| Literature DB >> 35125624 |
Man Fan1, Zheng Fu1, Jia Wang1, Zhaoying Wang1, Hanxiao Suo1, Xiangfei Kong1, Han Li1.
Abstract
In the era of Corona Virus Disease 2019 (COVID-19), inappropriate indoor ventilation may turn out to be the culprit of microbial contamination in enclosed spaces and deteriorate the environment. To collaboratively improve the thermal comfort, air quality and virus spread control effect, it was essential to have an overall understanding of different ventilation modes. Hence, this study reviewed the latest scientific literature on indoor ventilation modes and manuals of various countries, identified characteristics of different ventilation modes and evaluated effects in different application occasions, wherefore to further propose their main limitations and solutions in the epidemic era. For thermal comfort, various non-uniform ventilation modes could decrease the floor-to-ceiling temperature difference, draft rate or PPD by 60%, 80% or 33% respectively, or increase the PMV by 45%. Unsteady ventilation modes (including intermittent ventilation and pulsating ventilation) could lower PPD values by 12%-37.8%. While for air quality and virus spread control, non-uniform ventilation modes could lower the mean age of air or contaminants concentration by 28.3%-47% or 15%-47% respectively, increase the air change efficiency, contaminant removal effectiveness or protection efficiency by 6.6%-10.4%, 22.6% or 14%-50% respectively. Unsteady ventilation mode (pulsating ventilation) could reduce the peak pollutant concentration and exposure time to undesirable concentrations by 31% and 48% respectively. Non-uniform modes and unsteady modes presented better performance in thermal comfort, air quality and virus spread control, whereas relevant performance evaluation indexes were still imperfect and the application scenarios were also limited.Entities:
Keywords: Air quality; Non-uniform ventilation mode; Thermal comfort; Unsteady ventilation mode; Virus spread control
Year: 2022 PMID: 35125624 PMCID: PMC8799382 DOI: 10.1016/j.buildenv.2022.108831
Source DB: PubMed Journal: Build Environ ISSN: 0360-1323 Impact factor: 6.456
Keywords used in the literature retrieval.
| Category | Query set | Intention |
|---|---|---|
| Key terms | Indoor environment construction Energy conservation Ventilation forms Uniform state Non-uniform state Steady state Unsteady or dynamic state Public healthy | Studying impacts of ventilation modes on the control of virus spread, air quality and thermal comfort |
| Search criteria | Set the search scope to building or building cluster Concerned about indoor environment and pathological protection Concerned about the geographical location and climate of buildings | Determining ventilation modes application fields and characteristics |
Fig. 1Review content and flowchart of the present study.
Fig. 2Concept of different indoor environment construction methods.
Fig. 3The air dilution sketch of MV [19].
Simulation conditions of MV.
| Season | Supply air speed (m/s) | Supply air temperature (°C) | Wall temperature (External wall/Internal wall/Ceiling/Floor, °C) |
|---|---|---|---|
| Summer | 0.8 | 22 | 29.9/27.2/26.6/27.4 |
| Winter | 0.8 | 24 | −3.2/12.5/14.5/14.5 |
Fig. 4Temperature field of MV.
Fig. 5Sketches of various non-uniform ventilation modes.
Comparation of different non-uniform ventilation modes.
