Polymer-induced drag reduction (DR) in fluids was studied using a rotational rheometer with double-gap concentric cylinder geometry. Although both polymers (polyacrylamide (PAM) and 2-acrylamido-2-methylpropane sulfonic acid (SPAM)) had molecular weights of several MDa, the contrasting polymer charge, nonionic and anionic, led to different polymer overlap concentrations (c*), PAM ≫ SPAM, and fluid rheology, with PAM fluids mostly Newtonian and SPAM fluids non-Newtonian (shear-thinning). Based on these differences, it was important to account for the infinite shear viscosity and normalize the polymer concentration by the intrinsic concentration (c int) so that the DR performance of the two polymer fluids could be accurately compared. Both polymers induced DR, and the maximum DR by SPAM (DR% = 28) was slightly higher than that by PAM (DR% = 22) when Re p ∼ 1700. For PAM, the loss of DR with time diminished at higher polymer concentrations (≥100 ppm, at Re p = 3149) but was found to be sensitive to high Re p, with polymer chain scission the likely cause of the reduced performance. For the semi-dilute SPAM fluids, the shear stability contrasted that of PAM, showing negligible dependence on the polymer concentration and Re p. The apparent rapid loss of DR was predominantly attributed to a time-dependent effect and not polymer degradation. In pipe flow, the maximum DR for SPAM was higher than that measured by rheometry and was attributed to differences in the flow conditions. However, changes in the normalized DR/c with polymer concentration were found to be consistent between the two flow geometries. Furthermore, the high fluid stresses in pipe flow (at high Re p) led to drag reduction losses consistent with PAM, as the time-dependent effect was not seen.
Polymer-induced drag reduction (DR) in fluids was studied using a rotational rheometer with double-gap concentric cylinder geometry. Although both polymers (polyacrylamide (PAM) and 2-acrylamido-2-methylpropane sulfonic acid (SPAM)) had molecular weights of several MDa, the contrasting polymer charge, nonionic and anionic, led to different polymer overlap concentrations (c*), PAM ≫ SPAM, and fluid rheology, with PAM fluids mostly Newtonian and SPAM fluids non-Newtonian (shear-thinning). Based on these differences, it was important to account for the infinite shear viscosity and normalize the polymer concentration by the intrinsic concentration (c int) so that the DR performance of the two polymer fluids could be accurately compared. Both polymers induced DR, and the maximum DR by SPAM (DR% = 28) was slightly higher than that by PAM (DR% = 22) when Re p ∼ 1700. For PAM, the loss of DR with time diminished at higher polymer concentrations (≥100 ppm, at Re p = 3149) but was found to be sensitive to high Re p, with polymer chain scission the likely cause of the reduced performance. For the semi-dilute SPAM fluids, the shear stability contrasted that of PAM, showing negligible dependence on the polymer concentration and Re p. The apparent rapid loss of DR was predominantly attributed to a time-dependent effect and not polymer degradation. In pipe flow, the maximum DR for SPAM was higher than that measured by rheometry and was attributed to differences in the flow conditions. However, changes in the normalized DR/c with polymer concentration were found to be consistent between the two flow geometries. Furthermore, the high fluid stresses in pipe flow (at high Re p) led to drag reduction losses consistent with PAM, as the time-dependent effect was not seen.
With global energy demand continuing to
increase, significant effort
must be made to improve the efficiency of energy-intensive systems
and processes. In the pumping of fluids, frictional drag costs energy,
which can be reduced by adding very low concentrations of soluble
high-molecular-weight polymers to the fluid.[1−8] Polymer drag reduction (DR) has found application in fluid transport
in pipelines,[9] hydrofracking,[10,11] flows in heat exchangers,[12] fire-fighting
equipment[13] and medicine.[14] The Trans-Alaskan pipeline is one of the largest demonstrations
of polymer-induced drag reduction, with the pipeline pressure drop
reduced by 80% when adding low concentrations (∼100 ppm) of
a very high-molecular-weight polymer.[15]Since the early work of Toms,[16] significant
progress has been made in understanding the governing principles of
polymer drag reduction. It is now widely accepted that drag reduction
can be induced using polymers of sufficiently high molecular weight,
added at concentrations above a critical level, and when a minimum
level of turbulence intensity is achieved in the flow.[1,17,18] The two theories of polymer drag
reduction are: (i) viscous theory, which describes the effect of an
increased fluid viscosity near the pipe wall, increasing the buffer
layer thickness and suppressing turbulent fluctuations; and (ii) elastic
theory, which assumes a negligible increase in the effective viscosity.
