| Literature DB >> 33187274 |
Abstract
In recent years, the need for comfortable visual environments in indoor spaces has increased energy use in buildings. There have been diverse studies on using a light shelf to solve this problem. It is an effective system that allows external natural light deep into indoor spaces through reflection. However, prior studies have used light shelves with a fixed reflectivity, and there are few studies on improving the visual environment through light shelf control. Therefore, this study proposes a movable light shelf with a rolling reflector that can change the reflectivity. To achieve these objectives, we conducted a performance evaluation of the system's ability to save energy and improve the visual environment. This study built a real scale testbed and conducted a performance evaluation by deriving values for lighting energy consumption, uniformity, and luminance contrast depending on the light shelf variables. We conclude that (1) the light shelf system achieved an energy savings of 13.6% and 5.7%, respectively, compared to a fixed type light shelf, whose reflectivity cannot be changed, and a traditional movable light shelf; (2) in terms of improving the visual environment, results suggest that the visual environment could be improved using a light shelf by deriving light shelf variables that disturb indoor uniformity; and (3) the results verified glare generation conditions by deriving luminance contrast caused by the variables of light shelf angle and its reflectivity.Entities:
Keywords: light shelf; performance evaluation; reflectivity; rolling type; visual comfort
Year: 2020 PMID: 33187274 PMCID: PMC7696370 DOI: 10.3390/ijerph17228338
Source DB: PubMed Journal: Int J Environ Res Public Health ISSN: 1660-4601 Impact factor: 3.390
Figure 1Light shelf concept and variables.
Review of prior studies on the light shelf.
| Author | Light Shelf Variables to Improve Its Performance | Light Shelf Reflectivity Setup for Performance Evaluation | Consideration of Glare Caused by Light Reflectivity |
|---|---|---|---|
| Soler and Oteiza [ | Fixed light shelf variables | Fixed to 91% | Not considered |
| Soler and Oteiza [ | Fixed light shelf variables | Fixed to 91% | Not considered |
| Claros and Soler [ | Fixed light shelf variables | Fixed to 84% | Not considered |
| Claros and Soler [ | Width, angle, height, reflectivity | Performance evaluation was conducted by considering light shelf reflectivity (50%, 60%, 70%, 80%, 90%), but reflectivity was not changed per case during performance evaluation. | Not considered |
| Freewan et al. [ | Fixed light shelf variables | Fixed to 85% | Not considered |
| Raphael [ | Angle | Fixed to 60% | Not considered |
| Lim and Ahmad [ | Height, shape | Fixed to 51.29% | Not considered |
| Lim and Heng [ | Shape, height, width | Fixed to 51.29% | Not considered |
| Lee et al. [ | Perforation rate of a reflector, angle, width | Fixed to 85% | Not considered |
| Berardi and Anaraki [ | Fixed light shelf variables | Fixed to 80% | Not considered |
| Lee [ | Angle | Fixed to 85% | Not considered |
| Lee et al. [ | Curvature, angle | Fixed to 85% | Not considered |
| Meresi [ | Width, angle, reflectivity | Performance evaluation was conducted by considering light shelf reflectivity (50%, 60%, 70%, 80%, 90%), but reflectivity was not changed per case during performance evaluation. | Not considered |
| Moazzeni and Ghiabaklou [ | Width, angle | Fixed to 90% | Not considered |
| Mangkuto et al. [ | Width, angle, reflectivity | Performance evaluation was conducted by considering light shelf reflectivity (60%, 70%, 80%, 90%), but reflectivity was not changed per case during performance evaluation. | Not considered |
Figure 2Natural light entering a room depending on light shelf angle and height: (a) natural light entering a room when light shelf angle is 0°; (b) natural light entering a room when light shelf angle is 20°; (c) natural light entering a room when light shelf height is 1.8 m; (d) natural light entering a room when light shelf height is 1.5 m.
Consideration of optimal indoor illuminance standards by country.
| Illuminance Standard | Type of Activity | Scope (lx) | ||
|---|---|---|---|---|
| Minimum Allowed Illumination | Standard Allowed Illumination | Maximum Allowed Illumination | ||
| IES (Illuminating Engineering Society) (USA) [ | General (performance of visual tasks of medium contrast) | 500 | 750 | 1000 |
| JIS (Japan Industrial Standard) Z 9110 (Japan) [ | 300 | 500 | 600 | |
| KS (Korean Industrial Standards) A 3011 (Republic of Korea) [ | 300 | 400 | 600 | |
Figure 3Internal structure of a light shelf with a rolling reflector.
