions by relying on occupant subjective responses to the question “How satisfied are you with the temperature of your workspace?” on a 7-point scale and open-ended responses. Occupant open-ended responses and building operator feedback indicate that there is uniform thermal comfort conditions, at least in open-plan office areas. Building operators reported that they receive fewer hot or cold spot complaints than in all-air buildings. Occupants in open-plan offices that selected “my area is colder than others” or “my area is hotter than others” typically referenced the space (or building) being too warm or too cool everywhere rather than in their particular workstation. Although this means that the thermal conditions were not considered comfortable, occupants rarely implied that spatial differences in temperature led to discomfort. Further, occupants suggest that there were predictable conditions throughout a space, throughout a day, or from day-to-day, which allows occupants to prepare accordingly. We hypothesize that these buildings have more stable interior temperatures due to the high thermal mass, but cannot confirm without physical measurements. “The temperature is always fantastic, never too hot or too cold, there are no spots in the building where the temperatures vary significantly.” “It’s often stuffy/hot in the morning in the summer, but I dress accordingly.” We are not drawing any conclusions on thermal comfort impacts from hot or cold surface or incoming solar radiation. As seen in Fig 2, only 11% of dissatisfied occupants identified floors as a source of discomfort and less than 10% identified hot or cold walls, windows, or ceilings. The low number of responses could be attributed to lack of occupant knowledge of radiant heat transfer rather than the absence of discomfort from these sources. Additionally, the building characteristic surveys indicated that buildings had well insulated envelopes and all had shading strategies to avoid direct solar heat gains through windows. Miscellaneous sources. There are sources of comfort/discomfort that were unique to one or two buildings but could be relevant for other buildings outside this dataset. These include: Supplementary air-cooling systems in at least two buildings appear to be a cause of discomfort, including over-cooling in warm weather. Although spatial differences in temperatures did not appear to be a problem in open-plan offices, one building has zones that serve both open-plan office and private offices. Occupants in private offices more often responded that their space was “hotter than others” compared to those in the open-plan office, especially when the private offices did not have operable windows or a mechanism for air movement. It is common for temperature sensors to be located in open-plan offices in this scenario. Building designers should closely consider the thermal comfort impact of this type of design. Humidity levels were not identified as a problem in any of the buildings, but only one is located in a climate that experiences high outdoor relative humidity, with summer mean monthly wet bulb temperature around 23 °C. Operators in two buildings indicate that they make ad hoc and frequent changes to temperature setpoints in attempts to improve comfort, which is more akin to all-air system control. One building has large radiant zones (500–1000 m2) with ESS and poor thermal comfort and complaints about inconsistent day-to-day temperatures, while the other building has small radiant zones (many less than 50 m2) with TABS and thermal comfort is relatively good. We expect this type of operation to result in poor thermal comfort, as well as energy performance, due to the long system response times. However, the difference in thermal comfort results between the two buildings could be attributed to the zone size or system control factors that could be further investigated. Designers and operators should better understand system control and could provide fast-response adaptive controls such as fans and heaters to occupants instead of making ad hoc changes to temperature setpoints. We did not identify any single optimal radiant design or control strategy to maximize occupant comfort. However, the small sample size does not provide enough consistency in design and radiant system control across buildings to provide a reliable conclusion. The assessment does not indicate relationships between temperature satisfaction and the primary radiant surface, radiant loop control (e.g., variable/constant flow, variable/constant temperature), temperature setpoint strategy (e.g., zone air temperature setpoint, slab temperature setpoint, etc.), ventilation distribution, or how the system is operated outside of occupied hours, with the exception of the building in which operators make ad hoc changes to setpoints. This suggests that designing and operating TABS and ESS radiant systems to maximize energy efficiency shall not pose a significant threat to thermal comfort as long as design and operation are appropriate for the radiant system context. Additionally, we do not see any correlation between LEED certification and thermal comfort, providing further evidence that LEED certification is not strongly correlated with building performance [30].

5.2.3 Feedback from building operators

A benefit of radiant systems that has not been widely highlighted amongst the design community is improvements to building operation work load. Each of the six building operators had previous experience in traditional all-air buildings and all provided examples of how radiant systems positively impact their work. Their reasons include that the system is generally hands free, reduces the physical area of work to mostly the manifolds, which are outside of occupant areas, and has fewer mechanical parts for maintenance and repair. All operators felt that radiant systems are more energy efficient compared to their experience with all-air systems, and they were generally pleased with the system’s ability to provide comfort. However, some felt that they did not achieve as good of thermal comfort. Operators for two buildings stated that they have less granular and instantaneous control compared to all-air systems, and therefore, feel they lack the ability to address individual comfort, particularly in large zones covering open-plan office area. One of these buildings has poor thermal comfort and operators who make ad hoc changes to temperature setpoints for large zones, which is not a recommended operation strategy. In contrast, an operator in another building that makes frequent temperature changes with relatively small radiant zones felt that the more granular control was able to achieve acceptable thermal comfort, if not better than an all-air system. This design needs further investigation, as it is an unexpected finding.

