Literature DB >> 10342703

A community outbreak of Legionnaires' disease linked to hospital cooling towers: an epidemiological method to calculate dose of exposure.

C M Brown1, P J Nuorti, R F Breiman, A L Hathcock, B S Fields, H B Lipman, G C Llewellyn, J Hofmann, M Cetron.   

Abstract

BACKGROUND: From July to September 1994, 29 cases of community-acquired Legionnaires' disease (LD) were reported in Delaware. The authors conducted an investigation to a) identify the source of the outbreak and risk factors for developing Legionella pneumophila serogroup 1 (Lp-1) pneumonia and b) evaluate the risk associated with the components of cumulative exposure to the source (i.e. distance from the source, frequency of exposure, and duration of exposure).
METHODS: A case-control study matched 21 patients to three controls per case by known risk factors for acquiring LD. Controls were selected from patients who attended the same clinic as the respective case-patients. Water samples taken at the hospital, from eight nearby cooling towers, and from four of the patient's homes were cultured for Legionella. Isolates were subtyped using monoclonal antibody (Mab) analysis and arbitrarily primed polymerase chain reaction (AP-PCR).
RESULTS: Eleven (52%) of 21 case-patients worked at or visited the hospital compared with 17 (27%) of 63 controls (OR 5.0, 95% CI : 1.1-29). For those who lived, worked, or visited within 4 square miles of the hospital, the risk of illness decreased by 20% for each 0.10 mile from the hospital; it increased by 80% for each visit to the hospital; and it increased by 8% for each hour spent within 0.125 miles of the hospital. Lp-1 was isolated from three patients and both hospital cooling towers. Based on laboratory results no other samples contained Lp-1. The clinical and main-tower isolates all demonstrated Mab pattern 1,2,5,6. AP-PCR matched the main-tower samples with those from two case-patients.
CONCLUSION: The results of our investigation suggested that the hospital cooling towers were the source of a community outbreak of LD. Increasing proximity to and frequency of exposure to the towers increased the risk of LD. New guidelines for cooling tower maintenance are needed. Knowing the location of cooling towers could facilitate maintenance inspections and outbreak investigations.

Entities:  

Mesh:

Substances:

Year:  1999        PMID: 10342703     DOI: 10.1093/ije/28.2.353

Source DB:  PubMed          Journal:  Int J Epidemiol        ISSN: 0300-5771            Impact factor:   7.196


  20 in total

1.  Community acquired legionnaires' disease: lessons for surveillance from recent outbreaks.

Authors:  M Regan; B Olowokure
Journal:  J Epidemiol Community Health       Date:  2006-06       Impact factor: 3.710

2.  Legionella pneumophila in cooling towers: fluctuations in counts, determination of genetic variability by pulsed-field gel electrophoresis (PFGE), and persistence of PFGE patterns.

Authors:  Sonia Ragull; Marian Garcia-Nuñez; Maria Luisa Pedro-Botet; Nieves Sopena; Maria Esteve; Rafael Montenegro; Miquel Sabrià
Journal:  Appl Environ Microbiol       Date:  2007-06-29       Impact factor: 4.792

3.  A large Legionnaires' disease outbreak in Pamplona, Spain: early detection, rapid control and no case fatality.

Authors:  J Castilla; A Barricarte; J Aldaz; M García Cenoz; T Ferrer; C Pelaz; S Pineda; B Baladrón; I Martín; B Goñi; P Aratajo; J Chamorro; F Lameiro; L Torroba; I Dorronsoro; V Martínez-Artola; M J Esparza; M A Gastaminza; P Fraile; P Aldaz
Journal:  Epidemiol Infect       Date:  2007-07-30       Impact factor: 2.451

4.  A community outbreak of Legionnaires' disease associated with a cooling tower in Vic and Gurb, Catalonia (Spain) in 2005.

Authors:  M R Sala Ferré; C Arias; J M Oliva; A Pedrol; M García; T Pellicer; P Roura; A Domínguez
Journal:  Eur J Clin Microbiol Infect Dis       Date:  2008-08-28       Impact factor: 3.267

Review 5.  A review of back-calculation techniques and their potential to inform mitigation strategies with application to non-transmissible acute infectious diseases.

Authors:  Joseph R Egan; Ian M Hall
Journal:  J R Soc Interface       Date:  2015-05-06       Impact factor: 4.118

Review 6.  Multi-Scale Airborne Infectious Disease Transmission.

Authors:  Charles F Dillon; Michael B Dillon
Journal:  Appl Environ Microbiol       Date:  2020-12-04       Impact factor: 4.792

Review 7.  Electrochemically activated solutions: evidence for antimicrobial efficacy and applications in healthcare environments.

Authors:  R M S Thorn; S W H Lee; G M Robinson; J Greenman; D M Reynolds
Journal:  Eur J Clin Microbiol Infect Dis       Date:  2011-08-02       Impact factor: 3.267

8.  Legionellosis and Recent Advances in Technologies for Legionella Control in Premise Plumbing Systems: A Review.

Authors:  Kelsie M Carlson; Laura A Boczek; Soryong Chae; Hodon Ryu
Journal:  Water (Basel)       Date:  2020-03-02       Impact factor: 3.103

9.  Legionella longbeachae detected in an industrial cooling tower linked to a legionellosis outbreak, New Zealand, 2015; possible waterborne transmission?

Authors:  C N Thornley; D J Harte; R P Weir; L J Allen; K J Knightbridge; P R T Wood
Journal:  Epidemiol Infect       Date:  2017-06-19       Impact factor: 4.434

10.  Meteorological conditions and incidence of Legionnaires' disease in Glasgow, Scotland: application of statistical modelling.

Authors:  C E Dunn; B Rowlingson; R S Bhopal; P Diggle
Journal:  Epidemiol Infect       Date:  2012-06-12       Impact factor: 4.434

View more

北京卡尤迪生物科技股份有限公司 © 2022-2023.