Overview of testbed.
| Room Size and Reflexibility | |
|---|---|
| Size | 4.9 m (W) × 6.6 m (D) × 2.5 m (H) |
| Reflexibility | Ceiling 86%, Wall 46%, Floor 25% |
| Window size and material | |
| Size | 1.9 m (W) × 1.7 m (H) |
| Type | Double glazed 12 mm 12 mm (3 Clean + 6 Air + 3 Clean) |
| Transmissivity | 80% |
| Lighting | |
| Type | Eight-level dimming (LED-type) 4ea |
| Dimensions (mm) | 600 × 600 |
| Dimming range | 10–100% |
| Energy consumption for phased light dimming | 0 kWh (OFF), 12.3 kWh (Dimming Level 1), 18.3 kWh (Dimming Level 2), 22.0 kWh (Dimming Level 3), 27.7 kWh (Dimming Level 4), 34.0 kWh (Dimming Level 5), 38.5 kWh (Dimming Level 6), 42.6 kWh (Dimming Level 7), and 50.8 kWh (Dimming Level 8) |
| Illuminance sensor | |
| Sensing element | Silicon photosensor, with filter |
| Precision | ±3% |
| Artificial solar light radiation apparatus | |
| Precision of solar light radiation | Grade A (according to ASTM E927-85) |
| Directions | South aspect |
| Energy monitoring system | |
| Model | SPM-141 |
| Measurement capacity | Single-phase (220 V, 1–50 A) |
| Error rate | Within 2.0% |
Figure 4Overview of testbed and measurement apparatus: (a) performance evaluation testbed; (b) artificial solar irradiation apparatus; (c) control of light source angle of artificial solar irradiation apparatus; (d) lever to control light source altitude of artificial solar irradiation apparatus; (e) installed light shelf; (f) eight-level lighting controller; (g) illuminance sensor monitoring server; (h) energy monitoring system.
Figure 5Cross-section and plane of testbed and sensor location.
Configuration of meridian altitude of the sun and external illuminance for summer, middle season, and winter.
| Season | Meridian Altitude | External Illuminance (lx) |
|---|---|---|
| Summer | 76.5 | 80,000 |
| Middle season | 52.5 | 60,000 |
| Winter | 29.5 | 30,000 |
Figure 6Light distribution curve and conical illuminance of lighting: (a) conical illuminance; (b) light distribution.
Cases for performance evaluation.
| Case | Light Shelf Variables | ||||
|---|---|---|---|---|---|
| Type | Height | Angle | Width | Reflectivity | |
| 1 | External light shelf | 1.8 m | Fixed to 0° | 0.3 m | Fixed to 85% |
| 2 | −10°–30° (10° steps) | 0.3 m | Fixed to 85% | ||
| 3 | 0.38 m | Changeable to 70%, 85%, and 97% | |||
Figure 7Glare measurement position and measurement spots.
Specifications and image of luminance meter.
| Details | Product and Measurement Images | |
|---|---|---|
| Model | Luminance Meter LS-100 (Tokyo, Japan) |
|
| Type | SLR spot luminance meter for measuring light source and surface brightness | |
| Measuring range | FAST: 0.001–299,900 cd/m2, SLOW: 0.001–49,990 cd/m2 | |
| Angle of view | 9° | |
| Accuracy | ±2% ±2 digits of displayed value |
Performance evaluation results of Case 1 and Case 2: analysis of uniformity, glare, and lighting energy consumption.
