Sasan Sadrizadeh1, Ann Tammelin2, Peter V Nielsen3, Sture Holmberg1.
Abstract
BACKGROUND: Air-borne bacteria in the operating room (OR) may contaminate the surgical wound, either by direct sedimentation from the air or indirectly, by contaminated sterile instruments. Reduced air contamination can be achieved with an efficient ventilation system. The current study assesses the additive effect of a mobile laminar airflow (MLAF) unit on the microbiological air quality in an OR supplied with turbulent-mixing air ventilation.Entities:
Keywords: Air-borne bacteria; CFD simulation; Colony-forming unit; Microbiological air quality; Mobile ultraclean exponential laminar airflow screen; Operating room
Year: 2014 PMID: 25006349 PMCID: PMC4086264 DOI: 10.1186/1754-9493-8-27
Source DB: PubMed Journal: Patient Saf Surg ISSN: 1754-9493
Figure 1An isometric view of the OR model.
Figure 2Two MLAF units in an OR. Photo from South Hospital (Södersjukhuset), Stockholm.
Mean values of volumetric bacteria-carrying particles for different centerline velocity of the mobile laminar screen unit
| off | 19.08 (9–32) | 18.12 (13–28) | 7.66 (5–24) |
| 0.2 | 9.94 (4–12) | 8.36 (3–13) | 1.82 (1–4) |
| 0.4 | 1.21 (1–4) | 1.14 (0–5) | 0.90 (0–3) |
| 0.6 | 0.72 (0–3) | 0.08 (0–1) | 0.08 (0–1) |
| 0.8 | 0.04 (0–1) | 0.06 (0–1) | 0.00 (0–0) |
| 1.0 | 0.00 (0–0) | 0.00 (0–0) | 0.00 (0–0) |
CFD simulation results were based on active air-sampling method. (CFU: colony-forming unit, MLAF: mobile laminar airflow).
Mean values of sedimenting bacteria-carrying particles for different centerline velocities of the MLAF unit
| off | 180.78 (157–210) | 225.80 (155–312) | 51.06 (32–63) | 382.85 (289–401) |
| 0.2 | 43.94 (34–55) | 96.44 (83–121) | 27.86 (23–35) | 380.36 (254–421) |
| 0.4 | 14.02 (11–20) | 37.42 (32–65) | 19.92 (14–29) | 393.69 (298–501) |
| 0.6 | 15.84 (8–19) | 29.54 (21–52) | 18.80 (15–24) | 390.50 (301–423) |
| 0.8 | 14.70 (9–14) | 22.72 (21–40) | 17.44 (13–22) | 384.85 (319–419) |
| 1.0 | 14.60 (8–14) | 17.32 (12–38) | 14.46 (14–21) | 386.07 (329–438) |
CFD simulation results were based on the passive air-sampling method. (CFU: colony-forming unit, MLAF: mobile laminar airflow).
Figure 3MLAF impact area as a function of screen-unit velocity and distance from the MLAF screen center.