| Literature DB >> 27706062 |
Wai Ling Lee1, Jie Jia2, Yani Bao3.
Abstract
Excessive lead has been found in drinking water in Hong Kong in tests carried out in 2015. Investigations have identified that the problem in public rental housing estates was caused by the problematic solders used in the plumbing, and recommendations on enhancing the quality control system and strengthening the relevant water quality standards have been proposed. The cause for the same problem happening in other premises where soldering has not been adopted for water pipe connections is left unidentified. Considering the unidentified cause and the recommendations made, this study aims to identify the gaps in practice followed in Hong Kong for safeguarding the water quality of new installations. A holistic review of governing ordinances and regulations, products and materials used and the testing and commissioning requirements adopted in Hong Kong and elsewhere in the world were conducted. Based on international practices and parametric analysis, it was found that there are gaps in practices followed in Hong Kong, which are directly and indirectly leading to the lead-in-water crisis. Recommendations for improvement in the quality control system, and the water quality standards including the allowable lead content and leaching limit for products and materials and the testing and commissioning requirements on plumbing installations have been made. The review and the identified gaps would become useful reference for countries in strengthening their relevant water quality standards.Entities:
Keywords: allowable lead contents; engineering aspects; lead in water; quality control system; regulations and ordinances; testing and commissioning
Mesh:
Substances:
Year: 2016 PMID: 27706062 PMCID: PMC5086709 DOI: 10.3390/ijerph13100970
Source DB: PubMed Journal: Int J Environ Res Public Health ISSN: 1660-4601 Impact factor: 3.390
Comparison of legislation structure and relevant standards in various regions.
| Geographic Entity | Enforcing Authority | Regulation | Standards & Guidelines | Installation |
|---|---|---|---|---|
| US | Environmental Protection Agency | Safe Drinking Water Act (SDWA) | Simultaneous Compliance Guidance Manual | Licensed Plumber |
| Canada | Health Canada | SDWA | Guidance on Controlling Corrosion in Drinking Water Distribution Systems | |
| Australia | Department of Health & Medical Research Council | SDWA | Australian Drinking Water Guidelines | |
| New Zealand | Ministry of Health | SDWA | Guidelines for Drinking-Water Quality Management for New Zealand | |
| UK | Secretary of State for the Environment, Transport and the Regions | Water Industry Act and Water Supply (Water Quality) Regulations | Guidance on the Implementation of the Water Supply (Water Quality) Regulations | |
| Hong Kong | Water Supplies Department | Waterworks Ordinance and the Sub-Legislature Waterworks Regulations | Plumbing Installation for Buildings Specific to Hong Kong |
Comparison of maximum allowable lead content (by % of weight) in copper pipe and copper alloy valves and fittings in various geographic entities.
| Geographic Entity | US * | Canada * | Australia | New Zealand | UK | Hong Kong |
|---|---|---|---|---|---|---|
| Copper Pipes | 0.25% | 0.25% | 0.05% | 0.085% | ||
| Copper Alloy Gate Valves | 0.25% | 0.25% | 4.5% | 8% | ||
| Facuets | 0.25% | 0.25% | 4.5% | not specified | ||
| Solder | 0.2% | 0.2% | 0.1% | 0% | ||
| Other Copper Alloy Valves and Fittings | 0.25% | 0.25% | 4.5% | 3% | ||
| Weighted-Average | ≤0.25% | ≤0.25% | Nil | Nil | ||
Remarks: * In total wetted parts.