The latter proposes that the buffer layer thickness increases when
the elastic energy stored by the polymer chains is similar to the
kinetic energy in the buffer layer at a given length scale greater
than the Kolmogorov scale, arguing that the so-called Kolmogorov energy
cascade is interrupted. As a result, eddy length scales below the
Kolmogorov scale start to behave elastically.[19,20]Pipe and duct flows have been used to study polymer drag reduction,
with changes in the pressure drop or velocity profile providing a
direct measure of performance.[19,21−23] However, such methods are often costly, time-consuming and require
large volumes of fluid; thus, the approach is not best-suited to rapidly
screen polymers. Rotational methods measure drag reduction by comparing
the torque difference between the polymeric solution and the solvent
at varying rotational velocities. One of the first reported studies
by Choi and Jhon,[24] used a rotating steel
disk in a cylindrical container to determine the drag reduction of
poly(ethylene oxide) (PEO) and polyisobutylene (PIB). A more commonly
used geometry is a concentric cylinder, where shear-driven Taylor–Couette
flow occurs at high rotational speeds.[25−27] With a high surface
area, the geometry enables detection of drag reduction at a lower
Reynolds number (Re), and with a precision that allows
small differences in performance to be meaningfully interpreted. For
high rotational velocities and small annular gap size, the boundary
layer at the wall can be sufficiently described by the Prandtl–von
Karman equation, similar to other canonical flows such as a wall-bounded
pressure-driven flow.[28,29] In such shear-driven rotational
flows, the polymer acts to modulate Taylor instabilities which are
a function of the rotational speed and fluid viscoelasticity.[30]Rajappan and McKinley[31] modified the
size of the rotor–stator of a TA Instruments AR-G2 rheometer
to increase the gap size, thus accessing a higher Re range to study the drag reduction performance of an extracted polysaccharide
in featureless turbulence. This is one of only a few studies that
compared performance in the regime of featureless turbulence, but
when combined with the rheometer, provides a level of sensitivity
often unattainable using bespoke instruments. However, most studies
only consider drag reduction in flow regimes in the absence of featureless
turbulence.The drag reduction performance of high-molecular-weight
polymers
such as water-soluble PEO, polyacrylamide (PAM), and xanthan gum have
been frequently studied using concentric cylinder geometries. Such
polymers are of interest because of their contrasting intrinsic properties,
for example, xanthan gum is a rigid polymer that exhibits type B drag
reduction, resulting in the early onset of drag reduction (so-called
retro-onset, at low turbulence), and the magnitude of drag reduction
is almost independent of Re. This contrasts type
A polymers where the drag reduction is a function of Re, as the polymer coils are stretched at higher turbulence intensity.[32] Generally, the shear stability increases in
the order PEO < PAM, with the better performance of PAM not fully
understood but likely attributed to the greater polymer rigidity and
its resistance to polymer chain scission.[33,34] Often, the loss of drag reduction can be attributed to polymer chain
scission, although de-aggregation of polymers has also been noted
to impart time-dependent effects.[35]In the current study, the drag reduction performance of dilute
polyacrylamide (PAM) and semi-dilute 2-acrylamido-2-methylpropane
sulfonic acid (SPAM) polymers have been assessed using rotational
rheometry. The rheometer method has frequently been used to determine
the drag-reducing properties of many polymers, yet the flow conditions
attained are often limiting when compared to pipe flow. The study
brings attention to the methods that should be used to correctly interpret
the drag reduction performance of high viscosity and semi-dilute polymer
samples and directly compares performance with that observed in pipe
flow. While trends of DR% with polymer concentration are consistent,
significant differences in DR stability were observed and could be
attributed to a time-dependency effect of the SPAM polymer that is
more apparent when the fluid stresses are lower.
Materials and Experimental Methods
The polyacrylamide
with ∼30% sulfonation (2-acrylamido-2-methylpropane
sulfonic acid, SPAM) and with a manufacturer-quoted molecular weight
between 5 and 8 × 106 Da was provided by SNF Floerger
(France). The nonionic polyacrylamide (PAM) with a quoted molecular
weight of 5 × 106 Da and potassium chloride (99.0%
pure, KCl) were supplied by Sigma-Aldrich, U.K. All chemicals were
used without further purification. The water used in the study was
deionized water (Milli-Q) with a resistivity of 18.2 MΩ cm at
25 °C.
Polymer Preparation
A polymer stock solution of 10,000
ppm was prepared by adding the required amount of dry polymer powder
into Milli-Q water (unadjusted pH) at room temperature. The polymer
was then dissolved by gently mixing the solution on a lab roller for
48 h, with complete dissolution visually assessed. The polymer solution
was stored at room temperature in a sealed glass vial, and the solution
was used within 30 days of its preparation. The sample was not observed
to degrade during this time. Prior to use, the concentrated polymer
solution was gently mixed overnight using a magnetic stirrer. Samples
were then removed from the glass vial and diluted with Milli-Q water
to the desired concentration for rheology assessment. For certain
tests, a monovalent electrolyte KCl was added following the dilution
step, and the polymer solutions were left to gently agitate for 2
h to ensure the samples were homogeneous prior to measurement.
Rheology
A DHR-II rheometer (TA Instruments, U.K.)
was used to measure the sample shear viscosity over a shear rate range
of 0.01–500 s–1. The geometry used was a
double-gap concentric cylinder, as shown in Figure , which has dimensions of L = 55 mm, r1 = 15.1 mm, r2 = 16 mm, r3 = 17.5 mm, and r4 = 18.5 mm. The instrument was first calibrated
following the standard protocol to determine the inertia of the rotor
and geometry and to ensure the geometry was lowered to a gap distance
of 2000 μm. The sample volume of 11 mL was gently transferred
to the cup using a wide bore pipette before lowering the geometry
to the standard gap. All measurements were conducted at 25 (±0.1)
°C, with the temperature maintained using a Peltier jacket. At
each desired shear rate, the fluid viscosity was measured after 5
s equilibration time and averaged over 30 s measurement time.
Figure 1
Schematic representation
of the double-gap coaxial cylinder used
to measure the rheology and drag reduction performance of the polymeric
fluids.
Schematic representation
of the double-gap coaxial cylinder used
to measure the rheology and drag reduction performance of the polymeric
fluids.
Fluid Drag Reduction
The DHR-II rheometer with the
double-gap geometry (Figure ) was used to measure the drag reduction performance of the
polymeric fluids relative to Milli-Q water. The same instrument calibration
procedure as described previously was followed, and all measurements
were conducted at 25 (±0.1) °C. The drag reduction performance
was studied to determine the magnitude of drag reduction, measured
from a flow sweep test, and the stability of drag reduction, measured
from a peak hold test. No pre-shear protocol was used. Once the sample
was added to the rheometer cup, the geometry was lowered to the gap
setting, the solvent trap was added, and the sample was left undistributed
for 2 min prior to measurement to ensure thermal equilibrium was attained.
For the flow sweep test, the rotational speed (ω) of the geometry
was increased from 3 to 200 rad/s using a logarithmic ramp collecting
100 data points over a test duration of 420 s. The relatively fast
flow sweep test was chosen to minimize possible sample degradation
during the shear ramp but was slightly compromised by the need to
have an equilibration time of 2 s to attain a steady state before
a measurement time of 2 s at every predetermined rotational speed.