| Season | Light Shelf | Illumination Sensor (lx) | U | Luminance (cd/m3) | L | Lighting Dimming Control: Light Number (Dimming Level) | Lighting Energy Consumption (kWh) | |||
|---|---|---|---|---|---|---|---|---|---|---|
| A | R (%) | Min. | Ave. | Max. | Ave. | |||||
| Summer | −10 | 85 | 68.2 | 347.1 | 0.197 | 2848.4 | 681.5 | 4.2 | 1(8) + 3(8) + 2(5) | 2.034 |
| 0 | 85 | 73.6 | 372.3 | 0.198 | 3111.1 | 711.1 | 4.4 | 1(8) + 3(8) + 2(5) | 2.034 | |
| 10 | 85 | 78.5 | 387.5 | 0.203 | 9224.7 | 1169.4 | 7.9 | 1(8) + 3(8) + 2(5) | 2.034 | |
| 20 | 85 | 81.9 | 391.9 | 0.209 | 9294.4 | 1185.3 | 7.8 | 1(8) + 3(8) + 2(4) | 1.939 | |
| 30 | 85 | 90.5 | 383.4 | 0.236 | 9814.2 | 1233.6 | 8.0 | 1(8) + 3(8) + 2(3) | 1.855 | |
| Middle season | −10 | 85 | 120.2 | 346.8 | 0.347 | 4606.0 | 1202.6 | 3.8 | 1(8)→3(7) | 2.802 |
| 0 | 85 | 125.4 | 355.7 | 0.353 | 4918.0 | 1269.9 | 3.9 | 1(8)→3(6) | 2.679 | |
| 10 | 85 | 131.5 | 359.1 | 0.366 | 12,539.7 | 1840.0 | 6.8 | 1(8)→3(5) | 2.544 | |
| 20 | 85 | 139.9 | 369.1 | 0.379 | 12,588.6 | 1809.2 | 7.0 | 1(8)→3(5) | 2.544 | |
| 30 | 85 | 149.6 | 469.7 | 0.318 | 17,659.0 | 1865.2 | 9.5 | 1(8)→3(4) | 2.354 | |
| Winter | −10 | 85 | 249.5 | 4928.2 | 0.051 | 11,247.8 | 1959.7 | 5.7 | 1(5) | 0.510 |
| 0 | 85 | 255.9 | 5044.6 | 0.051 | 11,472.6 | 1989.3 | 5.8 | 1(5) | 0.510 | |
| 10 | 85 | 265.8 | 5142.5 | 0.052 | 12,843.6 | 1947.7 | 6.6 | 1(4) | 0.415 | |
| 20 | 85 | 270.5 | 5278.8 | 0.051 | 18,432.5 | 2048.3 | 9.0 | 1(4) | 0.415 | |
| 30 | 85 | 247.9 | 5087.7 | 0.049 | 12,202.4 | 1952.7 | 6.2 | 1(5) | 0.510 | |
Note; A: Angle, R: Reflectivity, Min.: Minimum Ave.: Average, U: Uniformity factor, L: Luminance contrast.
Light shelf angle for lighting energy saving and total lighting energy consumption for Case 1 and Case 2.
| Case | Season | Light Shelf Angle for Energy Saving | Lighting Energy Consumption (kWh) | Total Lighting Energy Consumption (kWh) |
|---|---|---|---|---|
| 1 | Summer | Fixed to 0° | 2.034 | 5.290 |
| Middle season | 2.679 | |||
| Winter | 0.577 | |||
| 2 | Summer | 30° | 1.855 | 4.624 |
| Middle season | 30° | 2.354 | ||
| Winter | 10° | 0.415 |
Performance evaluation results of Case 3: analysis of uniformity, glare, and lighting energy consumption.
| Season | Light Shelf | Illumination Sensor (lx) | U | Luminance (cd/m3) | L | Lighting Dimming Control: Light Number (Dimming Level) | Lighting Energy Consumption (kWh) | |||
|---|---|---|---|---|---|---|---|---|---|---|
| A | R(%) | Min. | Ave. | Max. | Ave. | |||||
| Summer | −10 | 70 | 54.3 | 280.3 | 0.194 | 2273.3 | 548.1 | 4.1 | 1(8) + 3(8) + 2(6) | 2.102 |
| 85 | 67.4 | 341.8 | 0.197 | 2879.7 | 678.1 | 4.2 | 1(8) + 3(8) + 2(5) | 2.034 | ||
| 97 | 76.1 | 384.0 | 0.198 | 3235.4 | 745.9 | 4.3 | 1(8) + 3(8) + 2(5) | 2.034 | ||