Leaching limits and leaching test requirements.
| Description | US | Canada | Australia | New Zealand | UK | |
|---|---|---|---|---|---|---|
| Test Sample | Materials or Finished Products | Only for Non-Metallic Products | ||||
| Test Method | in-the-Product (all Samples except Solder); Immersion (Solder) | |||||
| Sample Size | in-the Product | Smallest Inner Diameter | ||||
| Immersion (Minimum Surface Area to Volume Ratio) | 5000 mm2/L | 1000 mm2/L | ||||
| Sample Pre-Test | Cleaning | Rinsed with Contaminate-Free Water | Rinsed in Flowing Tap Water | |||
| Conditioning in Test Water | for Minimum 2 days | for 24 h | ||||
| Test Water | pH value | Minimum 6.5 (Pipings) and 5 (Valves and Fittings) | Minimum 6.5 | |||
| Temperature | 23 ± 2 °C | 20 ± 2 °C | ||||
| Exposure Time | 24 ± 1 h | 24 ± 2 h | ||||
| Container | in-the Product | Capped with Inert Materials | ||||
| Immersion Test | Materials Inert to the Test Water | Glass or Polyethylene Ware | ||||
| Single Product Allowable Leaching Limit | ≤0.5 µg/L | ≤10 µg/L (Duplicate Samples) | ||||
Sampling protocols for copper pipelines of different regions.
| Description | US | Canada 1 | Australia | New Zealand | UK 2 | Hong Kong | |
|---|---|---|---|---|---|---|---|
| Number of Draws | Two-Tier | One-Tier | |||||
| Drawing Method | Unflushed | after a Stagnation Period of 6–12 h | 30 min | not Specified | |||
| Flushed | Flush for a While to 5 min | Flush for 2–5 min | |||||
| Sample Volume (L) | 1 | 1 | 0.1 | 0.15 | 1 | 0.25 | |
| Sampling Location | Random | Drinking or Cooking Taps | Representative Points | Consumer Taps | Determined by WSD | ||
| Sampling Size Confidence Level | 95% | not Specified | 95% | not Specified | Exact Number of Sampling Points Specified | ||
| Container | Fully Filled | not Specified | Thoroughly Rinsed | ||||
| Sample Holding Time | not Specified | 28 Days | within the Same Day | 7 Days | within the Same Day | ||
| Sampling Water Temperature | Cold | Cold | Constant | Cold | Constant | Cold | |
| Compliance | unflushed | 90% | 90% | 95% | 100% | not Specified | |
| ≤15 µg/L | ≤10 µg/L | ≤10 µg/L | ≤10 µg/L | ||||
| flushed | 100% | 100% | |||||
| ≤15 µg/L | ≤10 µg/L | ||||||
Remarks: 1 Canada’s regulations are provincial. The actual sampling protocol may differ by provinces. 2 UK adopts Random Daytime Sampling approach to estimate the lead problem in a water supply zone. The consumer tap being sampled is not flushed before taking the water sample. Should excessive lead components be present, two-tier sampling protocol at the consumer tap will be adopted. WSD = Water Supplies Department.
Consensus rules for the two tiers of sampling approach.
| Description | Unflushed | Flushed |
|---|---|---|
| Drawing Method | after a Period of Stagnation of 30 min to 12 h | Flush at a Uniform Rate for 2 to 5 min |
| Sample Volume | 0.1 L | |
| Sample Location | Sample Sites throughout the System and High Risk Areas | High Risk Areas |
| Sample Size | 95% Confidence Level Related to Population Size | 10% of the Tier-1 Sample Sites including the Problematic Sites |
| Compliance | 95% Non-Exceedance | 100% Non-Exceedance |
| Container | thoroughly Rinsed Container Provided by Recognized Laboratory | |
| Sample Holding Time | Deliver to Recognized Laboratory within a Day | |
| Sampling Water Temperature | Cold Water Pipeline at Constant Temperature | |
| Compliance | 10 µg/L | |
Figure 1Proposed and current quality control system. Remarks: LP = licensed plumber; AP = authorized person; PIC = plumbing installation contractor.
Figure 2A simplified schematic diagram of the plumbing installation.
