Adopting fresh air ventilation may reduce the risk of airborne transmission of SARS-CoV-2 in COVID-19 unit.

Habib Alkalamouni1, Eveline Hitti2, Hassan Zaraket3.   

Abstract

Entities:  

Mesh:

Year:  2021        PMID: 34480889      PMCID: PMC8409050          DOI: 10.1016/j.jinf.2021.08.046

Source DB:  PubMed          Journal:  J Infect        ISSN: 0163-4453            Impact factor:   6.072


× No keyword cloud information.
Dear Editor, With great interest we read the recently published letter by Julian and colleages highlighting the possibility of influenza airborne transmission as a result of using nebulizers. In the context of COVID-19, the use of nebulizers and other breathing aid devices is routine in the medical settings. However, high amounts of aerosols generated by these devices can expose healthcare workers and other patients to infectious particles thus increasing their risk of morbidity and mortality. Air samples have been shown to contain viable SARS-CoV-2 collected up to four meters away from COVID-19 patients in hospital rooms and isolation care units, and it was found that the viral load was significantly higher in patients fitted with a nasal cannula. The risk of airborne transmission of infectious agents can be mitigated by ventilation strategies. Since the majority of SARS-CoV-2 transmission occurs indoors, efficient ventilation systems that can dilute the viral concentration in the air is highly desirable. Recently, a surge of COVID-19 cases among our emergency department (ED) COVID-19 unit's staff involving 22% of the HCWs (3/20 physicians, 8/26 residents and housestaff, and 19/90 nurses) coincided with the national peak of COVID-19 cases averaging around 100,000 cases per month during that period. In contrast, only 3 COVID-19 cases were recorded among our 20 physicians during the proceeding 10 months. Case loads that exceeded our inpatient hospital capacity led to around 300 COVID-19 patients per month boarding in our 34 bed ED COVID-19 unit. Therefore, a decision was made to convert the ventilation settings from a 5.9 air changes per hour (ACH) with a 35% recirculated air and 65% fresh air to 5.9 ACH with 100% fresh air only. We aimed to assess the risk of exposure of healthcare workers by measuring SARS-CoV-2 viral load in air samples following the change in ventilation strategy. Air samples were collected inside the ED COVID-19 unit using the Coriolis µ microbial air sampler (Bertin Technologies) at a flow rate of 200 L/min for 20 min over two consecutive days. Air samples were collected in the COVID-19 unit hallway, near the staff station, and in patient rooms. Negative control samples were collected at the beginning and end of each sampling day. In addition, swabs or air vents from within the unit were also collected for analysis. The SARS-CoV-2 viral load (gene copy number) in each sample was then assessed using quantitative real-time reverse transcriptase polymerase chain reaction (qRT-PCR) targeting the ORF1b gene (further details available upon request). Sixteen COVID-19 patients (full capacity) were present in the unit during sampling. They were wearing either a surgical mask or a breathing aid device . Four air samples were collected in the COVID-19 unit hallway, and five return air vents from the same locations were also swabbed for analysis (Fig. 1 ). In addition, four patient rooms were air sampled at a distance of one meter away from the patient. The patients in the sampled rooms were either intubated, fitted with a high-flow nasal cannula, a BiPAP (bilevel positive airway pressure), or wearing a surgical mask.
Fig. 1

Layout of the COVID-19 unit indicating sampling locations.

Layout of the COVID-19 unit indicating sampling locations. All air samples tested negative for SARS-CoV-2 RNA. Consistently, all air vent swabs were negative, indicating either minimal (below detection limit) or absence of SARS-CoV-2 in the air inside the COVID-19 unit during the sampling period following changing air ventilation to 100% fresh air. Therfore, we expect no or minimal risk to the staff under these conditions especially with the proper use of PPEs. Our findings are in contrast with previous studies reporting the detection of SARS-CoV-2 infectious particles and RNA in air samples collected from ICUs and airborne infection isolation rooms (AIIRs). In our study, all the patients were ED boarders; i.e., patients requiring inpatient care but receiving care in the ED pending hospital bed availability, with an average ED length of stay of 250 h (range 11–483 h). Except for the patient who was wearing a surgical mask, all patients were exhibiting severe symptoms of COVID-19 and were still in the infectious phase of their illness as judged by their duration of symptoms and illness severity. Hospitalized patients have been shown to shed SARS-CoV-2 for prolonged periods (2–4 weeks from the onset of symptoms. Therefore, although the virological status of the patients in our COVID-19 unit was not confirmed at the time of sampling, it is highly likely that the patients were still shedding virus at the time of sampling and that shutting off air recirculation contributed to the lack of detectable virus in the environmental samples. This is consistent with recommendations to avoid air recirculation, as it can transport infectious particles from one space to another if they are connected through the same ventilation system. Air recirculation was implicated as the primary cause of SARS-CoV-2 transmission between cabins on the Diamond Princess cruise ship during the quarantine period, which fueled the outbreak. Likewise, a study by Shen et al. reported a 34.3% higher risk of transmission caused by air recirculation in a bus with an infected person. Therefore, circulating fresh air into COVID-19 facilities should be considered as one of the means to reduce the viral load in the environment and reduce the risk of exposure by HCWs. Overall, the results are assuring that by supplying fresh air into the COVID-19 unit the risk of SARS-CoV-2 exposure to staff can be mitigated.
  9 in total

Review 1.  Role of ventilation in airborne transmission of infectious agents in the built environment - a multidisciplinary systematic review.

