A 17-month evaluation of a chlorine dioxide water treatment system to control Legionella species in a hospital water supply.

Arjun Srinivasan1, Gregory Bova, Tracy Ross, Karen Mackie, Nicholas Paquette, William Merz, Trish M Perl.   

Abstract

OBJECTIVE: To assess the safety and efficacy of a chlorine dioxide water treatment system in controlling Legionella in a hospital water supply.
DESIGN: For 17 months following installation of the system, we performed regular water cultures throughout the building, assessed chlorine dioxide and chlorite levels, and monitored metal corrosion.
RESULTS: Sites that grew Legionella species decreased from 41% at baseline to 4% (P = .001). L. anisa was the only species recovered and it was found in samples of both hot and cold water. Levels of chlorine dioxide and chlorite were below Environmental Protection Agency (EPA) limits for these chemicals in potable water. Further, enhanced carbon filtration effectively removed the chemicals, even at chlorine dioxide levels of more than twice what was used to treat the water. After 9 months, corrosion of copper test strips exposed to the chlorine dioxide was not higher than that of control strips. During the evaluation period, there were no cases of nosocomial Legionella in the building with the system, whereas there was one case in another building.
CONCLUSIONS: Our results indicate that operation of a chlorine dioxide system effectively removed Legionella species from a hospital water supply. Furthermore, we found that the system was safe, as levels of chlorine dioxide and chlorite were below EPA limits. The system did not appear to cause increased corrosion of copper pipes. Our results indicate that chlorine dioxide may hold promise as a solution to the problem of Legionella contamination of hospital water supplies.

Entities:  

Mesh:

Substances:

Year:  2003        PMID: 12940577     DOI: 10.1086/502254

Source DB:  PubMed          Journal:  Infect Control Hosp Epidemiol        ISSN: 0899-823X            Impact factor:   3.254


  2 in total

1.  Control of Legionella Contamination and Risk of Corrosion in Hospital Water Networks following Various Disinfection Procedures.

Authors:  Isabella Marchesi; Greta Ferranti; Antonella Mansi; Anna M Marcelloni; Anna R Proietto; Navneet Saini; Paola Borella; Annalisa Bargellini
Journal:  Appl Environ Microbiol       Date:  2016-05-02       Impact factor: 4.792

2.  Legionnaires' disease case-finding algorithm, attack rates, and risk factors during a residential outbreak among older adults: an environmental and cohort study.

Authors:  Benjamin J Silk; Jennifer L Foltz; Kompan Ngamsnga; Ellen Brown; Mary Grace Muñoz; Lee M Hampton; Kara Jacobs-Slifka; Natalia A Kozak; J Michael Underwood; John Krick; Tatiana Travis; Olivia Farrow; Barry S Fields; David Blythe; Lauri A Hicks
Journal:  BMC Infect Dis       Date:  2013-06-27       Impact factor: 3.090

  2 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.