Abstract

General ventilation with recirculated air may be cost-effective to control the concentration of low-toxicity, contaminants in workplaces with diffuse, dusty operations, such as in agriculture. Such systems are, however, rarely adopted with little evidence showing improved air quality and ability to operate under harsh conditions. The goal of this work was to examine the initial and long-term performance of a fabric-filter shaker dust collector (SDC) in laboratory tests and as deployed within a recirculating ventilation system in an agricultural building. In laboratory tests, collection efficiency and pressure drop were tracked over several filter loading cycles, and the recovery of filter capacity (pressure drop) from filter shaking was examined. Collection efficiencies of particles larger than 5 μm was high (>95%) even when the filter was pristine, showing effective collection of large particles that dominate inhalable concentrations typical of agricultural dusts. For respirable-sized particles, collection efficiencies were low when the filter was pristine (e.g., 27% for 1 μm) but much higher when a dust cake developed on the filter (>99% for all size particles), even after shaking (e.g., 90% for 1 μm). The first shake of a filter was observed to recovery a substantial fraction of filter capacity, with subsequent shakes providing little benefit. In field tests, the SDC performed effectively over a period of three months in winter when incorporated in a recirculating ventilation system of a swine farrowing room. Trends in collection efficiency and pressure drop with loading were similar to those observed in the laboratory with overall collection efficiencies high (>80%) when pressure drop exceeded 230 Pa, or 23% of the maximum loading recommended by the manufacturer. This work shows that the SDC can function effectively over the harsh winter in swine rearing operations. Together with findings of improved air quality in the farrowing room reported in a companion manuscript, this article provides evidence that an SDC represents a cost-effective solution to improve air quality in agricultural settings.

Entities:  

Keywords:  air cleaner; dust; fabric filter; general ventilation; indoor air quality; inhalable particles

Mesh:

Substances:

Year:  2015        PMID: 25955507      PMCID: PMC4753559          DOI: 10.1080/15459624.2015.1043056

Source DB:  PubMed          Journal:  J Occup Environ Hyg        ISSN: 1545-9624            Impact factor:   2.155


  7 in total

1.  Predicting historical dust and wood dust exposure in sawmills: model development and validation.

Authors:  M C Friesen; H W Davies; K Teschke; S Marion; P A Demers
Journal:  J Occup Environ Hyg       Date:  2005-12       Impact factor: 2.155

Review 2.  Hazardous agents in agricultural dusts and methods of evaluation.

Authors:  K J Donham
Journal:  Am J Ind Med       Date:  1986       Impact factor: 2.214

3.  Modeled effectiveness of ventilation with contaminant control devices on indoor air quality in a swine farrowing facility.

Authors:  T Renée Anthony; Ralph Altmaier; Jae Hong Park; Thomas M Peters
Journal:  J Occup Environ Hyg       Date:  2014       Impact factor: 2.155

4.  Use of Recirculating Ventilation With Dust Filtration to Improve Wintertime Air Quality in a Swine Farrowing Room.

Authors:  T Renée Anthony; Ralph Altmaier; Samuel Jones; Rich Gassman; Jae Hong Park; Thomas M Peters
Journal:  J Occup Environ Hyg       Date:  2015       Impact factor: 2.155

5.  Organic barn dust extract exposure impairs porcine macrophage function in vitro: implications for respiratory health.

Authors:  Susan M Knetter; Christopher K Tuggle; Michael J Wannemuehler; Amanda E Ramer-Tait
Journal:  Vet Immunol Immunopathol       Date:  2013-11-05       Impact factor: 2.046

6.  Respiratory dysfunction in swine production facility workers: dose-response relationships of environmental exposures and pulmonary function.

Authors:  K J Donham; S J Reynolds; P Whitten; J A Merchant; L Burmeister; W J Popendorf
Journal:  Am J Ind Med       Date:  1995-03       Impact factor: 2.214

Review 7.  Concentrated swine feeding operations and public health: a review of occupational and community health effects.

Authors:  D Cole; L Todd; S Wing
Journal:  Environ Health Perspect       Date:  2000-08       Impact factor: 9.031

  7 in total
  2 in total

1.  Simulation of air quality and operational cost to ventilate swine farrowing facilities in Midwest U.S. during winter.

Authors:  Jae Hong Park; Thomas M Peters; Ralph Altmaier; Samuel M Jones; Richard Gassman; T Renée Anthony
Journal:  Trans ASABE       Date:  2017       Impact factor: 1.188

2.  Assessment of Interventions to Improve Air Quality in a Livestock Building.

Authors:  T Renée Anthony; Anthony Y Yang; Thomas M Peters
Journal:  J Agric Saf Health       Date:  2017-11-20
  2 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.