5.2.4 Energy performance and thermal comfort

Although there was no single radiant design or operation that maximized thermal comfort within this small building sample size, we identified trends that promote both energy savings and thermal comfort. We were not able to assess the energy consumption of the radiant system by itself, only whole building consumption. Additionally, two buildings are campus-style and could not provide building-level energy data, and we were not successful in interviewing operators from the two highest energy consuming buildings. The following features appear to be related to energy performance and also promote thermal comfort in these buildings. Of the four best energy performing buildings: All take advantage of free cooling through operable windows, or trickle vents in one building, which can improve thermal comfort from increased air movement in warm temperatures. At least one of these buildings turns off the radiant system operation to zones where windows are open, and one of these buildings relies solely on natural ventilation. All have zone air temperature deadband (i.e., degrees between heating and cooling air temperature setpoints) between 2.8 and 5.6 °C. Three use seasonal changeovers for the radiant system, which avoids heating and cooling in the same day. These buildings rely on operable windows, trickle vents, and/or personal control systems (i.e., desk fan, heaters) to maintain comfort during shoulder seasons. Multiple buildings have high performance envelopes, including sun shading to avoid direct solar heat gains, and reduce heat transfer. Of the two buildings with poor energy performance: Neither have operable windows for free cooling. At least one has a supplemental air-cooling system for hot and humid summer conditions that, based on occupant comments, appears to be overcooling the space. This building has the smallest dead band between heating and cooling (2.2 °C) and also has poor occupant comfort. This small dead band could be causing heating and cooling in the same day [31], and it could also be the cause of over-cooling in warm weather.

5.3 Acoustic quality assessment

5.3.1 Percentage of occupants satisfied with acoustics

In the IEQ survey used, satisfaction for acoustics is split between satisfaction with noise level and satisfaction with sound privacy. Noise level refers to general background noise, while sound privacy describes an occupant’s ability to avoid being overheard in or overhearing other conversations. Although noise level and sound privacy are known sources of occupant dissatisfaction in buildings [18], there is no target guiding minimal occupant satisfaction with acoustic in spaces. In this section, we calculated acoustical satisfaction as the average between noise level and sound privacy per occupant and applied the ASHRAE 55 analysis process and thresholds described in Section 5.2.1 to arrive at the percentage of occupants finding the acoustics acceptable in the eight buildings. We also report the percentage of occupant satisfied with noise levels and with sound privacy. As seen in Table 4, both satisfaction with noise level and with sound privacy, indicated in parenthesis respectively, are generally low across all buildings, with sound privacy ranging from only 27% to 57% satisfied considering only neutral and positive votes. Only one building meets the 80% threshold for acoustics under the most lenient acceptability definition. Overall, these results show that occupants are even less satisfied with acoustics than they are with thermal comfort.
Table 4

Acoustic satisfaction by building.

Bldg. ID# of occupant responses (response rate)Percentage reported for noise levels, sound privacy (in parenthesis) and acoustic satisfaction(a)
% satisfied considering votes from (-1) to (+3)% satisfied considering votes from (0) to (+3)% satisfied considering votes from (+1) to (+3)
B175 (60%)(76%, 64%) | 73%(49%, 40%) | 42%(40%, 18%) | 26%
B227 (36%)(82%, 71%) | 75%(54%, 57%) | 50%(43%, 36%) | 32%
B3 ( b ) 23 (27%) (83%, 70%) | 74%(74%, 57%) | 65%(65%, 57%) | 57%
B4 ( b , c ) 47 (4%) (89%, 72%) | 85%(81%, 51%) | 66%(70%, 45%) | 47%
B5 ( b ) 41 (<1%) (85%, 61%) | 76%(63%, 27%) | 44%(51%, 15%) | 17%
B690 (47%)(78%, 53%) | 64%(60%, 28%) | 45%(42%, 12%) | 18%
B736 (53%)(75%, 67%) | 67%(50%, 31%) | 44%(36%, 14%) | 17%
B8 ( b ) 204 (27%) (78%, 61%) | 68%(59%, 42%) | 52%(47%, 27%) | 33%

(a) We used the average between noise level and sound privacy per occupant to calculate satisfaction with acoustics per building.

(b) The buildings indicated in italic had a response rate lower than 35%.

(c) Bolden text is used when satisfaction rate meets the 80% threshold.

(a) We used the average between noise level and sound privacy per occupant to calculate satisfaction with acoustics per building. (b) The buildings indicated in italic had a response rate lower than 35%. (c) Bolden text is used when satisfaction rate meets the 80% threshold.