For the peak hold test, the sample preparation and sample loading
followed the same standard protocol. However, no shear ramp was used,
and the polymer solution was almost instantaneously sheared at a range
of rotational speeds between 100 and 200 rad/s with the instrument
torque measured every 2 s for 1000 s to follow the transient behavior.
All experiments were completed in triplicate and were found to be
reproducible within ±2%.
Data Analysis
For rheometry, the torque (M, μN m) on the rotating double-gap coaxial cylinder is related
to the shear stress (τ, Pa) through the stress constant (kτ) of the geometry (, where cL is
the geometry aspect ratio) such thatAssuming a smooth surface, the shear
stress can be transformed into a Fanning friction factor by[27]where ρ is the fluid density (997 kg/m3), ω is the rotational velocity (rad/s), and , with r2 and r3 as previously defined. The Reynolds number
(Re) is used to represent the flow as a dimensionless
value and taken to be the ratio of inertial to viscous forces[27,28]where r̅ = ((r2 – r1) +
(r4 – r3))/2 and η (Pa s) is taken as the infinite shear viscosity
of the fluid. In the following text, Res and Rep describe the shear Reynolds
numbers of the solvent and polymer fluid, respectively. The fluid
drag reduction is calculated bywhere xwater and xpolymer solution are either the torque
at an equivalent rotational velocity or the Fanning friction factor
at an equivalent Re for the pure solvent (deionized
water) and polymer fluid, respectively.
Pipe Flow
A 51 L industrial size friction flow loop
(Charlton & Hill Welding LTD, Alberta, Canada) of 18 mm I.D. (stainless
steel pipe) was used to measure the polymer-induced drag reduction
at a constant flow rate of 80 L/min (Res ∼ 105,000) at 21± 2 °C, with the slight variation
in temperature due to no temperature control on the flow loop. All
polymer samples were prepared using the standard protocol as previously
described. Prior to each test, the pipe loop was flushed with excess
water (rinse cycles of 10 min after each run) to remove any residual
chemicals. In the current study, tests were run in order of increasing
additive concentration so as to minimize error from any residual drag-reducing
additive. To begin, the test fluid without polymer was circulated
around the flow loop for 30 s until the pressure drop for water reached
a steady baseline. Then, concentrated polymer solutions were injected
into the feed tank, with the flow rate kept constant to obtain the
desired concentrations for each experiment. The fluid was pumped using
a progressive cavity pump (TOSHIBA 0106SDSR41A-P), and the flow rate
was measured using a Coriolis flow meter. The pressure drop was measured
by differential pressure transducers (Stellartech.) separated at a
distance (L) of ∼7.3 m. The drag reduction
was calculated using eq , where x is ΔP. Flow loop
tests were run for 40 min at a constant flow rate to study the stability
of drag reduction. The data was then processed using the data acquisition
software (Siemens SIMATIC WinCC Comfort V14 SP1). All experiments
were completed in duplicate and were found to be reproducible within
∼4%.
Results and Discussion
In rotational shear-driven flows,
flow instabilities occur as a
function of increasing rotational speed. For the double-gap geometry,
the relative difference in radial velocity between r1 and r2, and r3 and r4 results in nonuniform
instabilities, with the outer gap experiencing instabilities at a
lower critical Re compared to the inner gap. The
flow instability is referred to by the Taylor number, which is calculated
from the ratio of centrifugal to viscous forces[27]where v is the kinematic
viscosity (m2/s).Figure a shows
typical apparent shear viscosity data of increasing rotational speed of
the geometry and the transition from the laminar (stable) flow regime.
The test fluid is Milli-Q water and at low shear rates (ω <
10 rad/s), the fluid is Newtonian, with a viscosity of 0.87 ×
10–3 (±0.01) Pa s. Beyond ω = 10 rad/s,
the apparent fluid viscosity increases, which signifies the onset
of secondary flow and Taylor instabilities. The Taylor number at the
transition is Ta ∼ 1900 and in reasonable
agreement with the value reported by Taylor[36] (for a classical bob and cup geometry with one annular gap), although
the number is slightly higher due to contributions from the inner
and outer gaps. The measured torque is also shown in Figure a and follows a second-order
polynomial regression response. The Milli-Q water data is used as
a baseline comparison to the polymer fluids.
Figure 2
(a) Real and apparent
viscosity of Milli-Q water as a function
of rotational speed (ω). The laminar flow regime is up to ω
∼ 10 rad/s. (b) Empirical data in panel (a) plotted using Prandtl–von
Karman coordinates on a semi-log scale. The solid line takes the form and the fitting parameters A and B are 15.014 and −12.38, respectively.
(a) Real and apparent
viscosity of Milli-Q water as a function
of rotational speed (ω). The laminar flow regime is up to ω
∼ 10 rad/s. (b) Empirical data in panel (a) plotted using Prandtl–von
Karman coordinates on a semi-log scale. The solid line takes the form and the fitting parameters A and B are 15.014 and −12.38, respectively.Figure b replots
the raw data in Prandtl–von Karman coordinates (semi-log plot),
where 1√f and Log Res√f use the Fanning friction factor,
as described in eq .
For rotational speeds up to 200 rad/s, the maximum attainable Res and Ta values were 3700
and 7.7 × 105, respectively. The transition to unstable
flow is easily identified (highlighted by the dashed line), and with
increasing Log Res√f, the flow regime transitions from wavy to modulated to
turbulent Taylor vortices.[28]Similar
to pipe flow, the rheometer data (Figure b) can be described by a least-squares linear
fit of the form given by eq (where A and B are geometry-dependent
variables) when Log Res√f ≥ 1.54 (Res ∼
380).Equation is known
as the Prandtl–von Karman law,[37] which describes fully developed turbulence in pipe flow. Its use
in the current study is more empirical to provide a method of comparison
for the different test fluids. The method provides reasonable data
fitting, although the region just after the transition to unstable
flow is less well-described by the fit.Converting the rheometer
data to Prandtl–von Karman coordinates
is readily achieved for Newtonian fluids; however, the assessment
of fluid viscosity is more complicated for non-Newtonian fluids, such
as those encountered in the current study; see Figure . The viscosity of the SPAM fluid strongly
depends on the shear rate, confirming its non-Newtonian behavior,
with the response dependent on the polymer concentration (Figure a) and electrolyte
concentration of the base fluid (Figure b). A greater degree of shear-thinning was
observed for higher polymer concentrations but lower electrolyte concentrations.