| Modes | Layouts | Characteristics | Advantages | Disadvantages |
|---|---|---|---|---|
| Displacement ventilation (DV) | Air outlets were located on the side wall at a lower height [ | Fresh air flowed upward with the thermal plume, pushing pollutants out of air vents at the top of the room [ | Suitable for various scenarios, high air quality in the breathing zone [ | Temperature stratification decreased the indoor thermal comfort [ |
| Personalized ventilation (PEV) | Air outlets were located near the desks, chairs and other places close to occupations [ | The environmental control of working area was strict and that of background area was not strict [ | Directly supplied fresh air into breathing zone to avoid process of background space with contaminants [ | Required high costs and inflexible locations [ |
| Underfloor air distribution (UFAD) | The air outlets were located on the floor [ | Controlled zone near the floor and uncontrolled zone near the ceiling [ | Good flexibility [ | Lower energy efficiency [ |
| Impinging jet ventilation (IJV) | The air outlets were located on the side wall slightly above the ground [ | Affected by buoyancy, rising conditioned air mixed with indoor air [ | Could be used for heating in winter [ | Directly sent cold air near the floor under cooling condition, resulting in high energy consumption [ |
| Stratum ventilation (SV) | The air outlets were located on the side wall with a height of 1.2 m [ | Controlled zone in the occupied area [ | Low energy consumption and better air quality [ | Strong blowing feeling in the head and large temperature difference between the head and feet [ |
| Wall attached ventilation (WAV) | High momentum air supply was attached to the wall and sprayed downward [ | The basic mechanism was extended Coanda effect, which made jet quickly spread and adhere to the floor [ | High ventilation efficiency and low draft sensation [ | Hot air floats off the floor [ |
| Protected occupied zone ventilation (POV) | Divided indoor environment into protected and polluted area by jet to isolate high-concentration pollutant airflow [ | Used a low turbulence plane jet to separate an office environment into a few subzones [ | Could be combined with other ventilation methods to improve the removal rate of pollutants [ | The application scenario was limited [ |
Simulation conditions of DV.
| Season | Supply air speed (m/s) | Supply air temperature (°C) | Wall temperature (External wall/Internal wall/Ceiling/Floor, °C) |
|---|---|---|---|
| Summer | 0.8 | 18 | 29.9/27.2/26.6/27.4 |
| Winter | 0.8 | 26 | −3.2/12.5/14.5/14.5 |
Fig. 6Temperature field of DV.
Fig. 7Laminar airflow (LAF)/Piston ventilation (PIV) [50].
Fig. 8Schematic diagram of DV for ice rink [52].
Fig. 9Five different air personalized terminal types [54,55].
Comparation of different unsteady ventilation modes.
| Modes | Layouts | Characteristics | Advantages | Disadvantages |
|---|---|---|---|---|
| Dynamic personalized ventilation (DPEV) | A small amount of clean air was gently delivered to personnel breathing zone. | Users could freely adjust and improve the quality of intake air. | Reduced the inhaled air pollutants and unnecessary cooling or heating load. | Unconducive for moving occupants and required a background ventilation system. |
| Pulsating ventilation (PUV) | Changed control rules of cross flow fan to generate simulated natural wind. | Fresh air was supplied periodically following a predetermined dynamic trend. | Improved the indoor air quality and increased comfort in the personnel area. | Indoor air velocity sometimes was low, so the thermal comfort might not be guaranteed. |
| Intermittent ventilation (IV) | A periodic on and off operation method was introduced. | Supplied high speed and intermittent airflow to occupied zone. | Improved convective performance, elevated room temperature and reduced energy consumption. | The supply air amount was small and might not meet the requirement. |
| Wearable device ventilation (WDEV) | Used evaporative cooling and/or ventilation fans to control the skin heat loss. | The ambient air flowed from the bottom and left at upper ventilation holes. | Could be attached to the body to provide protection anywhere. | The sensing, driven and controlling technique were complex. |
Fig. 10Control flowchart of PUV.
Fig. 11Air velocity comparison for different ventilation strategies [68].
Fig. 12IPMV and IPPD for pulsating and steady ventilations [68].
Fig. 13Parameters to characterize an intermittent ventilation [71].
Fig. 14The ventilation jacket with fans and openings at the back site [74].
Fig. 15Components and structures of the hybrid vest [75].