5.3.2 Sources of satisfaction/dissatisfaction with acoustics

Occupants that expressed dissatisfaction with acoustics (answering negatively to either noise level or sound privacy satisfaction), were asked to select any or all of 10 listed sources of discomfort. Given that this is a “check all that apply” question and there are a different number of occupants per building, we represented the results in two ways in Fig 3, similarly as what was done for the thermal comfort assessment.
Fig 3

(A) Percentage of dissatisfied occupants across all eight buildings (n = 354) and (B) percentage of dissatisfied occupants per building for each of the 19 potential sources of thermal discomfort (n by building).

The black diamond represents the average percent dissatisfied across each of the individual buildings.

(A) Percentage of dissatisfied occupants across all eight buildings (n = 354) and (B) percentage of dissatisfied occupants per building for each of the 19 potential sources of thermal discomfort (n by building).

The black diamond represents the average percent dissatisfied across each of the individual buildings. Across all eight buildings, 354 of 543 occupants expressed dissatisfaction with noise and/or sound privacy, notably more than those that expressed dissatisfaction with temperature. 221 were dissatisfied with noise and 333 were dissatisfied with sound privacy; 200 were dissatisfied with both. The responses are in alignment with the quantitative survey study on 60 buildings, indicating the eight buildings are representative. Based on Fig 3, occupant open-ended responses, and building operator interviews, the following aspects appear to be related to acoustics in these buildings: Sound privacy in open-plan offices remains a challenge. The top three causes of acoustical dissatisfaction in Fig 3 are more closely aligned with sound privacy than noise, as are the majority of open-ended responses. The primary space type in these buildings is open-plan office, which is detrimental to sound privacy. In current design practice, radiant systems push designs towards more open-plan space and the highly reflective thermally active surfaces for TABS and ESS systems can exacerbate the problem. However, there are other perhaps stronger factors driving designs towards open-plan (such as higher occupant densities, affordability, flexibility of the space) and therefore, we cannot attribute the cause to radiant systems alone. “Open office spaces need to have private areas both large and small for meetings or private conversations” “I overhear technical conversations and my own interest in the technical issues is the problem. I end up listening to it instead of focusing on my own work.” Exposed reflective surfaces may contribute to unwanted sound reverberation. “Excessive echoing” and “telephones ringing” are the next most prevalent sources, but, notably, there is a large reduction in occupants selecting these as the source of their dissatisfaction. It is feasible that these sources could also be indirectly associated with the highly reflective surfaces like the following comments suggest; however, there are no acoustic pressure measurements to use as validation: “Lack of ceiling tile creates an echo chamber.” “The building tends to echo quite a bit, I can hear people on first level all the way to the third level.” Lack of noisy mechanical equipment. As speculated by the design community, very few respondents identified mechanical equipment as an issue, which supports statements that radiant systems are quiet. However, 16% of occupants selected office equipment as a problem. In the building where this was primarily a problem, the issue appears to be two-fold: improperly sized ventilation diffusers that create a whistling noise and noisy ceiling fans, neither of which are directly related to the radiant system. “The mechanical heating and cooling system is very quiet.” Few designs employ noise reduction strategies. Six buildings have strategies in place to reduce noise issues in the studied buildings, including wall or vertical acoustic panels (two buildings), high partitions and a white noise generator (one building), carpeted floors (four buildings), and unique acoustically designed VanAir doors (one building). No buildings included horizontally hung acoustic clouds. One of the buildings that uses carpet on portions of the radiant floor as its only acoustic treatment has 51% of the occupants satisfied with acoustics, the second highest of all buildings. This building also has low occupant density, which could contribute to lower sound pressure levels in the space. The other solutions do not appear to be highly effective based on comments and satisfaction scores. Outdoor noises are primarily a problem in Building 3 with automated windows. There happened to be nearby construction at the time of the survey that could have influenced responses, so it is not conclusive that this would remain the primary source of dissatisfaction. Acoustics continue to be a main area of design concern in buildings, much of it having to do with open-plan office and sound privacy. There have been few studies on whether radiant designs cause increased dissatisfaction, and successful studies will benefit from sound pressure measurements.

6 Limitations

Our analysis of the eight buildings is meant to provide insight into occupant satisfaction and perception that can help radiant building designers and building operators. Eight buildings represent a small sample, and we are aware that results may not be generalized. We chose buildings that showed various levels of occupant satisfaction and that were located in different climates to broaden the range of answers we could get. This also increased the variability between building designs and operation, which limited the common characteristics by which to assess. Our analysis is based on information provided in the occupant, building characteristics, radiant design, and facility operation surveys. The building and radiant design surveys were completed by knowledgeable contacts, and we assumed the information provided in these forms to be correct; we did not perform a fact checking review to assess the responses. The survey responses reflect the operation at the time they were filled and have limited ability to capture system-specific details. We did not gather any field measurements for factors influencing comfort or acoustics in the buildings. Additionally, we acknowledge that supplemental systems, such as upsized mechanical ventilation, may serve a portion of the heating and/or cooling loads in these buildings. More investigation is needed to better guide proper supplemental system sizing in high thermal mass radiant buildings. The occupant satisfaction survey has pre-defined options, which may not capture nuances or could be interpreted differently. The survey is voluntary, and respondents are not required to answer every question, so survey completeness and response rate is a concern. ASHRAE 55–2017 guidance suggests 35% response rate to increase accuracy and representation of a building’s population. We used occupant feedback from all of the eight buildings regardless of the response rate. Additionally, the occupant survey used in this analysis is meant to capture occupants’ subjective perceptions of their typical experience in the space, not of specific episodic events (e.g., right-now survey).

