| Literature DB >> 33071439 |
Mingyue Guo1, Peng Xu1, Tong Xiao1, Ruikai He1, Mingkun Dai1, Shelly L Miller2.
Abstract
Various organizations and societies around the globe have issued guidelines in response to the coronavirus disease (COVID-19) and virus (SARS-CoV-2). In this paper, heating, ventilating, and air-conditioning-related guidelines or documents in several major countries and regions have been reviewed and compared, including those issued by the American Society of Heating Refrigerating and Air-Conditioning Engineers, the Federation of European Heating, Ventilation, and Air Conditioning Associations, the Society of Heating, Air-Conditioning and Sanitary Engineers of Japan, Architectural Society of China, and the Chinese Institute of Refrigeration. Most terms and suggestions in these guidelines are consistent with each other, although there are some conflicting details, reflecting the underlying uncertainty surrounding the transmission mechanism and characteristics of COVID-19 in buildings. All guidelines emphasize the importance of ventilation, but the specific ventilation rate that can eliminate the risk of transmission of airborne particulate matter has not been established. The most important countermeasure, commonly agreed countermeasures, the conflicting content from different guidelines, and further work have been summarized in this paper.Entities:
Keywords: COVID-19; Guidance; HVAC; SARS-CoV-2
Year: 2020 PMID: 33071439 PMCID: PMC7548082 DOI: 10.1016/j.buildenv.2020.107368
Source DB: PubMed Journal: Build Environ ISSN: 0360-1323 Impact factor: 6.456
Fig. 1Theoretical aerobiology of transmission of droplets and small airborne particles produced by an infected patient with an acute infection (from ASHRAE) [14].
Fig. 2Exposure mechanisms of SARS-CoV-2, SARS-CoV-1 and other flu viruses in buildings (from REHVA [16]).
Table A.1 comparison of the main strategies
| ASHRAE | REHVA | SHASE | Related Society of China | |
|---|---|---|---|---|
Increase the amount of outdoor air. Open outdoor air dampers, as high as 100% if possible. | Supply as much outdoor air as reasonably possible. Switch the terminal devices to 100% outdoor air if possible. Open windows regularly. | Supply as much outdoor air as reasonably possible. Switch the terminal devices to 100% outdoor air if possible. Open windows regularly. | Supply as much outdoor air as reasonably possible. Switch the terminal devices to 100% outdoor air if possible. The ratio of outdoor air should be greater than 40%. | |
Operate HVAC related devices to provide flushing 2 hours before and post occupancies. Keep the system on for 24 h a day, 7 days a week if possible. Disable DCV. | Run ventilation at the nominal speed for at least 2 h before occupancies and at a lower speed 2 h after occupancies. Run toilet ventilation system for 24 h a day, 7 days a week. In DCV systems, change the CO2 setpoint to 400 ppm. | Increase the running time of HVAC equipment, running it continuously for 24 h if possible. Run the exhaust system in toilets continuously. Lower the CO2 setpoint. | Increase the air supply temperature in heating mode and decrease the temperature in cooling mode. | |
Control the temperature and humidity is beneficial. But the temperature and relative humidity setpoint should be considered on a case-by-case basis. | There is no need to adjust the temperature and humidity setpoint. | The temperature should be controlled between 17 and 28 °C, and the relative humidity should be controlled between 40 and 70%. | Haven't mentioned. | |
The air should flow from safe areas to unsafe areas, from personal use areas to public areas. | Ensure the negative pressure in the toilets. | Ensure the negative pressure in the toilets. | A slight positive pressure should be maintained in the kitchen. Keep negative pressure in toilets. | |
Improve the level of the central air filter as much as possible, at least to the grade of MERV-13. | Filters should be replaced and maintained as usual. | For a system with 100% outdoor air, the filter can be operated as usual. For return air operation, check the differential pressure of the filter more often and replace the filter sooner than usual. | Maintain filters as usual. | |
HEPA filters and UVGI are recommended. | It is recommended to locate the air-cleaning device close to the breathing zone. Special UV cleaning equipments installed for the supply air or room air treatment are also effective. | Air cleaners are effective as auxiliary devices. Ventilation is more effective than air cleaners. | Indoor air cleaners should be operated. UV devices shouldn't be installed in the HVAC system. | |
Check the status of heat recovery wheels in the systems for leakage. | If heat exchangers with leakage below 5%, operate with increasing amount of outdoor air ventilation. Else, operate with an increased ventilation rate. | For the static total heat exchanger, operate in heat exchange mode. For the rotary type, if return air pressure is less than supply air pressure, operate with a large effective ventilation volume. | Indirect heat exchangers and other heat exchangers can operate as usual. Rotary heat exchangers are not recommended to be used. | |
Create the strategic plan prior to opening a building. | Close the lid when flushing toilets. Avoid dried-out water seals. | Close the lid when flushing toilets. Check water seals regularly. | Check water seals regularly. Keep the uplift ventilation pipe. |