| Literature DB >> 29049017 |
Robert Fitzhenry, Don Weiss, Dan Cimini, Sharon Balter, Christopher Boyd, Lisa Alleyne, Renee Stewart, Natasha McIntosh, Andrea Econome, Ying Lin, Inessa Rubinstein, Teresa Passaretti, Anna Kidney, Pascal Lapierre, Daniel Kass, Jay K Varma.
Abstract
The incidence of Legionnaires' disease in the United States has been increasing since 2000. Outbreaks and clusters are associated with decorative, recreational, domestic, and industrial water systems, with the largest outbreaks being caused by cooling towers. Since 2006, 6 community-associated Legionnaires' disease outbreaks have occurred in New York City, resulting in 213 cases and 18 deaths. Three outbreaks occurred in 2015, including the largest on record (138 cases). Three outbreaks were linked to cooling towers by molecular comparison of human and environmental Legionella isolates, and the sources for the other 3 outbreaks were undetermined. The evolution of investigation methods and lessons learned from these outbreaks prompted enactment of a new comprehensive law governing the operation and maintenance of New York City cooling towers. Ongoing surveillance and program evaluation will determine if enforcement of the new cooling tower law reduces Legionnaires' disease incidence in New York City.Entities:
Keywords: Legionnaires’ disease; New York City; United States; bacteria; bacterial infection; cooling towers; disease outbreaks; environmental exposure; epidemiology; legionellosis; legislation; pneumonia; space-time clustering
Mesh:
Year: 2017 PMID: 29049017 PMCID: PMC5652439 DOI: 10.3201/eid2311.161584
Source DB: PubMed Journal: Emerg Infect Dis ISSN: 1080-6040 Impact factor: 6.883
Community outbreaks of Legionnaires’ disease, New York City, New York, USA, 2006–2015*
| NYC borough (outbreak no.) | Outbreak dates | Outbreak zone ZIP codes | No. cases |
| Crude rate† | Median age, y (range) | No. deaths, all cases | No. patients | Environmental testing results | ||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Outbreak total (zone residents) | Rest of NYC | Outbreak zone | Rest of NYC | ||||||||
| Bronx (1) | Jun–Oct 2006 | 10460, 10461, 10462, 10472, 10473 | 29 (29) | 87 |
| 9.7 | 1.1 | 57 (38–91) | 1 | 0 | No sampling performed at time of outbreak |
| Manhattan (2) | Aug–Sep 2008 | 10018, 10019, 10036 | 7 (7) | 36 |
| 9.8 | 0.4 | 64 (46–81) | 0 | 0 | Supportive housing potable water |
| Bronx (3) | Nov 2014–Jan 2015 | 10475 | 8 (8) | 41 |
| 18.8 | 0.5 | 58 (29–69) | 0 | 1 | Residential potable water (no |
| Queens (4) | Apr–Jun 2015 | 11354, 11355 | 16 (14) | 26 |
| 9.2 | 0.3 | 65 (50–99) | 0 | 0 | Potable water of 2 housing complexes (6 PCR+, |
| Bronx (5) | Jul–Aug 2015 | 10451, 10452, 10454, 10455, 10456, 10459, 10474 | 138 (108) | 48 |
| 25.7 | 0.6 | 55 (30–90) | 16 | 26 (23) | All (55) identified CTs in outbreak zone (14 culture+ for |
| Bronx (6) | Sep–Oct 2015 | 10461, 10462, 10469 | 15 (10) | 18 | 5.0 | 0.2 | 56 (31–71) | 1 | 4 | All (50) identified CTs in outbreak zone (8 culture+ for | |
*CT, cooling tower; Lp, Legionella pneumophila; NYC, New York City; +, positive. †Cases/100,000 population.
Timeline for investigations of community outbreaks of Legionnaires’ disease, New York City, New York, USA, 2006–2015*
| Outbreak no. | Date outbreak detected | Method of outbreak detection | Outbreak source | Date implicated CT initially sampled | Date implicated tower first reported with | Date remediation of implicated CT began | Date CT linked to human case by DNA typing | Days from | Days from detection to source identification |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 2006 Oct 2 | Detected by epidemiologist | ND | NA | NA | NA | NA | NA | NA |
| 2 | 2008 Sep 15 | Detected by epidemiologist, then by historical limits method | ND | NA | NA | NA | NA | NA | NA |
| 3 | 2014 Dec 1 | Historical limits method, then BIN | Power plant CT | 2015 Jan 7 | 2015 Jan 9 | 2015 Jan 10 | 2015 Jan 23 | 40 | 53 |
| 4 | 2015 May 7 | SaTScan | ND | NA | NA | NA | NA | NA | NA |
| 5 | 2015 Jul 17 | SaTScan | Hotel CT | 2015 Jul 29 | 2015 Jul 30 | 2015 Jul 31 | 2015 Aug 12 | 14 | 26 |
| 6 | 2015 Sep 25 | Detected by epidemiologist, then by SaTScan | Worksite CT | 2015 Sep 26 | 2015 Sep 29 | 2015 Sep 29 | 2015 Oct 16 | 4 | 21 |
*BIN, building identifiers; CT, cooling tower; Lp, Legionella pneumophila; NA, not applicable; ND, not determined; SaTScan, space-time permutation scan statistic.