| 0 | 70 | 58.6 | 300.6 | 0.195 | 2482.9 | 571.8 | 4.3 | 1(8) + 3(8) + 2(6) | 2.102 | |
| 85 | 72.7 | 366.6 | 0.198 | 3145.3 | 707.5 | 4.4 | 1(8) + 3(8) + 2(5) | 2.034 | ||
| 97 | 82.2 | 411.9 | 0.200 | 3533.8 | 778.3 | 4.5 | 1(8) + 3(8) + 2(4) | 1.939 | ||
| 10 | 70 | 62.7 | 313.0 | 0.200 | 7362.2 | 940.5 | 7.8 | 1(8) + 3(8) + 2(5) | 2.034 | |
| 85 | 77.8 | 381.7 | 0.204 | 9326.2 | 1163.6 | 8.0 | 1(8) + 3(8) + 2(4) | 1.939 | ||
| 97 | 88.1 | 428.9 | 0.205 | 10642.8 | 1280.0 | 8.3 | 1(8) + 3(8) + 2(3) | 1.855 | ||
| 20 | 70 | 65.3 | 316.6 | 0.206 | 7417.8 | 953.2 | 7.8 | 1(8) + 3(8) + 2(5) | 2.034 | |
| 85 | 81.0 | 386.1 | 0.210 | 9396.6 | 1179.4 | 8.0 | 1(8) + 3(8) + 2(4) | 1.939 | ||
| 97 | 91.8 | 433.8 | 0.212 | 10723.2 | 1297.3 | 8.3 | 1(8) + 3(8) + 2(3) | 1.855 | ||
| 30 | 70 | 71.9 | 309.6 | 0.232 | 7832.7 | 992.0 | 7.9 | 1(8) + 3(8) + 2(5) | 2.034 | |
| 85 | 89.3 | 377.6 | 0.236 | 9922.2 | 1227.4 | 8.1 | 1(8) + 3(8) + 2(3) | 1.855 | ||
| 97 | 101.3 | 424.2 | 0.239 | 11323.0 | 1350.1 | 8.4 | 1(8) + 3(8) + 2(2) | 1.799 | ||
| Middle season | −10 | 70 | 96.0 | 280.1 | 0.343 | 3676.1 | 967.1 | 3.8 | 1(8) + 3(8) + 2(1) | 3.419 |
| 85 | 118.4 | 341.6 | 0.347 | 4656.7 | 1196.6 | 3.9 | 1(8) + 3(7) | 2.802 | ||
| 97 | 133.7 | 383.8 | 0.348 | 5314.1 | 1316.3 | 4.0 | 1(8) + 3(5) | 2.544 | ||
| 0 | 70 | 100.6 | 286.3 | 0.351 | 3925.0 | 1021.3 | 3.8 | 1(8) + 3(8) | 3.049 | |
| 85 | 124.1 | 349.1 | 0.355 | 4972.1 | 1263.6 | 3.9 | 1(8) + 3(6) | 2.679 | ||
| 97 | 140.2 | 392.2 | 0.357 | 5674.0 | 1390.0 | 4.1 | 1(8) + 3(4) | 2.354 | ||
| 10 | 70 | 104.2 | 289.5 | 0.360 | 10007.8 | 1479.7 | 6.8 | 1(8) + 3(8) | 3.049 | |
| 85 | 129.5 | 353.1 | 0.367 | 12677.6 | 1830.8 | 6.9 | 1(8) + 3(5) | 2.544 | ||
| 97 | 147.8 | 396.7 | 0.373 | 14467.4 | 2013.9 | 7.2 | 1(8) + 3(4) | 2.354 | ||
| 20 | 70 | 111.2 | 297.9 | 0.373 | 10046.9 | 1455.0 | 6.9 | 1(8) + 3(7) | 2.802 | |
| 85 | 138.2 | 363.3 | 0.380 | 12727.1 | 1800.2 | 7.1 | 1(8) + 3(4) | 2.354 | ||
| 97 | 149.6 | 391.1 | 0.382 | 14923.9 | 1980.2 | 7.5 | 1(8) + 3(4) | 2.354 | ||
| 30 | 70 | 118.9 | 378.9 | 0.314 | 14093.5 | 1500.0 | 9.4 | 1(8) + 3(7) | 2.802 | |
| 85 | 147.6 | 462.1 | 0.319 | 17853.2 | 1855.9 | 9.6 | 1(8) + 3(4) | 2.354 | ||
| 97 | 159.9 | 498.5 | 0.321 | 20673.7 | 2041.5 | 10.1 | 1(8) + 3(2) | 2.074 | ||
| Winter | −10 | 70 | 202.2 | 3962.6 | 0.051 | 8865.9 | 1600.0 | 5.5 | 1(5) | 0.510 |
| 85 | 247.3 | 4853.3 | 0.051 | 11247.8 | 1959.7 | 5.7 | 1(4) | 0.415 | ||
| 97 | 280.8 | 5481.4 | 0.051 | 12769.6 | 2213.3 | 5.8 | 1(4) | 0.415 | ||
| 0 | 70 | 207.4 | 4052.1 | 0.051 | 9070.1 | 1624.2 | 5.6 | 1(5) | 0.510 | |
| 85 | 253.6 | 4962.9 | 0.051 | 11472.6 | 1989.3 | 5.8 | 1(4) | 0.415 | ||
| 97 | 287.9 | 5605.2 | 0.051 | 13078.8 | 2251.4 | 5.8 | 1(4) | 0.415 | ||
| 10 | 70 | 215.3 | 4130.9 | 0.052 | 10154.0 | 1590.2 | 6.4 | 1(5) | 0.510 | |