Weighted lead content (WLC) prediction.
| Item | Diameter | Pipe/Fitting | Length (m) | Wetted Surface Area (m2) | Ratio Wetted Surface Area | UK/Hong Kong | Australia/New Zealand | US/Canada | |||
|---|---|---|---|---|---|---|---|---|---|---|---|
| % Lead Content | % Lead Contribution | % Lead Content | % Lead Contribution | % Lead Content | % Lead Contribution | ||||||
| AB | 150 | Pipe | 152 | 71,628.5 | 0.5421 | 0.085 | 0.0461 | 0.05 | 0.0271 | 0.25 | 0.1355 |
| A1 | 150 | Elbow | 0.267 | 125.8 | 0.0010 | 3 | 0.0029 | 4.5 | 0.0043 | 0.25 | 0.0002 |
| CD | 150 | Pipe | 15 | 7068.6 | 0.0535 | 0.085 | 0.0045 | 0.05 | 0.0027 | 0.25 | 0.0134 |
| C1 | 150 | Elbow | 0.3 | 141.4 | 0.0011 | 3 | 0.0032 | 4.5 | 0.0048 | 0.25 | 0.0003 |
| C2 | 150 | Elbow | 0.3 | 141.4 | 0.0011 | 3 | 0.0032 | 4.5 | 0.0048 | 0.25 | 0.0003 |
| DE | 150 | Pipe | 4 | 1885.0 | 0.0143 | 0.085 | 0.0012 | 0.05 | 0.0007 | 0.25 | 0.0036 |
| D1 | 150 | Valve | 0.267 | 125.8 | 0.0010 | 8 | 0.0076 | 4.5 | 0.0043 | 0.25 | 0.0002 |
| EF | 150 | Pipe | 10 | 4712.4 | 0.0357 | 0.085 | 0.0030 | 0.05 | 0.0018 | 0.25 | 0.0089 |
| E1 | 150 | Valve | 0.267 | 125.8 | 0.0010 | 8 | 0.0076 | 4.5 | 0.0043 | 0.25 | 0.0002 |
| E2 | 150 | Elbow | 0.3 | 141.4 | 0.0011 | 3 | 0.0032 | 4.5 | 0.0048 | 0.25 | 0.0003 |
| FG | 150 | Pipe | 38 | 17,907.1 | 0.1355 | 0.085 | 0.0115 | 0.05 | 0.0068 | 0.25 | 0.0339 |
| F1 | 150 | Valve | 0.267 | 125.8 | 0.0010 | 8 | 0.0076 | 4.5 | 0.0043 | 0.25 | 0.0002 |
| F2 | 150 | Socket | 0.267 | 125.8 | 0.0010 | 3 | 0.0029 | 4.5 | 0.0043 | 0.25 | 0.0002 |
| GH | 100 | Pipe | 38 | 11,938.1 | 0.0904 | 0.085 | 0.0077 | 0.05 | 0.0045 | 0.25 | 0.0226 |
| G1 | 100 | Elbow | 0.2 | 62.8 | 0.0005 | 3 | 0.0014 | 4.5 | 0.0021 | 0.25 | 0.0001 |
| HI | 100 | Pipe | 38 | 11,938.1 | 0.0904 | 0.085 | 0.0077 | 0.05 | 0.0045 | 0.25 | 0.0226 |
| H1 | 100 | Elbow | 0.2 | 62.8 | 0.0005 | 3 | 0.0014 | 4.5 | 0.0021 | 0.25 | 0.0001 |
| IJ | 100 | Pipe | 4 | 1256.6 | 0.0095 | 0.085 | 0.0008 | 0.05 | 0.0005 | 0.25 | 0.0024 |
| I1 | 100 | Elbow | 0.2 | 62.8 | 0.0005 | 3 | 0.0014 | 4.5 | 0.0021 | 0.25 | 0.0001 |
| I2 | 100 | Valve | 0.203 | 63.8 | 0.0005 | 8 | 0.0039 | 4.5 | 0.0022 | 0.25 | 0.0001 |
| I3 | 100 | Socket | 0.203 | 63.8 | 0.0005 | 3 | 0.0014 | 4.5 | 0.0022 | 0.25 | 0.0001 |