7 Conclusion

We conducted a post-occupancy assessment in eight buildings using embedded radiant systems (TABS or ESS). We investigated over 500 occupant survey responses in all eight buildings and interviewed building operators in six. Five buildings had at least 80% occupants reaching the ASHRAE 55–2017 criteria of thermal acceptability and seven had at least 75% reaching this criterion. The primary factors leading to temperature discomfort in these buildings were the lack of control over the thermal environment, both temperature and air movement, and the slow system response (i.e., high response time) for these systems. Occupant comfort trends in these buildings were not unique to radiant buildings. Features that appear to resolve the comfort issues included fast-response adaptive opportunities, such as operable windows that allow for group control, and/or personal fans or heaters that allow for individual control based on user thermal sensation and preference. These are important for designers and operators to consider in radiant buildings due to slow response time of the systems. Other factors contributing to temperature satisfaction were low risk for unwanted air movement, likely due to lower airflow rates in radiant spaces compared to all-air, and predictable temperatures. We did not find a specific radiant system design or control scheme that clearly outperformed the other from the point of view of thermal comfort; although, the sample size is small. Acoustics had low satisfaction across all eight buildings, and most issues stem from sound privacy in open-plan offices; there was no strong evidence linking sources of acoustic dissatisfaction with the radiant design. Strategies such as carpets and acoustical panels should be further explored for effectiveness, especially in open-plan office spaces.

Aggregated occupant satisfaction responses.

