| Literature DB >> 35890033 |
Chunyan Niu1, Yajie Zhang1, Yong Zhang1.
Abstract
The detection and enumeration of Legionella pneumophila (L. pneumophila) in water is crucial for water quality management, human health and has been a research hotspot worldwide. Due to the time-consuming and complicated operation of the plate culture method, it is necessary to adopt a fast and effective method for application. The present study aimed to comprehensively evaluate the performance and applicability of the MPN method by comparing its qualitative and quantitative results with the GB/T 18204.5-2013 and ISO methods, respectively. The qualitative results showed that 372 samples (53%) were negative for both methods; 315 samples (45%) were positively determined by the MPN method, compared with 211 samples (30%) using GB/T 18204.5-2013. The difference in the detection rate between the two methods was statistically significant. In addition, the quantitative results showed that the concentration of L. pneumophila by the MPN method was greater than ISO 11731 and the difference was statistically significant. However, the two methods were different but highly correlated (r = 0.965, p < 0.001). The specificity and sensitivity of the MPN method were 89.85% and 95.73%, respectively. Overall, the results demonstrated that the MPN method has higher sensitivity, a simple operation process and good application prospects in the routine monitoring of L. pneumophila from water samples.Entities:
Keywords: Legionella pneumophila; MPN method; condensed water; cooling water; plate culture; sanitary hot water
Year: 2022 PMID: 35890033 PMCID: PMC9324539 DOI: 10.3390/pathogens11070789
Source DB: PubMed Journal: Pathogens ISSN: 2076-0817
Figure 1The concentration of L. pneumophila was determined by the MPN method under different treatment methods.
McNemar’s test analysis of the results for detection of L. pneumophila for MPN method and GB/T 18204.5-2013.
| MPN Method | GB/T 18204.5-2013 | Total | χ2-Value | ||
|---|---|---|---|---|---|
| + | − | ||||
| + | 202 | 113 | 315 | 311.388 | <0.001 |
| − | 9 | 372 | 381 | ||
| Total | 211 | 485 | 696 | ||
Figure 2Comparison of the quantitative data from MPN method and ISO method. Note that count for MPN method: log/(MPN/100 mL), ISO method: log/ (CFU/ 100 mL).
Figure 3Comparison of the quantitative data from MPN method and ISO method. Count in y-axis: log/(MPN/100 mL) for MPN method or log/(CFU/100 mL) for ISO method.
Figure 4Detection data of L. pneumophila in different water samples by MPN method and GB/T 18204.5-2013.