Miranda Suchomel1, Magda Diab-Elschahawi, Michael Kundi, Ojan Assadian.
Abstract
BACKGROUND: Non-touch fittings have been reported to be susceptible for Pseudomonas aeruginosa accumulation. A number of factors may contribute to this, including the frequency of usage, duration of water stagnation, or presence of plastic materials. Programmable non-touch fittings are appearing which allow regular automated post-flushing with cold water to prevent water stagnation. However, the ideal duration of post-flushing is unknown as well as the effect of pre-rinsing with cold water before use.Entities:
Mesh:
Year: 2013 PMID: 24000790 PMCID: PMC3846848 DOI: 10.1186/1471-2334-13-402
Source DB: PubMed Journal: BMC Infect Dis ISSN: 1471-2334 Impact factor: 3.090
Figure 1Laboratory set-up of non-touch sensor fittings on a mobile water sink.
Details of tested variation in presence or absence of connection water pipe, frequency of use, and time interval of pre- and post-usage water flush
| | ||||
|---|---|---|---|---|
| 1 | 50 cm | once weekly | none | none |
| 2 | 50 cm | once monthly | none | none |
| 3 | 50 cm | 10× daily | none | none |
| 4 | 300 cm | 10× daily | none | none |
| 5 | 50 cm | 10× daily | none | 2 s |
| 6 | 50 cm | 10× daily | none | 10 s |
| 7 | none | 10× daily | none | none |
| 8 | 50 cm | none | 30 s | none |
a usage: 30 seconds at a pre-set water temperature of 37°C.
b cold water at a pre-set water temperature of 18°C.
Number of cfu/mL retrieved from fittings no. 1-8
| 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 1 | 0 | - | 0 | 0 | 0 | 0 | 0 | - |
| 2 | > 1,000 | - | 0 | 2 | 67 | 15 | 0 | - |
| 3 | > 1,000 | - | 0 | 0 | 0 | 0 | 124 | - |
| 4 | > 1,000 | > 1,000 | 0 | 0 | 0 | 0 | 0 | 0 |
| 5 | > 1,000 | - | 150 | >1,000 | 46 | 0 | 100 | - |
| 6 | > 1,000 | - | 62 | 400 | 123 | 14 | 300 | - |
| 7 | > 1,000 | - | 1 | 1 | 10 | 1 | 10 | - |
| 8 | > 1,000 | > 1,000 | 162 | 200 | 152 | 22 | 500 | - |
| 9 | > 1,000 | - | 69 | 226 | 30 | 0 | 167 | 4 |
| 10 | > 1,000 | - | 4 | 17 | 1 | 1 | 170 | 0 |
| 11 | > 1,000 | - | 317 | 67 | 147 | 6 | 286 | 5 |
| 12 | > 1,000 | > 1,000 | 17 | 21 | 14 | 0 | 252 | 0 |
| 13 | > 1,000 | - | 89 | 139 | 30 | 0 | 192 | 1 |
| 14 | > 1,000 | - | 87 | 46 | 402 | 1 | 90 | 0 |
| 15 | > 1,000 | - | 95 | 15 | 10 | 16 | 226 | 0 |
| 16 | > 1,000 | > 1,000 | 20 | 1 | 1 | 1 | 55 | 1 |
| 17 | > 1,000 | - | 200 | 259 | 321 | 11 | 500 | 3 |
| 18 | > 1,000 | - | 180 | 117 | 237 | 26 | 118 | 2 |
| 19 | > 1,000 | - | 290 | 109 | 150 | 40 | 250 | 0 |
| 20 | > 1,000 | - | 17 | 0 | 0 | 0 | 0 | - |
| Geometric mean | - | - | 17.8 | 15.4 | 14.2 | 2.2 | 39.7 | 1.0 |
| Scatter factor | - | - | 11.9 | 14.6 | 12.2 | 5.4 | 14.0 | 2.4 |
Tukey HSD-test of log10 cfu between fittings no. 3-7
| 3 | | 1.0000 | 0.9997 | 0.0006 | 0.1900 |
| 4 | 1.0000 | | 0.9995 | 0.0006 | 0.1988 |
| 5 | 0.9997 | 0.9995 | | 0.0011 | 0.1271 |
| 6 | 0.0006 | 0.0006 | 0.0011 | | 0.0001 |
| 7 | 0.1900 | 0.1988 | 0.1271 | 0.0001 |