The effect of polymer concentration on the rheology of nonionic PAM
was less significant, with a Newtonian response up to 2500 ppm, and
a weakly shear-thinning response at 7500 ppm (Figure c). Such contrasting fluid behaviors result
from the different polymer conformations. With its strongly charged
backbone, SPAM adopts an extended rod-like conformation in water;
hence, the polymer chains overlap at much lower concentrations than
polymers that adopt a coiled conformation, such as the nonionic PAM.
Using the shear viscosity (Figure ), the polymer chain overlap concentration (c*) for the two polymers was approximated by calculating
the specific viscosity, ηsp. It should be noted that
the more accepted method of c* ≈ 1/[η]
(where [η] is the intrinsic viscosity measured using a capillary
viscometer) was initially considered; however, the reduced viscosity
of SPAM with concentration did not vary linearly, and thus it was
not possible to reliably determine [η]. Using the method of
specific viscosity,[38,39] the c* for PAM
and SPAM was ∼1500 and 0.01 ppm, respectively. For PAM, the c* value was in excellent agreement with that calculated
using [η], [η] = 6.5dLg, c[η]* ∼ 1530 ppm.
While there may be some error in the reported c*
value of SPAM (the value could not be verified from [η]), the
non-Newtonian response of SPAM was seen at a significantly lower concentration
than that for PAM; therefore, the reported difference in c* values is reasonable. Further details of this method are provided
in Figure S1 of the Supporting Information.
The high occupied volume and greater interaction between SPAM chains
increase the fluid viscosity, but with increased hydrodynamic forces
(higher shear rates), the chains disentangle and align with the flow
to induce a shear-thinning fluid response.[40] The charge screening effect in high electrolyte solutions weakens
the rigidity of the polymer backbone (induced by charge repulsion)
and allows SPAM to adopt a more coiled conformation. It is reasonable
to assume that the collapse of the polyelectrolyte due to salt addition
will ultimately lead to a conformational state resembling that of
its nonionic counterpart (PAM) in a good solvent.[41,42] Therefore, the weak shear-thinning response at 10 ppm can be diminished
when up to 13.41 mM KCl is added to the base fluid (Figure b).
Figure 3
(a) Shear rate-dependent
fluid viscosity as a function of polymer
type (a, b) SPAM and (c) PAM. The effect of polymer concentration
is shown in panel (a) and panel (c), and the effect of electrolyte
(KCl) concentration is shown in panel (b). The fits in panel (a) are
based on the Carreau–Yasuda model, see eq .
(a) Shear rate-dependent
fluid viscosity as a function of polymer
type (a, b) SPAM and (c) PAM. The effect of polymer concentration
is shown in panel (a) and panel (c), and the effect of electrolyte
(KCl) concentration is shown in panel (b). The fits in panel (a) are
based on the Carreau–Yasuda model, see eq .To approximate the fluid viscosity in the regime
of drag reduction,
the approach was taken to fit the flow curve data using the Carreau–Yasuda
model to determine the infinite shear viscosity (η∞) and then calculate Re using eq . The Carreau–Yasuda model is given
bywhere ηeff(γ̇)
is the fluid viscosity as a function of shear rate, η0 is the zero-shear viscosity, η∞ is the infinite
shear viscosity, κ is the consistency index, n is the power-law index, and a describes the transition
from Newtonian to power law behavior. Details regarding all parameters
of the Carreau–Yasuda model are provided in Table S1 of the Supporting Information. For the nonionic PAM,
the fluid was found to be Newtonian or weakly non-Newtonian at the
polymer concentrations used for drag reduction testing, thus the η∞ was taken to be the fluid viscosity at the highest
measured shear rate.
Drag Reduction
Figure shows typical drag reduction data for PAM (Figure a,b) and SPAM (Figure c,d) at increasing
polymer concentrations in Milli-Q water. All data is compared to Milli-Q
water only. When considering the raw data of rotational speed and
torque, for PAM, at low rotational speeds (<10 rad/s) in the laminar
flow regime, the polymer concentration-torque data superimposes the
Milli-Q water baseline, which is characteristic for a Newtonian fluid
and consistent with Bizotto and Sabadini et al.,[26] who studied PEO and PAM drag-reducing fluids. The flow
regime becomes unstable with increasing rotational speed and the measured
torque values for the polymeric fluids diverge from the Milli-Q water
baseline at a critical rotational speed, ω = ωcrit, with the measured torque found to be lower at higher polymer concentrations,
except at 250 ppm PAM, where a higher torque value was measured compared
to 50 and 100 ppm. This inconsistency is magnified for SPAM (Figure c), with torque values
mostly exceeding those of Milli-Q water in both the stable and unstable
flow regimes. In the stable regime, this is partly attributed to the
high fluid viscosity of the non-Newtonian SPAM fluids, shifting the
transition to unstable flow and thus the onset of drag reduction,
similar to the study of Dutcher and Muller,[30] who attributed the shift in flow regime to be governed by weak fluid
viscoelasticity. Although the flow is unstable, for SPAM concentrations
of 50 and 100 ppm, the measured torque remains to exceed that of Milli-Q
water over a wide range of rotational speeds, which may be interpreted
as an apparent drag enhancement. Drag enhancement has also been observed
in pressure-driven flows when using extended polymers and operating
at low shear rates (low Re) below the onset of drag
reduction.[43,44] In contrast to pipe flow, defining
drag reduction by rotational rheometry (low Re),
as shown in this study, is less trivial.
