Sick building syndrome in relation to air exchange rate, CO(2), room temperature and relative air humidity in university computer classrooms: an experimental study.

Dan Norbäck1, Klas Nordström.   

Abstract

OBJECTIVE: To study the effects of ventilation and temperature changes in computer classrooms on symptoms in students.
METHODS: Technical university students participated in a blinded study. Two classrooms had higher air exchange (4.1-5.2 ac/h); two others had lower (2.3-2.6 ac/h) air exchange. After 1 week, ventilation conditions were interchanged between the rooms. The students reported symptoms during the last hour, on a seven-step rating scale. Room temperature, relative air humidity (RH) carbon dioxide (CO(2)), PM10 and ultra-fine particles (UFP) were measured simultaneously (1 h). Illumination, air velocity, operative temperature, supply air temperature, formaldehyde, NO(2) and O(3) were measured. Multiple logistic regression was applied in cross-sectional analysis of the first answer (N = 355). Those participating twice (N = 121) were analysed longitudinally.
RESULTS: Totally 31% were females, 2.9% smokers and 3.8% had asthma. Mean CO(2) was 993 ppm (674-1,450 ppm), temperature 22.7 degrees C (20-25 degrees C) and RH 24% (19-35%). Lower and higher air exchange rates corresponded to a personal outdoor airflow of 7 l/s*p and 10-13 L/s*P, respectively. Mean PM10 was 20 microg/m(3) at lower and 15 microg/m(3) at higher ventilation flow. Ocular, nasal and throat symptoms, breathlessness, headache and tiredness were significantly more common at higher CO(2) and temperature. After mutual adjustment, ocular (OR = 1.52 per 1 degrees C), nasal (OR = 1.62 per 1 degrees C) and throat symptoms (OR = 1.53 per 1 degrees C), headache (OR = 1.51 per 1 degrees C) and tiredness (OR = 1.54 per 1 degrees C) were significantly associated with temperature; headache was associated only with CO(2) (OR = 1.19 per 100 ppm CO(2)). Longitudinal analysis demonstrated that increased room temperature was related to tiredness (P < 0.05).
CONCLUSION: Computer classrooms may have CO(2) above 1,000 ppm and temperatures above 22 degrees C. Increased temperature and CO(2) may affect mucosal membrane symptoms, headaches and tiredness. Room temperature was most important. CO(2) associations may partly be temperature effects.

Entities:  

Mesh:

Substances:

Year:  2008        PMID: 18246367     DOI: 10.1007/s00420-008-0301-9

Source DB:  PubMed          Journal:  Int Arch Occup Environ Health        ISSN: 0340-0131            Impact factor:   3.015


  20 in total

1.  New ventilation systems at select schools in Sweden--effects on asthma and exposure.

Authors:  G Smedje; D Norbäck
Journal:  Arch Environ Health       Date:  2000 Jan-Feb

2.  Air quality and well-being perception in subjects attending university libraries in Modena (Italy).

Authors:  E Righi; G Aggazzotti; G Fantuzzi; V Ciccarese; G Predieri
Journal:  Sci Total Environ       Date:  2002-03-08       Impact factor: 7.963

3.  Perception of cockpit environment among pilots on commercial aircraft.

Authors:  Torsten Lindgren; Kjell Andersson; Dan Norbäck
Journal:  Aviat Space Environ Med       Date:  2006-08

4.  Changes in ocular and nasal signs and symptoms among air crew in relation to air humidification on intercontinental flights.

Authors:  Dan Norbäck; Torsten Lindgren; Gunilla Wieslander
Journal:  Scand J Work Environ Health       Date:  2006-04       Impact factor: 5.024

5.  Adaptation of office workers to a new building - impaired well-being as part of the sick-building-syndrome.

Authors:  Ralf Neuner; Hans-Joachim Seidel
Journal:  Int J Hyg Environ Health       Date:  2006-05-12       Impact factor: 5.840

Review 6.  The sick-building syndrome.

Authors:  M Hodgson
Journal:  Occup Med       Date:  1995 Jan-Mar

Review 7.  Epidemiology of the sick building syndrome.

Authors:  A Apter; A Bracker; M Hodgson; J Sidman; W Y Leung
Journal:  J Allergy Clin Immunol       Date:  1994-08       Impact factor: 10.793

8.  Effect of air humidification on the sick building syndrome and perceived indoor air quality in hospitals: a four month longitudinal study.

