Azhan Fikry1, Siow Chun Lim1, Mohd Zainal Abidin Ab Kadir2.
Abstract
Background: There has been rising concern amongst the public regarding their home's proximity to high tension power transmission lines. The primary cause of fear is the impact of the electromagnetic interference (EMI) radiation on the nearby occupants' health. Despite the presence of national permissible limits of EMI radiation, there is still lack of information with regards to the EMI radiation of the types of power lines configuration in Malaysia.Entities:
Keywords: ELF; EMF; EMI radiation; ICNIRP; Right-of-Way; power transmission lines; public exposure limit
Mesh:
Year: 2021 PMID: 35387277 PMCID: PMC8941290 DOI: 10.12688/f1000research.73067.2
Source DB: PubMed Journal: F1000Res ISSN: 2046-1402
Figure 1. Overhead power transmission lines towers in Malaysia. - , ,
Figure 2. Overall project flow.
Figure 3. Geometrical illustration for the magnetic and electric field calculation.
Geometrical parameters.
| Coordinates of plotted area | ||||
|---|---|---|---|---|
| x1 | x2 | y1 | y2 | Step |
| −30 m | 30 m | 0 m | 40 m | 0.1 m |
Figure 4. Double circuit phase configuration for standard transposed phasing (left) and un-transposed phasing (right).
Figure 5. Quadruple circuit phase configuration for standard transposed phasing (left) and un-transposed phasing (right).
275/132 kV quadruple circuit power line.
| No | Phase code | Cond. coordinate | Current rating (A) | Voltage level (kV) | Phase angle (Deg.) | |||
|---|---|---|---|---|---|---|---|---|
| U | T | x(m) | y(m) | U | T | |||
| 1 | A1 | A1 | −6.0 | 43.13 | 1232 | 275 | 0 | 0 |
| 2 | B1 | B1 | −6.0 | 37.58 | 1232 | 275 | 120 | 120 |
| 3 | C1 | C1 | −6.0 | 32.03 | 1232 | 275 | 240 | 240 |
| 4 | A2 | C2 | 6.0 | 43.13 | 1232 | 275 | 0 | 240 |
| 5 | B2 | B2 | 6.0 | 37.58 | 1232 | 275 | 120 | 120 |
| 6 | C2 | A2 | 6.0 | 32.03 | 1232 | 275 | 240 | 0 |
| 7 | a1 | c1 | −5.2 | 24.31 | 729 | 132 | 0 | 240 |
| 8 | b1 | b1 | −5.2 | 20.43 | 729 | 132 | 120 | 120 |
| 9 | c1 | a1 | −5.2 | 16.55 | 729 | 132 | 240 | 0 |
| 10 | a2 | a2 | 5.2 | 24.31 | 729 | 132 | 0 | 0 |
| 11 | b2 | b2 | 5.2 | 20.43 | 729 | 132 | 120 | 120 |
| 12 | c2 | c2 | 5.2 | 16.55 | 729 | 132 | 240 | 240 |
500 kV double circuit power line.
| No | Phase code | Cond. coordinate | Current rating (A) | Voltage level (kV) | Phase angle (Deg.) | |||
|---|---|---|---|---|---|---|---|---|
| U | T | x(m) | y(m) | U | T | |||
| 1 | A1 | A1 | −6.2 | 47.5 | 2309.4 | 500 | 0 | 0 |
| 2 | B1 | B1 | −6.2 | 36.5 | 2309.4 | 500 | 120 | 120 |
| 3 | C1 | C1 | −7.0 | 25.25 | 2309.4 | 500 | 240 | 240 |
| 4 | A2 | C2 | 6.2 | 47.5 | 2309.4 | 500 | 0 | 240 |
| 5 | B2 | B2 | 6.2 | 36.5 | 2309.4 | 500 | 120 | 120 |
| 6 | C2 | A2 | 7.0 | 25.25 | 2309.4 | 500 | 240 | 0 |
Benchmarked public exposure limits.
| No | Category | Public exposure limit |
|---|---|---|
|
| Specific International Organization | ICNIRP 2010
|
|
| National Standardization Committee | EU Recommendation 1999
|
|
| Regional variation of a country | Exposure limit for the residential region – Slovenia and Italy
|
Magnetic field of the power transmission lines in Malaysia.