(XLS) Click here for additional data file. 7 Jun 2021 PONE-D-21-01672 Field evaluation of thermal and acoustical comfort in eight North-American buildings using embedded radiant systems PLOS ONE Dear Dr. Dawe, Thank you for submitting your manuscript to PLOS ONE. After careful consideration, we feel that it has merit but does not fully meet PLOS ONE’s publication criteria as it currently stands. Therefore, we invite you to submit a revised version of the manuscript that addresses the points raised during the review process. Please submit your revised manuscript by Jul 20 2021 11:59PM. If you will need more time than this to complete your revisions, please reply to this message or contact the journal office at plosone@plos.org. When you're ready to submit your revision, log on to https://www.editorialmanager.com/pone/ and select the 'Submissions Needing Revision' folder to locate your manuscript file. Please include the following items when submitting your revised manuscript: A rebuttal letter that responds to each point raised by the academic editor and reviewer(s). You should upload this letter as a separate file labeled 'Response to Reviewers'. A marked-up copy of your manuscript that highlights changes made to the original version. You should upload this as a separate file labeled 'Revised Manuscript with Track Changes'. An unmarked version of your revised paper without tracked changes. You should upload this as a separate file labeled 'Manuscript'. If you would like to make changes to your financial disclosure, please include your updated statement in your cover letter. Guidelines for resubmitting your figure files are available below the reviewer comments at the end of this letter. If applicable, we recommend that you deposit your laboratory protocols in protocols.io to enhance the reproducibility of your results. Protocols.io assigns your protocol its own identifier (DOI) so that it can be cited independently in the future. For instructions see: http://journals.plos.org/plosone/s/submission-guidelines#loc-laboratory-protocols. Additionally, PLOS ONE offers an option for publishing peer-reviewed Lab Protocol articles, which describe protocols hosted on protocols.io. Read more information on sharing protocols at https://plos.org/protocols?utm_medium=editorial-email&utm_source=authorletters&utm_campaign=protocols. We look forward to receiving your revised manuscript. Kind regards, Forrest Meggers Academic Editor PLOS ONE Journal Requirements: When submitting your revision, we need you to address these additional requirements. Please ensure that your manuscript meets PLOS ONE's style requirements, including those for file naming. The PLOS ONE style templates can be found at https://journals.plos.org/plosone/s/file?id=wjVg/PLOSOne_formatting_sample_main_body.pdf and https://journals.plos.org/plosone/s/file?id=ba62/PLOSOne_formatting_sample_title_authors_affiliations.pdf 2. Thank you for including your ethics statement: "The occupant survey data was collected and analyzed anonymously. IRB approval was granted for the surveys under CPHS protocol 2010-05-1550. Under this approval, only staff at the research institute are able to access and use the survey data." Please amend your current ethics statement to include the full name of the ethics committee/institutional review board(s) that approved your specific study. Once you have amended this/these statement(s) in the Methods section of the manuscript, please add the same text to the “Ethics Statement” field of the submission form (via “Edit Submission”). For additional information about PLOS ONE ethical requirements for human subjects research, please refer to http://journals.plos.org/plosone/s/submission-guidelines#loc-human-subjects-research. 3. Please provide additional details regarding participant consent. In the ethics statement in the Methods and online submission information, please ensure that you have specified (1) whether consent was informed and (2) what type you obtained (for instance, written or verbal, and if verbal, how it was documented and witnessed). If your study included minors, state whether you obtained consent from parents or guardians. If the need for consent was waived by the ethics committee, please include this information. If you are reporting a retrospective study of medical records or archived samples, please ensure that you have discussed whether all data were fully anonymized before you accessed them and/or whether the IRB or ethics committee waived the requirement for informed consent. If patients provided informed written consent to have data from their medical records used in research, please include this information 4. In your Data Availability statement, you have not specified where the minimal data set underlying the results described in your manuscript can be found. PLOS defines a study's minimal data set as the underlying data used to reach the conclusions drawn in the manuscript and any additional data required to replicate the reported study findings in their entirety. All PLOS journals require that the minimal data set be made fully available. For more information about our data policy, please see http://journals.plos.org/plosone/s/data-availability. Upon re-submitting your revised manuscript, please upload your study’s minimal underlying data set as either Supporting Information files or to a stable, public repository and include the relevant URLs, DOIs, or accession numbers within your revised cover letter. For a list of acceptable repositories, please see http://journals.plos.org/plosone/s/data-availability#loc-recommended-repositories. Any potentially identifying patient information must be fully anonymized. Important: If there are ethical or legal restrictions to sharing your data publicly, please explain these restrictions in detail. Please see our guidelines for more information on what we consider unacceptable restrictions to publicly sharing data: http://journals.plos.org/plosone/s/data-availability#loc-unacceptable-data-access-restrictions. Note that it is not acceptable for the authors to be the sole named individuals responsible for ensuring data access. We will update your Data Availability statement to reflect the information you provide in your cover letter. 5. Please include captions for your Supporting Information files at the end of your manuscript, and update any in-text citations to match accordingly. Please see our Supporting Information guidelines for more information: http://journals.plos.org/plosone/s/supporting-information. 6. Please review your reference list to ensure that it is complete and correct. If you have cited papers that have been retracted, please include the rationale for doing so in the manuscript text, or remove these references and replace them with relevant current references. Any changes to the reference list should be mentioned in the rebuttal letter that accompanies your revised manuscript. If you need to cite a retracted article, indicate the article’s retracted status in the References list and also include a citation and full reference for the retraction notice. 