| Literature DB >> 35991295 |
Ye Lu1, Ran Cai1, Zhongyi Xie1, Xiaodong Gao2, Xiaoqiang Huang3, Ji Xu1, Ye Li1, Guoqing Hu1.
Abstract
Background: Indoor air quality is controlled in the clean operating room (OR) to reduce the risk of surgical-site infections (SSIs). The aim of this study is to assess the usage and management of clean ORs in China and to identify factors associated with the risk of SSIs.Entities:
Mesh:
Year: 2022 PMID: 35991295 PMCID: PMC9391144 DOI: 10.1155/2022/8749785
Source DB: PubMed Journal: J Healthc Eng ISSN: 2040-2295 Impact factor: 3.822
Univariate analysis of factors influencing compliance with the GB 50333 standards.
| Influencing factors | Sample number | Noncompliance with the GB 50333 standards |
|
| ||
|---|---|---|---|---|---|---|
| Number, n | Rate, % | |||||
| Type of OR | Clean OR | 966 | 243 | 25.2 | 0.549 | 0.459 |
| Clean OR and general OR | 342 | 93 | 27.2 | |||
|
| ||||||
| Hospital level | Tertiary | 677 | 164 | 24.2 | 1.752 | 0.416 |
| Secondary | 594 | 163 | 27.4 | |||
| Lower than secondary | 37 | 9 | 24.3 | |||
|
| ||||||
| Number of beds | <500 | 453 | 111 | 24.5 | 2.574 | 0.276 |
| 500–1,000 | 498 | 122 | 24.5 | |||
| >1,000 | 357 | 103 | 28.9 | |||
|
| ||||||
| Number of ORs | <5 | 291 | 79 | 27.1 | 0.636 | 0.888 |
| 5–9 | 432 | 106 | 24.6 | |||
| 10–15 | 287 | 75 | 26.1 | |||
| >15 | 299 | 76 | 25.4 | |||
|
| ||||||
| Usage time (year) | ≤5 | 464 | 114 | 24.6 | 0.472 | 0.492 |
| >5 | 844 | 222 | 26.3 | |||
|
| ||||||
| Maintenance mode | Professional | 1,269 | 314 | 24.7 | 19.876 | <0.0001 |
| Outsource or no | 39 | 22 | 56.4 | |||
|
| ||||||
| Test frequency | More than once a year | 1,117 | 274 | 24.5 | 5.374 | 0.020 |
| Occasionally or no | 191 | 62 | 32.5 | |||
Significance at p < 0.05.
Multivariate analysis of factors influencing compliance with the GB 50333 standards.
| Influencing factors |
| Standard error | Wald statistic | Odds ratio | 95% CI |
|
|---|---|---|---|---|---|---|
| Type of OR | −0.033 | 0.151 | 0.047 | 0.968 | 0.719–1.302 | 0.829 |
| Hospital level | −0.348 | 0.154 | 5.084 | 0.706 | 0.522–0.955 | 0.024 |
| Number of beds | −0.363 | 0.136 | 7.118 | 0.696 | 0.533–0.908 | 0.008 |
| Number of ORs | 0.065 | 0.093 | 0.482 | 1.067 | 0.889–1.281 | 0.488 |
| Usage time (year) | −0.080 | 0.148 | 0.318 | 0.923 | 0.699–1.219 | 0.573 |
| Maintenance mode | −0.672 | 0.169 | 15.722 | 0.511 | 0.367–0.711 | <0.0001 |
| Test frequency | −0.152 | 0.087 | 3.028 | 0.859 | 0.724–1.019 | 0.082 |