Literature DB >> 9054302

Air movement around a worker in a low-speed flow field.

A E Johnson1, B Fletcher, C J Saunders.   

Abstract

A knowledge of the air movement around a worker in a low-speed airflow is important in a number of areas: containment testing of fume cupboards; testing of personal dust samplers; testing of LEV effectiveness; and measurement of worker exposure. Measurements of velocity vectors around the upper torsos of manikins and a human in low-speed airflows have been made using a laser Doppler anemometer. Both heated and unheated manikins, as well as a 'breathing' manikin were used. The results show that quite distinctive flow patterns develop with heated and unheated bodies. Comparison of the flows around two- and three-dimensional manikins with that around a human shows that only a three-dimensional heated manikin gives good results. The unheated breathing manikin gave results which were unrepresentative of the real situation. A suitable manikin for use in sampling or testing in low-speed airflows would have a heated, rounded, three-dimensional body of reasonably human dimensions and would be non-breathing and clothed.

Entities:  

Mesh:

Year:  1996        PMID: 9054302     DOI: 10.1016/0003-4878(95)00060-7

Source DB:  PubMed          Journal:  Ann Occup Hyg        ISSN: 0003-4878


  2 in total

1.  Numerical simulation and experimental validation of the ventilation system performance in a heated room.

Authors:  Sondes Ifa; Zied Driss
Journal:  Air Qual Atmos Health       Date:  2020-09-04       Impact factor: 3.763

2.  The investigation of the influence of thermal plume and breathing on sleeping microenvironment.

Authors:  Zhu Cheng; Nuoa Lei; Guangyu Cao; Baizhan Li
Journal:  J Environ Health Sci Eng       Date:  2021-05-26
  2 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.