Literature DB >> 9309436

Nosocomial legionellosis traced to a contaminated ice machine.

P S Graman1, G A Quinlan, J A Rank.   

Abstract

OBJECTIVE: To investigate a case of nosocomial legionellosis, identify pathways of transmission, and effect control of the environmental source.
DESIGN: Case investigation and environmental culture surveillance.
SETTING: A 720-bed university teaching hospital. CASE PATIENT: A ventilator-dependent 66-year-old male developed nosocomial pneumonia due to Legionella pneumophila serogroup 6 after 3 months in an intensive-care unit (ICU). The patient had no intake of potable water except for ice chips from an ice machine in the ICU.
RESULTS: Cultures revealed L pneumophila serogroup 6 in the ice (4.3 colony-forming units/mL) and ice machine cold water (too numerous to count). Cultures from adjacent hot and cold taps, plus taps located near the patient, all were negative; ice machines and cold water on seven other patient units also were negative. Only sterile water had been used for tube feedings, mouth care, suctioning, and ventilator humidification. Hospital hot water previously had been colonized with L pneumophila serogroup 6, but all surveillance water cultures had been negative since chlorination of the hot-water system began the previous year; cold-water cultures had never before grown Legionella. The ice machine was disinfected with a 2-hour flush of 2.625% sodium hypochlorite. The supply line to the ice machine was replaced, and the cold-water pipe from the floor below was treated with 83 ppm sodium hypochlorite for 48 hours. All follow-up surveillance cultures of the ice machine remained negative through mid-1996. No additional cases of nosocomial legionellosis occurred.
CONCLUSIONS: Ice machines may be reservoirs of L pneumophila in hospitals. Both ice and water dispensed from these machines may be contaminated, and nosocomial transmission may occur. Successful long-term decontamination and control can be accomplished with shock chlorination.

Entities:  

Mesh:

Substances:

Year:  1997        PMID: 9309436     DOI: 10.1086/647689

Source DB:  PubMed          Journal:  Infect Control Hosp Epidemiol        ISSN: 0899-823X            Impact factor:   3.254


  8 in total

1.  Legionella confirmation using real-time PCR and SYTO9 is an alternative to current methodology.

Authors:  Steven Giglio; Paul T Monis; Christopher P Saint
Journal:  Appl Environ Microbiol       Date:  2005-12       Impact factor: 4.792

Review 2.  Current and emerging Legionella diagnostics for laboratory and outbreak investigations.

Authors:  Jeffrey W Mercante; Jonas M Winchell
Journal:  Clin Microbiol Rev       Date:  2015-01       Impact factor: 26.132

3.  A cluster of cases of nosocomial legionnaires disease linked to a contaminated hospital decorative water fountain.

Authors:  Tara N Palmore; Frida Stock; Margaret White; MaryAnn Bordner; Angela Michelin; John E Bennett; Patrick R Murray; David K Henderson
Journal:  Infect Control Hosp Epidemiol       Date:  2009-08       Impact factor: 3.254

Review 4.  Plumbing of hospital premises is a reservoir for opportunistically pathogenic microorganisms: a review.

Authors:  Margaret M Williams; Catherine R Armbruster; Matthew J Arduino
Journal:  Biofouling       Date:  2013       Impact factor: 3.797

5.  Preventing Healthcare-Associated Legionellosis: Results after 3 Years of Continuous Disinfection of Hot Water with Monochloramine and an Effective Water Safety Plan.

Authors:  Maria Anna Coniglio; Margherita Ferrante; Mohamed H Yassin
Journal:  Int J Environ Res Public Health       Date:  2018-07-27       Impact factor: 3.390

6.  Contamination of Hospital Water Supplies in Gilan, Iran, with Legionella pneumophila, Escherichia coli, and Pseudomonas aeruginosa.

Authors:  Masoumeh Ahmadi Jalali Moghadam; Hamidreza Honarmand; Sajad Asfaram Meshginshahr
Journal:  Interdiscip Perspect Infect Dis       Date:  2015-09-07

Review 7.  Uncertainties associated with assessing the public health risk from Legionella.

Authors:  Harriet Whiley; Alexandra Keegan; Howard Fallowfield; Kirstin Ross
Journal:  Front Microbiol       Date:  2014-09-24       Impact factor: 5.640

Review 8.  Considerations for large building water quality after extended stagnation.

Authors:  Caitlin R Proctor; William J Rhoads; Tim Keane; Maryam Salehi; Kerry Hamilton; Kelsey J Pieper; David M Cwiertny; Michele Prévost; Andrew J Whelton
Journal:  AWWA Water Sci       Date:  2020-08-06