Specific requirements of thermal comfort in different standards.
| Standard | GB/T 18883-2020 | GB 50736–2012 | ISO 7730–2005 | ISO 17772–2017 | EN 16798-1-2019d | ASHRAE 62.1–2019 | ASHRAE 55-2017 |
|---|---|---|---|---|---|---|---|
| Temperature (Summer, °C) | 22–28 | Ⅰ: 24-26 | A: 24.5 ± 1.0 | Ⅰ: 25.5 Ⅱ: 26 Ⅲ: 27 Ⅳ: 28 | Ⅰ: 25.5 | – | – |
| Temperature (Winter, °C) | 16–24 | Ⅰ: 22-24 | A: 22 ± 1.0 | Ⅰ: 21 | Ⅰ: 21 | – | – |
| Vertical temperature difference (°C) | – | – | A: <2 | Ⅰ: 2 | Ⅰ: 2 | – | Standing: 4 °C Sitting: 3 °C |
| Humidity (Summer, %) | 40–80 | Ⅰ: 40-60 | 60 | 60 | 60 | 65 | 0.012 kg-H2O/kg-dry air |
| Humidity (Winter, %) | 30–60 | Ⅰ: ≥30 Ⅱ: | 40 | 40 | 40 | 65 | 0.012 kg-H2O/kg-dry air |
| Air speed (Summer, m/s) | 0.3 | Ⅰ: ≤0.25 Ⅱ: ≤0.3 | A:0.12 | Ⅰ: 0.12 Ⅱ: 0.19 | Ⅰ:0.12 | – | – |
| Air speed (Winter, m/s) | 0.2 | Ⅰ: ≤0.2 Ⅱ: ≤0.2 | A: 0.1 | Ⅰ: 0.1 | Ⅰ: 0.1 | – | – |
Notes.
Ⅰ: 0.5≤PMV≤0.5; PPD≤10%. Ⅱ: 1≤PMV < −0.5, 0.5
A: 0.2
Ⅰ: 0.2
Wind speed requirement in ASHRAE 55–2017.
| Average air speed, m/s (fpm) | Humidity ratio | Met | Clo |
|---|---|---|---|
| <0.20 (40) | <0.012 kg-H2O/kg-dry air | 1.0–1.3 | 0.5–1.0 |
| <0.20 (40) | All | 1.0–2.0 | 0–1.5 |
| >0.20 (40) | All | 1.0–2.0 | 0–1.5 |
Specific requirements of air quality in different standards.
| Pollutants | GB/T | ISO | EN | ASHRAE |
|---|---|---|---|---|
| SO2 | 0.5 (mg/m3)/1 h | 10 min: 500 μg/m3 | 10 min: 500 μg/m3 | 1 h: 75 ppb |
| NO2 | 0.24 (mg/m3)/1 h | 1 h: 200 μg/m3 | 1 h: 200 μg/m3 | 1 h: 100 ppb |
| CO | 10 (mg/m3)/1 h | 15 min: 100 mg/m3 | 15 min: 100 mg/m3 | 1 h: 40 mg/m3 |
| CO2 | 0.1%/24 h | – | – | – |
| NH3 | 0.2 (mg/m3)/1 h | – | – | – |
| O3 | 0.16 (mg/m3)/1 h | 8 h: 100 mg/m3 | 8 h: 100 mg/m3 | 8 h: 0.007 ppm |
| HCHO | 0.1 (mg/m3)/1 h | 100 | 100 | – |
| C6H6 | 0.11 (mg/m3)/1 h | <5 mg/m3 | <5 mg/m3 | – |
| C7H8 | 0.2 (mg/m3)/1 h | – | – | – |
| C8H10 | 0.2 (mg/m3)/1 h | – | – | – |
| Benzopyrene | 1 (mg/m3)/1 h | – | – | – |
| PM10 | 0.15 (mg/m3)/24 h | 24 h: 50 μg/m3 | 24 h: 50 μg/m3 | 24 h: 150 μg/m3 |
| TVOC | 0.6 (mg/m3)/2 h | 1000 | 1000 | – |
| Total number of colonies | 2500 cfu/m3 | – | – | – |
| Radon | 400 bq/m3/per year | 100 bq/m3 | 100 bq/m3 | – |
Notes.