Authors:  Y Li; G M Leung; J W Tang; X Yang; C Y H Chao; J Z Lin; J W Lu; P V Nielsen; J Niu; H Qian; A C Sleigh; H-J J Su; J Sundell; T W Wong; P L Yuen
Journal:  Indoor Air       Date:  2007-02       Impact factor: 5.770

2.  Community Outbreak Investigation of SARS-CoV-2 Transmission Among Bus Riders in Eastern China.

Authors:  Ye Shen; Changwei Li; Hongjun Dong; Zhen Wang; Leonardo Martinez; Zhou Sun; Andreas Handel; Zhiping Chen; Enfu Chen; Mark H Ebell; Fan Wang; Bo Yi; Haibin Wang; Xiaoxiao Wang; Aihong Wang; Bingbing Chen; Yanling Qi; Lirong Liang; Yang Li; Feng Ling; Junfang Chen; Guozhang Xu
Journal:  JAMA Intern Med       Date:  2020-12-01       Impact factor: 21.873

3.  Viable SARS-CoV-2 in the air of a hospital room with COVID-19 patients.

Authors:  John A Lednicky; Michael Lauzardo; Z Hugh Fan; Antarpreet Jutla; Trevor B Tilly; Mayank Gangwar; Moiz Usmani; Sripriya Nannu Shankar; Karim Mohamed; Arantza Eiguren-Fernandez; Caroline J Stephenson; Md Mahbubul Alam; Maha A Elbadry; Julia C Loeb; Kuttichantran Subramaniam; Thomas B Waltzek; Kartikeya Cherabuddi; J Glenn Morris; Chang-Yu Wu
Journal:  Int J Infect Dis       Date:  2020-09-16       Impact factor: 3.623

4.  Nebulisers as a potential source of airborne virus.

Authors:  Julian W Tang; Petri Kalliomaki; Taru M Varila; Matti Waris; Hannu Koskela
Journal:  J Infect       Date:  2020-05-15       Impact factor: 6.072

5.  How can airborne transmission of COVID-19 indoors be minimised?

Authors:  Lidia Morawska; Julian W Tang; William Bahnfleth; Philomena M Bluyssen; Atze Boerstra; Giorgio Buonanno; Junji Cao; Stephanie Dancer; Andres Floto; Francesco Franchimon; Charles Haworth; Jaap Hogeling; Christina Isaxon; Jose L Jimenez; Jarek Kurnitski; Yuguo Li; Marcel Loomans; Guy Marks; Linsey C Marr; Livio Mazzarella; Arsen Krikor Melikov; Shelly Miller; Donald K Milton; William Nazaroff; Peter V Nielsen; Catherine Noakes; Jordan Peccia; Xavier Querol; Chandra Sekhar; Olli Seppänen; Shin-Ichi Tanabe; Raymond Tellier; Kwok Wai Tham; Pawel Wargocki; Aneta Wierzbicka; Maosheng Yao
Journal:  Environ Int       Date:  2020-05-27       Impact factor: 9.621

6.  Airborne route and bad use of ventilation systems as non-negligible factors in SARS-CoV-2 transmission.

Authors:  G Correia; L Rodrigues; M Gameiro da Silva; T Gonçalves
Journal:  Med Hypotheses       Date:  2020-04-25       Impact factor: 1.538

7.  Detection of air and surface contamination by SARS-CoV-2 in hospital rooms of infected patients.

Authors:  Po Ying Chia; Kristen Kelli Coleman; Yian Kim Tan; Sean Wei Xiang Ong; Marcus Gum; Sok Kiang Lau; Xiao Fang Lim; Ai Sim Lim; Stephanie Sutjipto; Pei Hua Lee; Than The Son; Barnaby Edward Young; Donald K Milton; Gregory C Gray; Stephan Schuster; Timothy Barkham; Partha Pratim De; Shawn Vasoo; Monica Chan; Brenda Sze Peng Ang; Boon Huan Tan; Yee-Sin Leo; Oon-Tek Ng; Michelle Su Yen Wong; Kalisvar Marimuthu
Journal:  Nat Commun       Date:  2020-05-29       Impact factor: 14.919

8.  Duration and key determinants of infectious virus shedding in hospitalized patients with coronavirus disease-2019 (COVID-19).

Authors:  Jeroen J A van Kampen; David A M C van de Vijver; Pieter L A Fraaij; Bart L Haagmans; Mart M Lamers; Nisreen Okba; Johannes P C van den Akker; Henrik Endeman; Diederik A M P J Gommers; Jan J Cornelissen; Rogier A S Hoek; Menno M van der Eerden; Dennis A Hesselink; Herold J Metselaar; Annelies Verbon; Jurriaan E M de Steenwinkel; Georgina I Aron; Eric C M van Gorp; Sander van Boheemen; Jolanda C Voermans; Charles A B Boucher; Richard Molenkamp; Marion P G Koopmans; Corine Geurtsvankessel; Annemiek A van der Eijk
Journal:  Nat Commun       Date:  2021-01-11       Impact factor: 14.919

9.  Preventing Infection of Patients and Healthcare Workers Should Be the New Normal in the Era of Novel Coronavirus Epidemics.

Authors:  Andrew Bowdle; L Silvia Munoz-Price
Journal:  Anesthesiology       Date:  2020-06       Impact factor: 7.892

  9 in total
  2 in total

Review 1.  An Old Defence Against New Infections: The Open-Air Factor and COVID-19.

Authors:  Richard Hobday; Peter Collignon
Journal:  Cureus       Date:  2022-06-20

2.  Nationwide evaluation of energy and indoor air quality predictive control and impact on infection risk for cooling season.

Authors:  Xuezheng Wang; Bing Dong; Jianshun Jensen Zhang
Journal:  Build Simul       Date:  2022-09-30       Impact factor: 4.008

  2 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.