M Koide1, A Saito, N Kusano, F Higa.
Abstract
The presence of Legionella spp. in cooling tower water was investigated by using the polymerase chain reaction. Total Legionella spp. detection was performed with 20-mer 5S rRNA complementary DNA sequence primers, and specific Legionella pneumophila detection was performed with 20-mer and then 21-mer macrophage infectivity potentiator gene sequence primers. Of 27 cooling tower water samples, 25 were positive for Legionella spp., and 14 of these contained L. pneumophila.Entities:
Mesh:
Substances:
Year: 1993 PMID: 8328811 PMCID: PMC182188 DOI: 10.1128/aem.59.6.1943-1946.1993
Source DB: PubMed Journal: Appl Environ Microbiol ISSN: 0099-2240 Impact factor: 4.792