Epidemic Legionnaires' disease. Airborne transmission down a chimney.

J D Band, M LaVenture, J P Davis, G F Mallison, P Skaliy, P S Hayes, W L Schell, H Weiss, D J Greenberg, D W Fraser.   

Abstract

Between June 18 and July 9, 1979, Legionnaires' disease (LD) developed in 13 persons who had visited a hotel complex in Wisconsin. All had visited the part of the hotel that contains the restaurants and meeting rooms (building A). Legionnaires' disease occurred in 1% who had been exclusively in the meeting rooms and in 0.1% who had eaten only at the hotel restaurants. Furthermore, 1.5% exposed to meeting room 1 and none of those exposed only to the other meeting rooms had LD. Legionella pneumophila was isolated from water in the cooling tower on top of building A. Located within 5 m downwind of the cooling-tower exhaust, a chimney with an open damper allowed cooling-tower exhaust (as demonstrated by air tracer studies) to enter meeting room 1 via the fireplace. Although cases did not occur after the cooling-tower water was treated by continuous hyperchlorination and the chimney was sealed, a seven-day lag occurred between treatment and elimination of the organism from the tower water.

Entities:  

Mesh:

Year:  1981        PMID: 7230470

Source DB:  PubMed          Journal:  JAMA        ISSN: 0098-7484            Impact factor:   56.272


  13 in total

Review 1.  Current and emerging Legionella diagnostics for laboratory and outbreak investigations.

Authors:  Jeffrey W Mercante; Jonas M Winchell
Journal:  Clin Microbiol Rev       Date:  2015-01       Impact factor: 26.132

2.  An alkaline approach to treating cooling towers for control of Legionella pneumophila.

Authors:  S J States; L F Conley; S G Towner; R S Wolford; T E Stephenson; A M McNamara; R M Wadowsky; R B Yee
Journal:  Appl Environ Microbiol       Date:  1987-08       Impact factor: 4.792

3.  Minimising the risk of Legionnaires' disease.

Authors:  R Finch
Journal:  Br Med J (Clin Res Ed)       Date:  1988-05-14

4.  Failure of Legionella pneumophila sensitivities to predict culture results from disinfectant-treated air-conditioning cooling towers.

Authors:  A C England; D W Fraser; G F Mallison; D C Mackel; P Skaliy; G W Gorman
Journal:  Appl Environ Microbiol       Date:  1982-01       Impact factor: 4.792

5.  Legionella pneumophila in cooling water systems. Report of a survey of cooling towers in London and a pilot trial of selected biocides.

Authors:  J B Kurtz; C L Bartlett; U A Newton; R A White; N L Jones
Journal:  J Hyg (Lond)       Date:  1982-06

6.  Solar and Climate Effects Explain the Wide Variation in Legionellosis Incidence Rates in the United States.

Authors:  Xiang Y Han
Journal:  Appl Environ Microbiol       Date:  2019-10-30       Impact factor: 4.792

7.  Survival of virulent Legionella pneumophila in aerosols.

Authors:  P Hambleton; M G Broster; P J Dennis; R Henstridge; R Fitzgeorge; J W Conlan
Journal:  J Hyg (Lond)       Date:  1983-06

8.  Ecology of Legionella: From Data to Knowledge with a Little Wisdom

Authors: 
Journal:  Microb Ecol       Date:  1996-07       Impact factor: 4.552

9.  Legionella oakridgensis: unusual new species isolated from cooling tower water.

Authors:  L H Orrison; W B Cherry; R L Tyndall; C B Fliermans; S B Gough; M A Lambert; L K McDougal; W F Bibb; D J Brenner
Journal:  Appl Environ Microbiol       Date:  1983-02       Impact factor: 4.792

10.  Outbreak of legionnaires' disease from a cooling water system in a power station.

Authors:  S Morton; C L Bartlett; L F Bibby; D N Hutchinson; J V Dyer; P J Dennis
Journal:  Br J Ind Med       Date:  1986-09
View more

北京卡尤迪生物科技股份有限公司 © 2022-2023.