| JK | 25 | Pipe | 15 | 1178.1 | 0.0089 | 0.085 | 0.0008 | 0.05 | 0.0004 | 0.25 | 0.0022 |
| J1 | 25 | Valve | 0.165 | 13.0 | 0.0001 | 8 | 0.0008 | 4.5 | 0.0004 | 0.25 | 0.0000 |
| J2 | 25 | Elbow | 0.05 | 3.9 | 0.0000 | 3 | 0.0001 | 4.5 | 0.0001 | 0.25 | 0.0000 |
| J3 | 25 | Elbow | 0.05 | 3.9 | 0.0000 | 3 | 0.0001 | 4.5 | 0.0001 | 0.25 | 0.0000 |
| KL | 25 | Pipe | 15 | 1178.1 | 0.0089 | 0.085 | 0.0008 | 0.05 | 0.0004 | 0.25 | 0.0022 |
| K1 | 25 | Valve | 0.165 | 13.0 | 0.0001 | 8 | 0.0008 | 4.5 | 0.0004 | 0.25 | 0.0000 |
| K2 | 25 | Elbow | 0.05 | 3.9 | 0.0000 | 3 | 0.0001 | 4.5 | 0.0001 | 0.25 | 0.0000 |
| K3 | 25 | Elbow | 0.05 | 3.9 | 0.0000 | 3 | 0.0001 | 4.5 | 0.0001 | 0.25 | 0.0000 |
| K4 | 25 | Cold water faucet | 0.165 | 13.0 | 0.0001 | 4.5 | 0.0004 | 4.5 | 0.0004 | 0.25 | 0.0000 |
| Misc | 87 | Solder | 0.058 | 15.9 | 0.0001 | 0 | 0 | 0.1 | 0.0000 | 0.2 | 0.0000 |
| 0.1342 | 0.098 | 0.25 | |||||||||
Remarks: solder joints of 2 mm wide were assumed before and after each fitting; calculations were based on Equation (1), and data on Table 2.
Lead leaching concentration (LLC) prediction.
| Item | Diameter | Pipe/Fitting | Length (m) | Wetted Surface Area (m2) | Ratio Wetted Surface Area | US/Canada | Australia/New Zealand | ||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| AB | 150 | Pipe | 152 | 71,628.5 | 0.5421 | 4.18 | 2.09 | 1.1330 | 47.752 | 47,752.3 | 258.868 |
| A1 | 150 | Elbow | 0.267 | 125.8 | 0.0010 | 1 | 0.50 | 0.0005 | 0.084 | 83.9 | 0.001 |
| CD | 150 | Pipe | 15 | 7068.6 | 0.0535 | 0.41 | 0.21 | 0.0110 | 4.712 | 4712.4 | 2.521 |
| C1 | 150 | Elbow | 0.3 | 141.4 | 0.0011 | 1 | 0.50 | 0.0005 | 0.094 | 94.2 | 0.001 |
| C2 | 150 | Elbow | 0.3 | 141.4 | 0.0011 | 1 | 0.50 | 0.0005 | 0.094 | 94.2 | 0.001 |
| DE | 150 | Pipe | 4 | 1885.0 | 0.0143 | 0.11 | 0.06 | 0.0008 | 1.257 | 1256.6 | 0.179 |
| D1 | 150 | Valve | 0.267 | 125.8 | 0.0010 | 1 | 0.50 | 0.0005 | 0.084 | 83.9 | 0.001 |
| EF | 150 | Pipe | 10 | 4712.4 | 0.0357 | 0.28 | 0.14 | 0.0049 | 3.142 | 3141.6 | 1.120 |
| E1 | 150 | Valve | 0.267 | 125.8 | 0.0010 | 1 | 0.50 | 0.0005 | 0.084 | 83.9 | 0.001 |
| E2 | 150 | Elbow | 0.3 | 141.4 | 0.0011 | 1 | 0.50 | 0.0005 | 0.094 | 94.2 | 0.001 |