7. Thank you for submitting the above manuscript to PLOS ONE. During our internal evaluation of the manuscript, we found significant text overlap between your submission and the following previously published work, of which you are an author. https://escholarship.org/uc/item/6d95z6sw We would like to make you aware that copying extracts from previous publications, especially outside the methods section, word-for-word is unacceptable. In addition, the reproduction of text from published reports has implications for the copyright that may apply to the publications. Please revise the manuscript to rephrase the duplicated text, cite your sources, and provide details as to how the current manuscript advances on previous work. Please note that further consideration is dependent on the submission of a manuscript that addresses these concerns about the overlap in text with published work. We will carefully review your manuscript upon resubmission, so please ensure that your revision is thorough. Additional Editor Comments: Dear Megan, Caroline, Stefano, and Fred, First, I apologize for the delay and thank you for the excellent article and patience. I had a third reviewer I had hoped would complete a review, but I'm proceeding without it. The reviewers suggested revisions, one minor and one major. I am proceeding with suggesting minor revisions, but while I don't think the article needs major changes, it does need some major expansion in certain aspects detailed in the comments from the reviewers. One aspect I like about PLOS ONE is that the reviewer have the option to unblind their identity, which Reviewer 2 has done, and as Eric suggested major revisions feel free to work directly with him on his detailed comments in the attached PDF. I think both reviewers point to some issues with a lack of clarity between heating and cooling scenarios. I agree the relationship between draft and fans and in heating vs cooling scenarios should be considered how the body convectively exchanges with air that is either closer or farther from skin temperature is - Both of the broad and specific comments #3 from Eric and also mentioned by Reviewer 2 in the context of controls. I am happy to provide additional feedback if needed, and I promise to very quickly turn around your revised submission, and again sorry for the delay. It has been a challenging year and I hope you have all stayed safe and healthy. best, /Forrest [Note: HTML markup is below. Please do not edit.] Reviewers' comments: Reviewer's Responses to Questions Comments to the Author 1. Is the manuscript technically sound, and do the data support the conclusions? The manuscript must describe a technically sound piece of scientific research with data that supports the conclusions. Experiments must have been conducted rigorously, with appropriate controls, replication, and sample sizes. The conclusions must be drawn appropriately based on the data presented. Reviewer #1: Yes Reviewer #2: Yes ********** 2. Has the statistical analysis been performed appropriately and rigorously? Reviewer #1: Yes Reviewer #2: Yes ********** 3. Have the authors made all data underlying the findings in their manuscript fully available? The PLOS Data policy requires authors to make all data underlying the findings described in their manuscript fully available without restriction, with rare exception (please refer to the Data Availability Statement in the manuscript PDF file). The data should be provided as part of the manuscript or its supporting information, or deposited to a public repository. For example, in addition to summary statistics, the data points behind means, medians and variance measures should be available. If there are restrictions on publicly sharing data—e.g. participant privacy or use of data from a third party—those must be specified. Reviewer #1: Yes Reviewer #2: Yes ********** 4. Is the manuscript presented in an intelligible fashion and written in standard English? PLOS ONE does not copyedit accepted manuscripts, so the language in submitted articles must be clear, correct, and unambiguous. Any typographical or grammatical errors should be corrected at revision, so please note any specific errors here. Reviewer #1: Yes Reviewer #2: Yes ********** 5. Review Comments to the Author Please use the space provided to explain your answers to the questions above. You may also include additional comments for the author, including concerns about dual publication, research ethics, or publication ethics. (Please upload your review as an attachment if it exceeds 20,000 characters) Reviewer #1: See attachment. My main concerns for this paper are in reference to novelty in the interpretation of a small dataset in a field increasingly driven by large datasets for informed decision making. I believe there is a lot of novel potential, and a few reforming operations will greatly benefit this piece. Reviewer #2: Review In section 4.1, you should add a caveat to the use of TABS. Compared to radiant panels, TABS has a slow response time while panels are the fastest responding system. This is a significant difference. Another critical difference is that TABS has challenging control and basically, setpoints don't exist. The reason is that temperature measured across the slab thickness does not reflect slab surface temperature, especially when covered with carpet. In section 4 or section 5 or the Limitation section, you need to recognize the limitation of the data collection method. This is a widely used data collection method, but it has an inherent error that results can be biased, especially when we have low response rates. Lassen et al. (2020) reported this phenomenon. Discussion of this issue required a separate paper, so I am only asking to recognize this limitation, hoping that the scientific community will improve data collection or better understand the results. For example, we will understand what it means to have 30 responses out of 300 occupants, who is responding or voting and why. You address other issues very well in section 5. Lassen, N., Goia, F., Schiavon, S. and Pantelic, J., 2020. Field investigations of a smiley-face polling station for recording occupant satisfaction with indoor climate. Building and Environment, 185, p.107266. In Section 4.3 please add categories used. For example, how did you categorize information you received about the radiant system design? Please also include some indication of heating and cooling operation. How many buildings used both vs only one of these options. Line 276 - response time of the TABS is the essential factor. Another factor is the temperature of the surface that is exchanging heat with the occupants. How do we modulate that temperature? Slab temperature, slab surface temperature, and carpet (or similar top covering of the slab exchanging heat with the occupant) can have significantly different temperatures. You can find more details in Pantelic et al., (2018). Please discuss this issue also. Pantelic, J., Schiavon, S., Ning, B., Burdakis, E., Raftery, P. and