Figure 4
Fluid drag reduction
by PAM (a, b) and SPAM (c, d) as a function
of the polymer concentration. Panels (a) and (c) compare the raw data
of torque against rotational speed. Panels (b) and (d) compare the
dimensionless data plotted in Prandtl–von Karman coordinates
for the condition Log Rep√f ≥ 1.6. The dashed lines (b, d) show the empirically
determined maximum drag reduction (MDR), which was estimated using
a least-squares linear regression approach, taking the form of eq for the data of 500 < c < 750 ppm PAM. Further details are provided in Figure S2 of the Supporting Information.
Fluid drag reduction
by PAM (a, b) and SPAM (c, d) as a function
of the polymer concentration. Panels (a) and (c) compare the raw data
of torque against rotational speed. Panels (b) and (d) compare the
dimensionless data plotted in Prandtl–von Karman coordinates
for the condition Log Rep√f ≥ 1.6. The dashed lines (b, d) show the empirically
determined maximum drag reduction (MDR), which was estimated using
a least-squares linear regression approach, taking the form of eq for the data of 500 < c < 750 ppm PAM. Further details are provided in Figure S2 of the Supporting Information.The region of drag reduction (Log Rep√f >1.6) plotted
in Prandtl–von
Karman coordinates is shown in Figure b (PAM) and Figure d (SPAM). On the semi-log plot, the value of 1/√f increases with Rep, and for
PAM, the data of 1/√f diverges from the Milli-Q
water baseline while exhibiting a type A drag reduction response.
At 1 ppm PAM, baseline divergence is seen at Log Rep√f = 1.9, but for 250 ppm, divergence
occurs at a lower value, Log Rep√f = 1.42, very close to the onset of unstable
flow, Log Rep√f = 1.29; hence, the onset of drag reduction occurs at a lower critical Rep for higher polymer concentrations, which
is consistent with other studies.[45,46] For Log Rep√f > 1.8, the magnitude
of drag reduction increases with increasing polymer concentration.
However, at Log Rep√f = 2.0, the polymeric friction lines for 100 and 250 ppm
PAM approach the maximum drag reduction asymptote (MDR, dashed line
in Figure b), with
the slope of the polymeric friction line at 250 ppm attaining similar
values to the MDR line. Hence, further increases in polymer concentration
produce no discernible effect on the drag reduction. Such behavior
is more consistent with drag reduction in pipes,[47,48] and underlines the need to accurately account for fluid viscosity
when studying drag reduction using rotational rheometry with a small
annular gap.When accounting for the correct fluid viscosity
to calculate Rep (Re based
on the rotational
velocity and fluid viscosity, see eq ), the 250 ppm PAM fluid shows drag reduction and not
drag enhancement. For SPAM (Figure d), the effect of polymer concentration on drag reduction
performance is less clear. At low Re (Log Rep√f ≲ 1.85),
drag reduction increases in the following order: 20 > 100 >
1 ppm,
while at higher Re (Log Rep√f ≳ 1.85), the order
changes to 100 > 20 > 1 ppm and is more consistent with PAM
fluids.
This highlights the nonlinear response of SPAM (also seen in Figure c), which is attributed
to mild fluid hysteresis at low Rep and
at concentrations ≥5 ppm.[49] Similar
hysteresis has been observed for polymers of high elasticity[30,50] and is attributed to polymer conformational hysteresis.[51] It is noted that the PAM fluids showed no hysteresis,
even at the highest concentration of 750 ppm. The relevance of this
effect is discussed with reference to Figure b.
Figure 9
Rotational speed (ω, rad/s) flow sweep tests for
(a) 250
ppm PAM and (b) 10 ppm SPAM in Milli-Q water and 13.41 mM KCl. The
solid line is water.
The calculated drag reductions (eq ) based on torque and 1/√f are
shown in Figure for
PAM (Figure a torque; Figure b 1/√f) and SPAM (Figure c torque; Figure d 1/√f). If the fluid viscosity were
not considered (DR based on the torque), then the added polymer is
seen to promote drag enhancement at low rotational speeds, which eventually
decays as the rotational speed increases. As previously discussed,
this is attributed to the high viscosity of the fluids, which is more
prominent in SPAM than PAM. As such, at the highest SPAM concentrations,
an apparent drag enhancement is observed at all rotational speeds;
see Figure e,f for
the comparison of the critical rotational speed (ωcrit) to induce drag reduction. For PAM, ωcrit becomes
independent of polymer concentration; however, the effect of polymer
concentration on ωcrit remains strong for SPAM over
the studied concentration range. Accounting for the changes in fluid
viscosity with polymer concentration (Log Rep√f), the drag reduction response
of the PAM fluids is corrected, and the fluids exhibit negligible
drag enhancement (within the measurement noise) before a definitive
drag reduction regime is observed. However, for the SPAM fluids, a
strong drag enhancement remains for the highest polymer concentrations,
which is attributed to an incorrect interpretation of Rep when the flow regime is laminar, i.e., the condition
of η∞ is not satisfied. It is noted that the
apparent drag reduction with increasing Rep appears to oscillate. The first increase in DR% is attributed to
an extension of the laminar regime for high-viscosity fluids (i.e., Ta is inversely proportional to the fluid viscosity; hence
the onset of flow instabilities is delayed), and thus the true onset
of drag reduction is taken as the second intercept of DR% = 0, and
thereafter, a constant enhancement of DR% was observed with increasing
Log Rep√f. Based on this interpretation of the data, the Recrit for PAM decreased with increasing polymer concentration,
while for SPAM, the Recrit fluctuated
before being independent of polymer concentration when c ≥ 20 ppm. This response would not be consistent with type
A drag reduction but may suggest a type B response, where the critical
transition is less affected by the polymer concentration.[52]
Figure 5
Polymer-induced drag reduction calculated using eq , where the variable () is taken to be the measured torque (a, c)
or 1/√f (b, c) for polymers PAM (a, b) and
SPAM (c, d). The effect
of polymer concentration on the onset of drag reduction defined as
the critical rotational speed (ωcrit) and Reynolds
number (Recrit) for PAM (e) and SPAM (f).
