Literature DB >> 9503106

Nosocomial legionnaires' disease discovered in community hospitals following cultures of the water system: seek and ye shall find.

A M Goetz1, J E Stout, S L Jacobs, M A Fisher, R E Ponzer, S Drenning, V L Yu.   

Abstract

BACKGROUND: The reservoir for hospital-acquired legionnaires' disease is the water distribution system. The Allegheny County (Pa.) Health Department recommended environmental cultures for all health care facilities for the prevention of hospital-acquired Legionella infection including facilities with no known cases of legionnaires' disease.
METHODS: Environmental cultures of hot water tanks, faucets, and showerheads were performed in six health care facilities according to health department guidelines. If hot water tanks, faucets, or showerheads yielded Legionella, monitoring with Legionella culture and urinary antigen was performed for all cases of nosocomial pneumonia.
RESULTS: Legionella was isolated from the water distribution system in 83% (five of six) of facilities. Three facilities dropped out of the study; two decided to disinfect the water and one had no Legionella in the water system. The other three facilities all discovered cases of legionnaires' disease during the 1-year study period after introduction of Legionella testing. L. pneumophilia, serogroups 1, 3, and 5, caused 12 cases of hospital-acquired legionnaires' disease. Positive diagnostic tests included: 10 of 12 (83%) urinary antigen, 6 of 8 (75%) respiratory cultures, and 2 of 5 (40%) serology. Molecular typing confirmed that the source of infection was the water supply in two hospitals.
CONCLUSION: Routine environmental cultures for Legionella in the water distribution system are recommended even if the hospital had not previously recognized cases of hospital acquired legionnaires' disease. The Allegheny County Health Department guidelines were inexpensive to implement and resulted in the discovery of cases that would have otherwise been undiagnosed.

Entities:  

Mesh:

Year:  1998        PMID: 9503106     DOI: 10.1016/s0196-6553(98)70054-9

Source DB:  PubMed          Journal:  Am J Infect Control        ISSN: 0196-6553            Impact factor:   2.918


  10 in total

1.  Coping with Legionella.

Authors:  E Weir
Journal:  CMAJ       Date:  2000-11-14       Impact factor: 8.262

2.  Legionella.

Authors: 
Journal:  Curr Infect Dis Rep       Date:  1999-04       Impact factor: 3.725

Review 3.  Microorganisms resistant to free-living amoebae.

Authors:  Gilbert Greub; Didier Raoult
Journal:  Clin Microbiol Rev       Date:  2004-04       Impact factor: 26.132

4.  Outbreak Column 16: Cognitive errors in outbreak decision making.

Authors:  Evonne T Curran
Journal:  J Infect Prev       Date:  2015-01-05

Review 5.  Emerging waterborne infections in health-care settings.

Authors:  A M Emmerson
Journal:  Emerg Infect Dis       Date:  2001 Mar-Apr       Impact factor: 6.883

6.  Association between contaminated faucets and colonization or infection by nonfermenting gram-negative bacteria in intensive care units in Taiwan.

Authors:  Jiun-Ling Wang; Mei-Ling Chen; Yusen Eason Lin; Shan-Chwen Chang; Yee-Chun Chen
Journal:  J Clin Microbiol       Date:  2009-07-08       Impact factor: 5.948

7.  A case of legionella pneumonia caused by home use of continuous positive airway pressure.

Authors:  Ruby Schnirman; Nasifa Nur; Alice Bonitati; Gerardo Carino
Journal:  SAGE Open Med Case Rep       Date:  2017-12-05

Review 8.  Nosocomial pneumonia : rationalizing the approach to empirical therapy.

Authors:  Gunnar I Andriesse; Jan Verhoef
Journal:  Treat Respir Med       Date:  2006

9.  Healthcare-Associated Legionnaires' Disease, Europe, 2008-2017.

Authors:  Julien Beauté; Diamantis Plachouras; Sven Sandin; Johan Giesecke; Pär Sparén
Journal:  Emerg Infect Dis       Date:  2020-10       Impact factor: 6.883

10.  Environmental surveillance of Legionella pneumophila in distal water supplies of a hospital for early identification & prevention of hospital-acquired legionellosis.

Authors:  Shihail Jinna; Ujjwala Nitin Gaikwad
Journal:  Indian J Med Res       Date:  2018-06       Impact factor: 2.375

  10 in total