Authors:  K Nordström; D Norbäck; R Akselsson
Journal:  Occup Environ Med       Date:  1994-10       Impact factor: 4.402

9.  Indoor air quality, ventilation and health symptoms in schools: an analysis of existing information.

Authors:  J M Daisey; W J Angell; M G Apte
Journal:  Indoor Air       Date:  2003-03       Impact factor: 5.770

10.  Why do women report 'sick building symptoms' more often than men?

Authors:  B Stenberg; S Wall
Journal:  Soc Sci Med       Date:  1995-02       Impact factor: 4.634

View more
  12 in total

1.  Carbon dioxide (CO2) demand-controlled ventilation in university computer classrooms and possible effects on headache, fatigue and perceived indoor environment: an intervention study.

Authors:  Dan Norbäck; Klas Nordström; Zhuohui Zhao
Journal:  Int Arch Occup Environ Health       Date:  2012-03-16       Impact factor: 3.015

2.  Assessing associations between indoor environment and health symptoms in Romanian school children: an analysis of data from the SINPHONIE project.

Authors:  Jillian R Palumbo; Shao Lin; Ziqiang Lin; Iulia A Neamtiu; Wangjian Zhang; Eva Csobod; Eugen S Gurzau
Journal:  Environ Sci Pollut Res Int       Date:  2018-02-22       Impact factor: 4.223

3.  The effects of building-related factors on classroom relative humidity among North Carolina schools participating in the 'Free to Breathe, Free to Teach' study.

Authors:  K A Angelon-Gaetz; D B Richardson; D M Lipton; S W Marshall; B Lamb; T LoFrese
Journal:  Indoor Air       Date:  2015-01-03       Impact factor: 5.770

4.  Relationship between sick building syndrome and indoor environmental factors in newly built Japanese dwellings.

Authors:  Makoto Takeda; Yasuaki Saijo; Motoyuki Yuasa; Ayako Kanazawa; Atsuko Araki; Reiko Kishi
Journal:  Int Arch Occup Environ Health       Date:  2009-02-10       Impact factor: 3.015

5.  Headache symptoms and indoor environmental parameters: Results from the EPA BASE study.

Authors:  Gretchen E Tietjen; Jagdish Khubchandani; Somik Ghosh; Suchismita Bhattacharjee; Joann Kleinfelder
Journal:  Ann Indian Acad Neurol       Date:  2012-08       Impact factor: 1.383

6.  Allostatic load model associated with indoor environmental quality and sick building syndrome among office workers.

Authors:  Chien-Cheng Jung; Hsiu-Hao Liang; Hui-Ling Lee; Nai-Yun Hsu; Huey-Jen Su
Journal:  PLoS One       Date:  2014-04-23       Impact factor: 3.240

7.  Personal, Psychosocial and Environmental Factors Related to Sick Building Syndrome in Official Employees of Taiwan.

Authors:  Chung-Yen Lu; Meng-Chuan Tsai; Chih-Hsin Muo; Yu-Hsien Kuo; Fung-Chang Sung; Chin-Ching Wu
Journal:  Int J Environ Res Public Health       Date:  2017-12-22       Impact factor: 3.390

8.  Evaluating prevalence and risk factors of building-related symptoms among office workers: Seasonal characteristics of symptoms and psychosocial and physical environmental factors.

Authors:  Kenichi Azuma; Koichi Ikeda; Naoki Kagi; U Yanagi; Haruki Osawa
Journal:  Environ Health Prev Med       Date:  2017-04-12       Impact factor: 3.674

9.  Epidemiological association between multiple chemical sensitivity and birth by caesarean section: a nationwide case-control study.

Authors:  Kentaro Watai; Yuma Fukutomi; Hiroaki Hayashi; Yosuke Kamide; Kiyoshi Sekiya; Masami Taniguchi
Journal:  Environ Health       Date:  2018-12-14       Impact factor: 5.984

10.  Characterization of Indoor Air Quality on a College Campus: A Pilot Study.

Authors:  Grant Erlandson; Sheryl Magzamen; Ellison Carter; Julia L Sharp; Stephen J Reynolds; Joshua W Schaeffer
Journal:  Int J Environ Res Public Health       Date:  2019-07-30       Impact factor: 3.390

View more

北京卡尤迪生物科技股份有限公司 © 2022-2023.