Low emitting products for low polluted buildings.
Very low emitting products for very low polluted buildings.
The average value.
Thermal sensation evaluated by RWI index and ASHRAE Standard.
| Thermal sensation | ASHRAE thermal sensory scale | RWI index value |
|---|---|---|
| Warm | 2 | 0.25 |
| Slightly warm | 1 | 0.15 |
| Comfortable | 0 | 0.08 |
| Slightly cool | −1 | 0 |
Fig. 16The chilled ceiling system assisted by an intermittent PEV [125].
Fig. 17Layout of the SV combined with pulsating air supply [70].
Fig. 18Temperature change pattern under intermittent operation mode [135].
Fig. 19Pictures of air jet diffusers and visualization operation [72].
Comparison of thermal comfort for different ventilation modes.
| Contrast type | Application scenarios | Thermal comfort | |||||
|---|---|---|---|---|---|---|---|
| PD | PMV | PPD | Draft rate | Floor-to-ceiling temperature difference | Overall thermal sensation and comfort | ||
| MV vs. DV | Office | DV<10%, MV<20% [ | – | DV<20%, | Summer: DV < MV | – | – |
| Classroom | DV<10%, MV<20% [ | – | DV<20%, | – | – | – | |
| Retail shop | DV<10%, MV<20% [ | – | DV<20%, | – | – | – | |
| Industrial workshop | DV>25%, MV>25% [ | – | DV<20%, | – | – | – | |
| Aircraft cabin | MV<1%, DV: 3%–8% [ | – | – | MV: 10%–40%, | – | – | |
| MV vs. DV vs. SV | Office | – | – | – | MV and DV:< 20%, | – | SV was 10% better than MV [ |
| IJV vs. MV | Spaces with occupants moving frequently | – | – | – | – | IJV was 60% less than MV [ | – |
| WAV vs. MV | Office | – | Similar [ | – | – | – | – |
| POV vs. MV | Office | – | – | – | MV:100%, | – | – |
| UFAD vs. MV | Open-plan office room | – | UFAD was 45% better than MV [ | – | – | – | – |
| MV vs. DV vs. IV | Classroom | – | MV: 1.31, | MV: 45%, | – | – | – |
| SV vs. PUV + SV | Office | – | – | SV: 16%, | SV: 34%, | – | – |
| SSV vs. PUV | Office | – | – | SSV: 36.5% [ | – | – | – |
Comparison of air quality and virus spread control for different ventilation modes.
| Contrast type | Application scenarios | Air quality and virus spread control | ||||||
|---|---|---|---|---|---|---|---|---|
| Infection risk | Mean age of air | Concentration of contaminants | Protection efficiency | Contaminant removal effectiveness | HCHO/PM | Air change efficiency | ||
| MV vs. DV | Office | – | DV < MV [ | – | – | – | – | – |
| Aircraft cabin | MV: 0.2/0.07/0.02, DV: 0.05/0.02/0 (No mask/Mask worn by index person only/Masks worn by all passengers) [ | Did not differ greatly [ | – | – | – | – | – | |
| MV vs. IJV | Large space (10 m high) or spaces with occupants moving frequently | – | IJV was 37%–47% less than MV [ | – | – | – | – | – |
| MV vs. WAV | Office | – | – | WAV was 15%–47% less than MV [ | – | – | – | – |
| MV vs. POV | Office | – | – | – | POV was 14%–50% higher than MV [ | – | – | – |
| MV vs. SV | Office | – | – | – | – | SV was 22.6% higher than MV [ | – | – |
| MV vs. UFAD | Open-plan office room | – | UFAD was 28.3% less than MV [ | – | – | – | – | – |
| MV vs. IV | Office or classroom | – | – | – | – | – | – | MV: 43.7%–49.7%, |
| DV vs. IV | Office | – | – | – | – | – | – | DV: 56.1%, |
| SSV vs. PUV | Residence | – | – | – | – | – | Peak pollutant concentration: PUV was 31% less. | – |