Polymer-induced drag reduction calculated using eq , where the variable () is taken to be the measured torque (a, c)
or 1/√f (b, c) for polymers PAM (a, b) and
SPAM (c, d). The effect
of polymer concentration on the onset of drag reduction defined as
the critical rotational speed (ωcrit) and Reynolds
number (Recrit) for PAM (e) and SPAM (f).To compare the drag reduction performance of PAM
and SPAM, it is
desirable to normalize the polymer concentration by the polymer volume
fraction, which requires an accurate measure of the intrinsic viscosity.[53,54] With SPAM being a polyelectrolyte, its reduced viscosity does not
vary linearly with polymer concentration, and hence it is not possible
to attain a reliable measure of the intrinsic viscosity in salt-free
solutions. Therefore, the method of Little et al.[55] was followed which normalizes the concentration by the
intrinsic concentration (cint) of the
polymer solution. The cint was defined
by Virk et al.[16] as, , where DRmax is the theoretical
maximum drag reduction and is the intrinsic drag reduction. Plots
of c/DR against c to determine cint for both polymers are provided in Figure S3 of the Supporting Information.Figure a compares
the DR% (difference in torques at the same rotational speed, 180 rad/s)
as a function of c/cint, with the trend being consistent for both polymer fluids, and a
maximum DR% was found when c/cint ∼ 8, indicating the onset of a region influenced
by the increasing fluid viscosity. When compared at constant Rep (differences in friction factors) (Figure b), the DR% for both
polymers increases with c/cint before plateauing at the highest values of c/cint. In this region, SPAM is found
to be a more efficient drag reducer than PAM, with a DRmax of 27.6% compared to 22.3% for PAM, and having a lower intrinsic
concentration, see Table for all values of DRmax, cint, and . Therefore, to achieve equivalent values
of DR%, the effective concentration of SPAM is less than PAM and confirms
the polymer to be more efficient in promoting fluid drag reduction,
with the difference in performance attributed to the greater apparent
size of the anionic SPAM relative to the nonionic PAM.
Figure 6
PAM and SPAM polymer
drag reduction as a function of c/cint, where c is the
polymer concentration (ppm) and cint is
the intrinsic concentration of the polymer fluid. The data is shown
for both an equivalent rotational speed (a) and shear Reynolds number
(Rep) (b). The gray-shaded regions represent
the same data in both panels (a) and (b) but are included to highlight
the reduction in DR% in panel (a) and the plateau of DR% in panel
(b).
Table 1
Parameters for a
polymer
DRmax (%)
% deviation
from actual DRmax
cint (ppm)
PAMω
25.0
8.0
11.7
2.14
SPAMω
16.2
10.7
1.0
15.77
PAMRe
22.3
5.8
46.5
0.48
SPAMRe
27.6
8.9
10.1
2.73
The % deviation DRmax is the difference between the theoretical DRmax and measured
DRmax.
PAM and SPAM polymer
drag reduction as a function of c/cint, where c is the
polymer concentration (ppm) and cint is
the intrinsic concentration of the polymer fluid. The data is shown
for both an equivalent rotational speed (a) and shear Reynolds number
(Rep) (b). The gray-shaded regions represent
the same data in both panels (a) and (b) but are included to highlight
the reduction in DR% in panel (a) and the plateau of DR% in panel
(b).The % deviation DRmax is the difference between the theoretical DRmax and measured
DRmax.
Stability of Drag Reduction
Along with the maximum
drag reduction, the shear stability should also be considered. From eq , and taking x as the friction factor (eq ), the drag reduction with time is shown as: (i) a function
of increasing polymer concentration at a constant Rep; and (ii) at a fixed polymer concentration and increasing Rep, see Figure for PAM. The inset data in Figure shows the relative change in DR from t = 0 (DRRelative = DR/DR0) and is fitted using a least-squares regression
model that describes the loss in drag reduction with time, which is
given by[56]where W and b are fitting parameters that describe the shear stability and decay
rate, respectively.
Figure 7
Drag reduction stability for PAM as a function of (a)
increasing
polymer concentration and at a constant Re and (b)
at a fixed polymer concentration (50 ppm) and increasing Rep. All DR% values were calculated based on the friction
factor. Insets show the relative change in drag reduction (DRRelative) with time. Equation is used to fit the DRRelative data, and
the fitting parameters W and b are
provided in the inset graphs.
Drag reduction stability for PAM as a function of (a)
increasing
polymer concentration and at a constant Re and (b)
at a fixed polymer concentration (50 ppm) and increasing Rep. All DR% values were calculated based on the friction
factor. Insets show the relative change in drag reduction (DRRelative) with time. Equation is used to fit the DRRelative data, and
the fitting parameters W and b are
provided in the inset graphs.For all PAM concentrations shown in Figure a, the flow regime is unstable
at Rep = 3149. With increasing polymer
concentrations
the relative stability of drag reduction increases as the turbulent
fluid stresses become increasingly modulated. Such behavior is consistent
with previous observations.[35]At
a fixed PAM concentration and increasing Rep (Figure b), the
relative change in drag reduction showed a weak dependence
on Rep; only the highest Rep values lead to measurable losses in DR. At low Rep, the fluid stress intensity is lower; hence
polymer stretching is weakened, which leads to an apparent increase
in polymer stability. At higher Rep (Rep > 3000), the strong interaction between
the
high-molecular-weight polymer and fluid instabilities imposes greater
stress on the extended polymer chains, likely causing the linear polymer
chains to undergo chain scission, reducing the molecular weight below
a critical threshold needed to induce the DRmax. As shown
in the inset of Figure b, only at Rep ∼ 3454 is the relative
change in drag reduction significant, decreasing by almost 60% within
1000 s. At this flow condition, the initial apparent shear stress
is 8.94 Pa compared to 6.81 Pa for Rep ∼ 2740, where the relative change in drag reduction was <8%.The drag reduction stability of SPAM as a function of polymer concentration
and Rep are shown in Figure . Due to the strong non-Newtonian
fluid response, the highest concentration was limited to 20 ppm where
the relative infinite shear viscosity of the polymer fluid was 1.08
× 10–3 Pa s. Unlike PAM, the effect of polymer
concentration on DR loss is less clear. At 1 ppm, the DR% is low (∼5–7%)
and likely contributes to the high apparent stability of the polymer
with time. With increasing polymer concentration, the decay rate of
drag reduction also increased. All polymer fluids appeared to degrade
rapidly within the first 400 s of shearing; thereafter, the polymer
fluids were stable. Although the range of concentrations was small,
a faster loss of drag reduction at higher SPAM concentrations is counterintuitive
and points to an influence of the semi-dilute regime and high occupied
volume of the polymer chains in the fluid when measured using the
rheometer method. Furthermore, for some experimental conditions, the
stress applied was consistent with that used for the PAM tests, and
hence those differences in apparent stability are independent of the
fluid stress.