| FG | 150 | Pipe | 38 | 17,907.1 | 0.1355 | 1.05 | 0.52 | 0.0708 | 11.938 | 11,938.1 | 16.179 |
| F1 | 150 | Valve | 0.267 | 125.8 | 0.0010 | 1 | 0.50 | 0.0005 | 0.084 | 83.9 | 0.001 |
| F2 | 150 | Socket | 0.267 | 125.8 | 0.0010 | 1 | 0.50 | 0.0005 | 0.084 | 83.9 | 0.001 |
| GH | 100 | Pipe | 38 | 11,938.1 | 0.0904 | 1.05 | 0.52 | 0.0472 | 7.959 | 7958.7 | 7.191 |
| G1 | 100 | Elbow | 0.2 | 62.8 | 0.0005 | 1 | 0.50 | 0.0002 | 0.042 | 41.9 | 2.0 × 10−4 |
| HI | 100 | Pipe | 38 | 11,938.1 | 0.0904 | 10.64 | 5.32 | 0.4808 | 7.959 | 7958.7 | 7.191 |
| H1 | 100 | Elbow | 0.2 | 62.8 | 0.0005 | 1 | 0.50 | 2.4 × 10−4 | 0.042 | 41.9 | 2.0 × 10−4 |
| IJ | 100 | Pipe | 4 | 1256.6 | 0.0095 | 0.11 | 0.06 | 5.2 × 10−4 | 0.838 | 837.8 | 8.0 × 10−2 |
| I1 | 100 | Elbow | 0.2 | 62.8 | 0.0005 | 1 | 0.50 | 2.4 × 10−4 | 0.042 | 41.9 | 2.0 × 10−4 |
| I2 | 100 | Valve | 0.203 | 63.8 | 0.0005 | 1 | 0.50 | 2.4 × 10−4 | 0.043 | 42.5 | 2.1 × 10−4 |
| I3 | 100 | Socket | 0.203 | 63.8 | 0.0005 | 1 | 0.50 | 2.4 × 10−4 | 0.043 | 42.5 | 2.1 × 10−4 |
| JK | 25 | Pipe | 15 | 1178.1 | 0.0089 | 0.08 | 0.04 | 3.7 × 10−4 | 0.785 | 785.4 | 7.0 × 10−2 |
| J1 | 25 | Valve | 0.165 | 13.0 | 0.0001 | 1 | 0.50 | 4.9 × 10−5 | 0.009 | 8.6 | 8.5 × 10−6 |
| J2 | 25 | Elbow | 0.05 | 3.9 | 0.0000 | 1 | 0.50 | 1.5 × 10−5 | 0.003 | 2.6 | 7.8 × 10−7 |
| J3 | 25 | Elbow | 0.05 | 3.9 | 0.0000 | 1 | 0.50 | 1.5 × 10−5 | 0.003 | 2.6 | 7.8 × 10−7 |
| KL | 25 | Pipe | 15 | 1178.1 | 0.0089 | 0.41 | 0.21 | 1.8 × 10−3 | 0.785 | 785.4 | 0.070 |
| K1 | 25 | Valve | 0.165 | 13.0 | 0.0001 | 1 | 0.50 | 4.9 × 10−5 | 0.009 | 8.6 | 8.5 × 10−6 |
| K2 | 25 | Elbow | 0.05 | 3.9 | 0.0000 | 1 | 0.50 | 1.5 × 10−5 | 0.003 | 2.6 | 7.8 × 10−7 |
| K3 | 25 | Elbow | 0.05 | 3.9 | 0.0000 | 1 | 0.50 | 1.5 × 10−5 | 0.003 | 2.6 | 7.8 × 10−7 |
| K4 | 25 | Cold Water Faucet | 0.165 | 13.0 | 0.0001 | 1 | 0.50 | 4.9 × 10−5 | 0.009 | 8.6 | 8.5 × 10−6 |
| Misc | 87 | Solder | 0.058 | 15.9 | 0.0001 | 1 | 0.50 | 6.0 × 10−5 | 0.011 | 10.6 | 1.3 × 10−5 |
| 1.76 | - | 293.5 | |||||||||
Remarks: LL was estimated based on Equation (3).
Drinking water pH value.
| Description | US | Canada | Australia | New Zealand | UK | Hong Kong |
|---|---|---|---|---|---|---|
| pH Value | 6.5–8.5 | 7–10.5 | 6.5–7.5 | 6–8 | 6.5–9.5 | 6.4–9.2 |
| Reference | [ | [ | [ | [ | [ | [ |