Bauman, F., 2018. Full scale laboratory experiment on the cooling capacity of a radiant floor system. Energy and Buildings, 170, pp.134-144. Line 350 - how many design strategies you evaluated? In Table 2 there is a summary of the systems, but DOAS means that airside supplies only outdoor air, and there is no information about the size of air vs. radiant system. Radiant loop control would be equivalent to coil water side control that we never really consider in any discussion on thermal comfort, so I think this is a wrong parallel. As I mentioned above, the critical problem besides slow response is what is setpoint controlling? Perhaps this is a good place to discuss this since you mentioned other design issues. Lines 375-380 - this is interesting information. I understand that you can't make a significant conclusion based on the information provided, but it certainly points out an issue that needs further investigation. In the Conclusion section, you mention that one of the comfort improvement methods is to use a personal fan. That is true for warm conditions in summer. What would be the method for winter operation and cold conditions? I don't see support for the sentence "We did not find a specific radiant system design or control scheme that clearly outperformed the other from the point of view of thermal comfort." In my opinion, you didn't evaluate the system design, so please remove this sentence from the Conclusion section. ********** 6. PLOS authors have the option to publish the peer review history of their article (what does this mean?). If published, this will include your full peer review and any attached files. If you choose “no”, your identity will remain anonymous but your review may still be made public. Do you want your identity to be public for this peer review? For information about this choice, including consent withdrawal, please see our Privacy Policy. Reviewer #1: Yes: Eric Teitelbaum Reviewer #2: No [NOTE: If reviewer comments were submitted as an attachment file, they will be attached to this email and accessible via the submission site. Please log into your account, locate the manuscript record, and check for the action link "View Attachments". If this link does not appear, there are no attachment files.] While revising your submission, please upload your figure files to the Preflight Analysis and Conversion Engine (PACE) digital diagnostic tool, https://pacev2.apexcovantage.com/. PACE helps ensure that figures meet PLOS requirements. To use PACE, you must first register as a user. Registration is free. Then, login and navigate to the UPLOAD tab, where you will find detailed instructions on how to use the tool. If you encounter any issues or have any questions when using PACE, please email PLOS at figures@plos.org. Please note that Supporting Information files do not need this step. Submitted filename: Review v1 Dawe et al. PLOS One.pdf Click here for additional data file. 20 Jul 2021 We appreciate the thorough review and comments from reviewers and the editor. We have attached detailed responses to each reviewer comment and a new letter to the editor describing our revisions. Submitted filename: Response to Reviewers.docx Click here for additional data file. 8 Oct 2021 Field evaluation of thermal and acoustical comfort in eight North-American buildings using embedded radiant systems PONE-D-21-01672R1 Dear Dr. Dawe, We’re pleased to inform you that your manuscript has been judged scientifically suitable for publication and will be formally accepted for publication once it meets all outstanding technical requirements. Within one week, you’ll receive an e-mail detailing the required amendments. When these have been addressed, you’ll receive a formal acceptance letter and your manuscript will be scheduled for publication. An invoice for payment will follow shortly after the formal acceptance. To ensure an efficient process, please log into Editorial Manager at http://www.editorialmanager.com/pone/, click the 'Update My Information' link at the top of the page, and double check that your user information is up-to-date. If you have any billing related questions, please contact our Author Billing department directly at authorbilling@plos.org. If your institution or institutions have a press office, please notify them about your upcoming paper to help maximize its impact. If they’ll be preparing press materials, please inform our press team as soon as possible -- no later than 48 hours after receiving the formal acceptance. Your manuscript will remain under strict press embargo until 2 pm Eastern Time on the date of publication. For more information, please contact onepress@plos.org. Kind regards, Forrest Meggers Academic Editor PLOS ONE Additional Editor Comments (optional): First, thank you for your patience. Finding good reviewers has been a challenge. Congratulations on the excellent paper. I do agree with the reviewers initial suggestions for more analysis, but I also appreciate your response and recognize that more work is forthcoming. The new Reviewer 3 does bring up some excellent points, and while I'm suggesting an accept now, I hope you will consider adding a couple sentences in your discussion to address issues of sizing air side and radiant side components in the types of HVAC systems you have analyzed. As reviewer 3 points out, by not addressing system size aspects you leave a very open avenue for critique. I think you can get ahead of those criticisms by mentioning the air-side sizing and by adding a couple comments on the implications, as suggested. Thanks again for the hard work putting this together and please reach out if you would like any additional feedback. Reviewers' comments: Reviewer's Responses to Questions Comments to the Author 1. If the authors have adequately addressed your comments raised in a previous round of review and you feel that this manuscript is now acceptable for publication, you may indicate that here to bypass the “Comments to the Author” section, enter your conflict of interest statement in the “Confidential to Editor” section, and submit your "Accept" recommendation. Reviewer #1: All comments have been addressed Reviewer #3: All comments have been addressed ********** 2. Is the manuscript technically sound, and do the data support the conclusions? The manuscript must describe a technically sound piece of scientific research with data that supports the conclusions. Experiments must have been conducted rigorously, with appropriate controls, replication, and sample sizes. The conclusions must be drawn appropriately based on the data presented. Reviewer #1: Yes Reviewer #3: Yes ********** 3. Has the statistical analysis been performed appropriately and rigorously? Reviewer #1: Yes Reviewer #3: Yes ********** 4. Have the authors made all data underlying the findings in their manuscript fully available? The PLOS Data policy requires authors to make all data underlying the findings described in their manuscript fully available without restriction, with rare exception (please refer to the Data Availability Statement in the manuscript PDF file). The data should be provided as part of the manuscript or its supporting information, or deposited to a public repository. For example, in addition to summary statistics, the data points behind means, medians and variance measures should be available. If there are restrictions on publicly sharing data—e.g. participant privacy or use of data from a third party—those must be specified. Reviewer #1: Yes Reviewer #3: Yes ********** 5. Is the manuscript presented in an intelligible fashion and written in standard English? PLOS ONE does not copyedit accepted manuscripts, so the language in submitted articles must be clear, correct, and unambiguous. Any typographical or grammatical errors should be corrected at revision, so please note any specific errors here. Reviewer #1: Yes Reviewer #3: Yes ********** 6. Review Comments to the Author Please use the space provided to explain your answers to the questions above. You may also include additional comments for the author, including concerns about dual publication, research ethics, or publication ethics. (Please upload your review as an attachment if it exceeds 20,000 characters) Reviewer #1: Thank you for taking my comments into such thorough consideration, even the very high level ones. It is quite a fine manuscript, looking forward to seeing the final, formatted work. Reviewer #3: Thank you for this article. I want to be clear that I am not one of your original reviewers, but I have assesssed the reviewer comments, and agree that comments have been mostly addressed as identified. I do have one point to raise, that was partially raised by different reviewers on the generalisability of findings and the lack of thorough analysis of the design history of these buildings. I would like to offer an analogy to an issue I have with this assessment. In the general discourse of HVAC assessment of real-world buildings, we know that 'oversizing' of HVAC systems is a historical / persistent problem in industry. It is, by any measure, a common problem (see Djuneady et al. 2011). It's been observed and discussed so sufficiently in research literature, that we accept it as a norm. Any field study of a random sample of commercial buildings designed to ASHRAE standards is likely to encounter oversized HVAC systems. I propose that the same must apply to building with radiant systems, and here we have to accept how an oversized embedded radiant system would perform. If I combine a TABS with a DOAS, but I oversize that DOAS (and it has a heating / cooling coil), you can bet that DOAS will begin to do heavy lifting with respect to regulating indoor air and humidity. So it brings up the question, is an embedded radiant system with an oversized ventilation system a proper radiant system, or is it just a radiant-assisted mechanical ventilation system. The ERI@N office of NTU in Singapore comes to mind, which was precisely this: a radiant system with so much mechanical ventilation provided that the sensible cooling provided by the ceiling was trivial. Anecdotally, for those of us in this field, we know that many radiant systems have not been implemented in practise in a way where the radiant system is truly the primary medium of heating and cooling delivery. Once I start seeing a building with several 'supplementary' mechanical ventilation systems, I get an innate feeling that these are buildings where the radiant system - though advertised as important - ultimately becomes ancillary to the ventilation system comfort-wise. My question to you is how do you discern this, and can you? I propose two changes to the paper: to expand in the discussion on this issue, and provide some discussion on the extent to which the ventilation systems are satisfying the bulk of the sensible heating and cooling needs in these spaces. Ideally, I would recommend that you provide more data on these buildings. What are the sizes of the DOAS systems implemented? How much air are they providing? What kind of setpoints are the DOAS systems using for heating and cooling? And yes, ultimately, are the ventilation systems contributing significantly or marginally to sensible heating and cooling indoors? Without acknowledging this, as an expert in radiant systems, I think this reads as a weak study because it avoids acknowledging this very issue that is at the heart of radiant system design (and the success failure of historical projects). ********** 7. PLOS authors have the option to publish the peer review history of their article (what does this mean?). If published, this will include your full peer review and any attached files. If you choose “no”, your identity will remain anonymous but your review may still be made public. Do you want your identity to be public for this peer review? For information about this choice, including consent withdrawal, please see our Privacy Policy. Reviewer #1: Yes: Eric Teitelbaum Reviewer #3: No 18 Oct 2021 PONE-D-21-01672R1 Field evaluation of thermal and acoustical comfort in eight North-American buildings using embedded radiant systems Dear Dr. Dawe: I'm pleased to inform you that your manuscript has been deemed suitable for publication in PLOS ONE. Congratulations! Your manuscript is now with our production department. If your institution or institutions have a press office, please let them know about your upcoming paper now to help maximize its impact. If they'll be preparing press materials, please inform our press team within the next 48 hours. Your manuscript will remain under strict press embargo until 2 pm Eastern Time on the date of publication. For more information please contact onepress@plos.org. If we can help with anything else, please email us at plosone@plos.org. Thank you for submitting your work to PLOS ONE and supporting open access. Kind regards, PLOS ONE Editorial Office Staff on behalf of Dr. Forrest Meggers Academic Editor PLOS ONE
  5 in total

1.  Listening to the occupants: a Web-based indoor environmental quality survey.

Authors:  Leah Zagreus; Charlie Huizenga; Edward Arens; David Lehrer
Journal:  Indoor Air       Date:  2004       Impact factor: 5.770

2.  A power primer.

Authors:  J Cohen
Journal:  Psychol Bull       Date:  1992-07       Impact factor: 17.737

3.  Quantitative relationships between occupant satisfaction and satisfaction aspects of indoor environmental quality and building design.

Authors:  M Frontczak; S Schiavon; J Goins; E Arens; H Zhang; P Wargocki
Journal:  Indoor Air       Date:  2011-10-20       Impact factor: 5.770

4.  The National Human Activity Pattern Survey (NHAPS): a resource for assessing exposure to environmental pollutants.

Authors:  N E Klepeis; W C Nelson; W R Ott; J P Robinson; A M Tsang; P Switzer; J V Behar; S C Hern; W H Engelmann
Journal:  J Expo Anal Environ Epidemiol       Date:  2001 May-Jun

Review 5.  Air movement--good or bad?

Authors:  J Toftum
Journal:  Indoor Air       Date:  2004       Impact factor: 5.770

  5 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.