Figure 8
Drag reduction stability for SPAM as a function of (a)
increasing
polymer concentration and at a constant Re and (b)
at a fixed polymer concentration (10 ppm) and increasing Rep. All DR% values were calculated based on the friction
factor. Insets show the relative change in drag reduction (DRRelative) with time. Equation was used to fit the DRRelative data, with
the fitting parameters W and b being
provided in the inset graphs.
Drag reduction stability for SPAM as a function of (a)
increasing
polymer concentration and at a constant Re and (b)
at a fixed polymer concentration (10 ppm) and increasing Rep. All DR% values were calculated based on the friction
factor. Insets show the relative change in drag reduction (DRRelative) with time. Equation was used to fit the DRRelative data, with
the fitting parameters W and b being
provided in the inset graphs.When increasing Rep (1100 < Rep < 2950) at a fixed
polymer concentration
(Figure b), the loss
of drag reduction weakly depends on Rep. For Rep between 1100 and 1700, the
relative loss of drag reduction was very similar and only at Rep ∼ 2950 was the rate of loss and the
magnitude of drag reduction loss increased further. Although not commonly
observed, a similar response of faster drag reduction loss at higher
polymer concentration has been reported by Bizotto and Sabadini[26] studying extended polyacrylamide. The authors
attributed the behavior to the low optimum polymer concentration for
DRmax and the high fluid viscosity, which in the current
study may not be valid since 10 ppm SPAM and 250 ppm PAM have almost
equal fluid viscosities (η∞) but undergo contrasting
drag reduction losses. Moreover, the apparent rapid drag reduction
loss of SPAM may be attributed to a time effect, as indicated by Pereira
et al.,[45] who showed that polymer (xanthan
gum) de-aggregation can influence the apparent drag reduction stability.
Gentle pre-shearing of the test fluids prior to measurement led to
improved drag reduction stability (removed the rapid decay in drag
reduction loss), which the authors attributed to de-aggregation of
polymer chains in solution.To assess if time-dependency was
important, 250 ppm PAM and 10
ppm SPAM (fluids of almost equivalent infinite shear fluid viscosities)
were subjected to shear ramp tests, as shown in Figure . For 250 ppm PAM (below c*), negligible
hysteresis was observed in the nonlaminar flow regime, and the slight
reduction in fluid viscosity (2 × 10–5 Pa s)
before and after shearing may correspond to a small decrease in the
average polymer molecular weight by shear-induced polymer chain scission
but is noted to be within the measurement error. The hysteresis loop
for 10 ppm SPAM (semi-dilute regime, above c*) is
more pronounced in the nonlaminar flow regime, and a crossover in
the loop was observed in the region of emerging drag reduction. In
the laminar flow regime, the fluid viscosities before and after shearing
were equivalent, indicating no apparent change in the average molecular
weight of the polymer. The contrasting hysteresis response between
the two fluids suggests that the SPAM fluid does not undergo substantial
polymer degradation, and the apparent rapid loss of drag reduction
is likely due to the hysteresis (time effect) response of the fluid.
The hysteresis response of SPAM could be diminished by increasing
the salt (KCl) concentration. By neutralizing the charge on SPAM the
polymer behaves similarly to the nonionic PAM (Figure b) and undergoes reduced loss of drag reduction
under prolonged shearing (Figure S4). However,
this behavior would contradict the general understanding that adding
salt to charged polymers decreases the stability of drag reduction.[35]Rotational speed (ω, rad/s) flow sweep tests for
(a) 250
ppm PAM and (b) 10 ppm SPAM in Milli-Q water and 13.41 mM KCl. The
solid line is water.These observations further support the understanding
that the apparent
rapid loss of drag reduction for SPAM (Figure ), when measured using the double-gap concentric
cylinder geometry, is not due to polymer degradation but a predominantly
shear/time-dependent effect when the polymer concentration is in the
semi-dilute regime.
Comparison of Rheometry and Pipe Flow Data
Although
rotational rheometry can be used to rapidly screen polymers for drag
reduction, it is important that the characteristic behavior is consistent
with pipe flow. Figure a compares the drag reduction performance of SPAM as measured
by rotational rheometry and pipe flow, with the flow conditions for
both setups being Rep ∼ 1700 (Ta < 7.7 × 105, turbulent Taylor vortex
regime) and Rep from ∼51,000 to
∼97,000 (dependent on the polymer concentration). While the
trends in DR% with increasing SPAM concentration were similar (Figure a), the magnitude
of drag reduction was vastly different, which could be attributed
to the differences in Re and the associated flow
regimes. While lower flow rates for the pipe flow were considered,
harmonic instabilities in the pressure response meant lower flow rates
were not possible; as such, 80 L/min was taken as the lowest flow
rate. At the test conditions, the rheometer data indicated an optimum
polymer concentration between 50 and 100 ppm, whereas, for the pipe
flow, the optimum concentration was slightly above 100 ppm as the
DR% asymptotes to the MDR. We attribute this difference to the time
effect that is more apparent in the rheometer data than in the pipe
flow data. At higher SPAM concentrations, the time effect is more
severe (Figure a),
which slightly offsets the drag reduction effect.