| Type of power lines | Conducting ground | Phasing | Magnetic flux densities (μT) | Compliance to exposure limit? | |||||
|---|---|---|---|---|---|---|---|---|---|
| Yes | No | Untransposed | Transposed | Under the line | ROW boundary | ICNIRP | EU | Slovenia/Italy | |
| 132 kV double circuit | ✓ | ✓ | 4.794284 | 0.253069 | Yes | Yes | Yes | ||
| ✓ | ✓ | 0.545671 | 0.624946 | Yes | Yes | Yes | |||
| ✓ | ✓ | 2.6043 | 1.4302 | Yes | Yes | Yes | |||
| ✓ | ✓ | 1.3384 | 0.4673 | Yes | Yes | Yes | |||
| 275 kV double circuit | ✓ | ✓ | 3.928109 | 0.960835 | Yes | Yes | Yes | ||
| ✓ | ✓ | 0.443016 | 1.074408 | Yes | Yes | Yes | |||
| ✓ | ✓ | 2.088845 | 1.494544 | Yes | Yes | Yes | |||
| ✓ | ✓ | 1.263348 | 0.636509 | Yes | Yes | Yes | |||
| 132/132 kV quadruple circuit | ✓ | ✓ | 13.62006 | 2.978469 | Yes | Yes | Yes | ||
| ✓ | ✓ | 1.13004 | 0.340224 | Yes | Yes | Yes | |||
| ✓ | ✓ | 7.28901 | 4.670191 | Yes | Yes | Yes | |||
| ✓ | ✓ | 1.493262 | 0.676831 | Yes | Yes | Yes | |||
| 275/132 kV quadruple circuit | ✓ | ✓ | 10.13539 | 2.489524 | Yes | Yes | Yes | ||
| ✓ | ✓ | 0.909531 | 0.18436 | Yes | Yes | Yes | |||
| ✓ | ✓ | 5.405135 | 3.546732 | Yes | Yes | Yes | |||
| ✓ | ✓ | 1.113876 | 0.588538 | Yes | Yes | Yes | |||
| 500 kV double circuit | ✓ | ✓ | 18.43185 | 4.860459 | Yes | Yes | Yes | ||
| ✓ | ✓ | 2.857379 | 4.293753 | Yes | Yes | Yes | |||
| ✓ | ✓ | 9.693522 | 6.762919 | Yes | Yes | Yes | |||
| ✓ | ✓ | 4.852491 | 2.516856 | Yes | Yes | Yes | |||
Electric field of the power transmission lines in Malaysia.
| Type of power lines | Conducting ground | Phasing | Electric field strength (kV/m) | Compliance to exposure limit? | |||||
|---|---|---|---|---|---|---|---|---|---|
| Yes | No | Untransposed | Transposed | Under the line | ROW boundary | ICNIRP | EU | Slovenia/Italy | |
| 132 kV double circuit | ✓ | ✓ | 0.924003 | 0.24556 | Yes | Yes | Yes | ||
| ✓ | ✓ | 0.15441 | 0.17748 | Yes | Yes | Yes | |||
| ✓ | ✓ | 0.263679 | 0.17961 | Yes | Yes | Yes | |||
| ✓ | ✓ | 0.182788 | 0.121504 | Yes | Yes | Yes | |||
| 275 kV double circuit | ✓ | ✓ | 1.50842 | 0.574706 | Yes | Yes |
| ||
| ✓ | ✓ | 0.222091 | 0.450741 | Yes | Yes | Yes | |||
| ✓ | ✓ | 0.394063 | 0.305229 | Yes | Yes | Yes | |||
| ✓ | ✓ | 0.276856 | 0.181895 | Yes | Yes | Yes | |||
| 132/132 kV quadruple circuit | ✓ | ✓ | 1.12788 | 0.367053 | Yes | Yes | Yes | ||
| ✓ | ✓ | 0.354182 | 0.319246 | Yes | Yes | Yes | |||
| ✓ | ✓ | 0.321052 | 0.211805 | Yes | Yes | Yes | |||
| ✓ | ✓ | 0.105488 | 0.081465 | Yes | Yes | Yes | |||
| 275/132 kV quadruple circuit | ✓ | ✓ | 1.48149 | 0.57809 | Yes | Yes |
| ||
| ✓ | ✓ | 0.534335 | 0.450279 | Yes | Yes | Yes | |||
| ✓ | ✓ | 0.457699 | 0.31446 | Yes | Yes | Yes | |||
| ✓ | ✓ | 0.135271 | 0.113173 | Yes | Yes | Yes | |||
| 500 kV double circuit | ✓ | ✓ | 3.08961 | 1.09486 | Yes |
|
| ||
| ✓ | ✓ | 0.651354 | 0.74896 | Yes |
|
| |||
| ✓ | ✓ | 0.724198 | 0.539665 | Yes |
|
| |||
| ✓ | ✓ | 0.414757 | 0.232802 | Yes | Yes | Yes | |||