| 85 | 263.3 | 5059.4 | 0.052 | 12843.6 | 1947.7 | 6.6 | 1(4) | 0.415 | ||
| 97 | 298.9 | 5714.1 | 0.052 | 14732.4 | 2204.3 | 6.7 | 1(4) | 0.415 | ||
| 20 | 70 | 219.1 | 4246.1 | 0.052 | 14746.0 | 1672.4 | 8.8 | 1(5) | 0.510 | |
| 85 | 268.0 | 5200.6 | 0.052 | 18432.5 | 2048.3 | 9.0 | 1(4) | 0.415 | ||
| 97 | 304.3 | 5873.6 | 0.052 | 21251.6 | 2313.4 | 9.2 | 1(4) | 0.415 | ||
| 30 | 70 | 200.9 | 4092.5 | 0.049 | 10045.0 | 1913.6 | 5.2 | 1(5) | 0.510 | |
| 85 | 245.7 | 5012.4 | 0.049 | 10250.02 | 1952.7 | 5.2 | 1(4) | 0.415 | ||
| 97 | 278.9 | 5661.1 | 0.049 | 10506.3 | 1991.8 | 5.3 | 1(4) | 0.415 | ||
Note; A: Angle, R: Reflectivity, Min.: Minimum Ave.: Average, U: Uniformity factor, L: Luminance contrast.
Light shelf angle for lighting energy saving and total lighting energy consumption for Case 3.
| Season | Light Shelf Variables for Energy Saving | Lighting Energy Consumption (kWh) | Total Lighting Energy Consumption (kWh) | |
|---|---|---|---|---|
| Angle | Reflectivity | |||
| Summer | 30 | 97 | 1.799 | 4.288 |
| Middle season | 30 | 97 | 2.074 | |
| Winter | 30 | 97 | 0.415 | |
Figure 8Analysis of uniformity per light shelf angle: (a) uniformity per light shelf angle in summer; (b) uniformity per light shelf angle in middle season; (c) uniformity per light shelf angle in winter.
Figure 9Diagram of light flow into a room per light shelf angle: (a) light shelf angle 30° in summer; (b) light shelf angle 20° in middle season; (c) light shelf angle 30° in winter.
Figure 10Analysis of luminance contrast per light shelf angle: (a) per light shelf angle in summer; (b) luminance contrast per light shelf angle in middle season; (c) luminance contrast per light shelf angle in winter.
Figure 11Analysis of luminance contrast per light shelf angle and reflectivity: (a) luminance contrast per light shelf angle and reflectivity in summer; (b) luminance contrast per light shelf angle and reflectivity in middle season; (c) luminance contrast per light shelf angle and reflectivity in winter.
Analysis of light shelf variables and lighting energy consumption to improve energy saving and visual environment.
| Case | Season | Light Shelf Variables to Improve Energy Saving, Uniformity, and Glare | Lighting Energy Consumption (kWh) | Total Lighting Energy Consumption (kWh) | |
|---|---|---|---|---|---|
| Angle | Reflectivity | ||||
| 2 | Summer | 30 | Fixed to 85% | 1.885 | 4.844 |
| Middle season | 20 | 2.544 | |||
| Winter | 10 | 0.415 | |||
| 3 | Summer | 30 | 97% | 1.799 | 4.568 |
| Middle season | 20 | 97% | 2.354 | ||
| Winter | 10 | 85% | 0.415 | ||
Figure 12Performance evaluation results by case: total lighting energy usage.
Figure 13Maintenance of reflector through reflector rolling (application of clean brush system).