Figure 10
(a) Pipe flow and rheometry
DR% for SPAM as a function of the polymer
concentration. The flow conditions for the double-gap geometry and
pipe flow were Re ∼ 1700 and Rep ∼ 97,000 (5 ppm SPAM) to ∼51,000 (100
ppm SPAM). (b) Normalized DR/c as a function of the normalized polymer
concentration for both pipe flow and rheometry geometries. The determination
of DRint and cint are given
in Figure S5 of the Supporting Information.
The fitting parameters for the data are provided in Table . (c) Drag reduction stability
for SPAM as a function of the polymer concentration and at a constant
volumetric flow rate. The Brostow model (eq ) was used to fit the data with the parameters W and b provided in the figure.
(a) Pipe flow and rheometry
DR% for SPAM as a function of the polymer
concentration. The flow conditions for the double-gap geometry and
pipe flow were Re ∼ 1700 and Rep ∼ 97,000 (5 ppm SPAM) to ∼51,000 (100
ppm SPAM). (b) Normalized DR/c as a function of the normalized polymer
concentration for both pipe flow and rheometry geometries. The determination
of DRint and cint are given
in Figure S5 of the Supporting Information.
The fitting parameters for the data are provided in Table . (c) Drag reduction stability
for SPAM as a function of the polymer concentration and at a constant
volumetric flow rate. The Brostow model (eq ) was used to fit the data with the parameters W and b provided in the figure.
Table 2
Fitting arameters from Figure b for both rheometer and pipe
flow dataa
geometry
DRmax (%)
% deviation
from actual DRmax
cint (ppm)
k
rheometer
27.6
8.9
10.1
2.7
1
pipe loop
92.5
14.6
15.9
5.8
1
The % deviation DRmax is the difference between the theoretical DRmax and measured
DRmax.
Taking the approach of Virk et al.,[16] the DR% from both pipe flow and rheometry experiments
can be compared
when plotting against c/cint. As shown in Figure b, the two data sets are in good agreement (the experimental
fits take the form of , where k describes the
polymer–solvent interaction, and all fitting parameters are
provided in Table ), which means that the polymer concentration
dependence on drag reduction is consistent between the two geometries.
Moreover, the intrinsic concentrations (cint) for the rheometer and pipe flow geometries were 10.1 and 15.9 ppm,
respectively, confirming that the polymer concentrations to achieve
half DRmax were similar. However, as previously noted,
caution should be taken when assessing the drag reduction stability
of non-Newtonian semi-dilute polymers using the rheometer technique.
This is because, when measuring the effect of SPAM concentration on
drag reduction loss, the pipe flow data was more consistent with the
common understanding that drag reduction is more stable at higher
polymer concentrations.[35] It is also noted
that the loss of drag reduction occurs over tens of minutes rather
than a few minutes (Figure ), suggesting that the response is not a viscoelastic time
effect as seen in the rheometer, but is more likely to be drag reduction
loss due to a change in the average molecular weight of the polymer.
With higher fluid shear stresses in pipe flow (wall shear stress up
to ∼60 Pa) compared to the rheometer (shear stress up to ∼8
Pa), polymer chain scission is expected to be more severe.The % deviation DRmax is the difference between the theoretical DRmax and measured
DRmax.
Conclusions
The drag reduction performance of high-molecular-weight
polymers
(PAM and SPAM) was measured using a shear rheometer with double-gap
concentric cylinder geometry. This method is ideal for chemical screening
as it needs small sample volumes and tests can be rapidly run. However,
the performance characteristics as measured by rheometry are not often
correlated to pipe flow data, and this study highlights features of
the rheometry method that must be correctly interpreted to ensure
reliable performance characteristics are described.Two high-molecular-weight
(several MDa) polymers, nonionic PAM
and anionic sulfonated PAM, were selected as they provided contrasting
rheology. The high c* for PAM meant the test fluids
were Newtonian and dilute, while the low c* (semi-dilute)
for SPAM led to non-Newtonian, shear-thinning behavior. For the rheometry
method with Taylor instabilities, the performance of DR based on the
raw data increased with polymer concentration up to c/cint ∼ 8, but at higher concentrations
the DR% appeared to fall due to a greater influence of the polymeric
fluid viscosity on the measured torque. To correctly describe the
data, the raw data was analyzed by calculating the friction factor
and the Re based on the infinite shear viscosity
of the fluid to compare DR% at equivalent Rep. The maximum drag reduction of SPAM exceeded that of PAM
at Rep ∼ 1700, with the improved
performance attributed to the slightly higher Mw and apparent size
of the charged polymer. With extended shearing, the drag reduction
loss of PAM was generally consistent with literature findings,[2,45] in that higher polymer concentrations extended the time of drag
reduction and higher Rep increased the
rate of drag reduction loss. The drag reduction stability of SPAM
showed negligible effects of polymer concentration and Rep, with a significant loss of drag reduction occurring
within 200–300 s. For SPAM, shear sweep tests revealed a hysteresis
(viscoelastic effect) that contributes to the apparent fast decay
in drag reduction performance. This is likely a consequence of the
polymer concentration being in the semi-dilute regime and the non-Newtonian
fluid response. In pipe flow, the effect is not apparent due to the
high stresses imposed on the fluid, with the loss of drag reduction
occurring over tens of minutes and the stability being dependent on
the polymer concentration, leading to a behavior more consistent with
the mechanism of polymer degradation via shear-induced polymer chain
scission. While the stability data for non-Newtonian polymeric fluids
in the semi-dilute regime is less reliable when measured by the double-gap
geometry, the relative scaling of drag reduction with polymer concentration
was found to be reasonably consistent between the two flow geometries.