A field-scale validation is summarized comparing the efficacy of commercially available stabilization amendments with the objective of mitigating per- and polyfluoroalkyl substance (PFAS) leaching from aqueous film-forming foam (AFFF)-impacted source zones. The scope of this work included bench-scale testing to evaluate multiple amendments and application concentrations to mitigate PFAS leachability and the execution of field-scale soil mixing in an AFFF-impacted fire-training area with nearly 2.5 years of post-soil mixing monitoring to validate reductions in PFAS leachability. At the bench scale, several amendments were evaluated and the selection of two amendments for field-scale evaluation was informed: FLUORO-SORB Adsorbent (FS) and RemBind (RB). Five ∼28 m3 test pits (approximately 3 m wide by 3 m long by 3 m deep) were mixed at a site using conventional construction equipment. One control test pit (Test Pit 1) included Portland cement (PC) only (5% dry weight basis). The other four test pits (Test Pits 2 through 5) compared 5 and 10% ratios (dry weight basis) of FS and RB (also with PC). Five separate monitoring events included two to three sample cores collected from each test pit for United States Environmental Protection Agency (USEPA) Method 1315 leaching assessment. After 1 year, a mass balance for each test pit was attempted comparing the total PFAS soil mass before, during, and after leach testing. Bench-scale and field-scale data were in good agreement and demonstrated >99% decrease in total PFAS leachability (mass basis; >98% mole basis) as confirmed by the total oxidizable precursor assay, strongly supporting the chemical stabilization of PFAS.
A field-scale validation is summarized comparing the efficacy of commercially available stabilization amendments with the objective of mitigating per- and polyfluoroalkyl substance (PFAS) leaching from aqueous film-forming foam (AFFF)-impacted source zones. The scope of this work included bench-scale testing to evaluate multiple amendments and application concentrations to mitigate PFAS leachability and the execution of field-scale soil mixing in an AFFF-impacted fire-training area with nearly 2.5 years of post-soil mixing monitoring to validate reductions in PFAS leachability. At the bench scale, several amendments were evaluated and the selection of two amendments for field-scale evaluation was informed: FLUORO-SORB Adsorbent (FS) and RemBind (RB). Five ∼28 m3 test pits (approximately 3 m wide by 3 m long by 3 m deep) were mixed at a site using conventional construction equipment. One control test pit (Test Pit 1) included Portland cement (PC) only (5% dry weight basis). The other four test pits (Test Pits 2 through 5) compared 5 and 10% ratios (dry weight basis) of FS and RB (also with PC). Five separate monitoring events included two to three sample cores collected from each test pit for United States Environmental Protection Agency (USEPA) Method 1315 leaching assessment. After 1 year, a mass balance for each test pit was attempted comparing the total PFAS soil mass before, during, and after leach testing. Bench-scale and field-scale data were in good agreement and demonstrated >99% decrease in total PFAS leachability (mass basis; >98% mole basis) as confirmed by the total oxidizable precursor assay, strongly supporting the chemical stabilization of PFAS.
Historical discharges
of aqueous film-forming foam (AFFF), primarily
at former fire training areas (FTAs), resulted in per- and polyfluoroalkyl
(PFAS) source zones within vadose zone soils and shallow groundwater.[1−8] Studies have demonstrated that PFAS retained in FTA source zone
soils can sustain groundwater plumes potentially for decades.[9−12] While authoritative methodologies to determine and quantify the
source-strength that account for the relevant retention and transformation
processes are still very much actively being researched by the academic
community,[13] many of these AFFF-impacted
source zones will likely require degrees of active management to comply
with increasingly conservative groundwater criteria. Therefore, cost-effective
management strategies that specifically target vadose zone sources
and shallow groundwater are urgently needed.Currently, multiple
technologies are used to consolidate large
volumes of marginally contaminated matrices into small, highly concentrated
volumes for energy-intensive destruction.[14] Commercially available technologies to address AFFF-impacted source
zones, however, are limited[15−20] to in situ stabilization[21] and excavation
with offsite disposal/destruction or onsite management using soil
washing[20] or thermal desorption.[22] Ex situ technologies require waste handling,
disposal in a landfill, or separating the PFAS from the soil in favor
of adsorption/consolidation technologies relevant to liquids. Once
concentrated in a liquid, PFAS destruction challenges remain.[23,24] PFAS has shown recalcitrance to chemical mineralization,[25−27] and no complete biodegradation mechanism has been universally established.[28] Incomplete destruction and unknown intermediates
associated with incineration of PFAS in liquid waste have been discussed.[23,24] Hydrothermal alkaline treatment and super critical water oxidation,[29,30] sonochemical degradation,[31] electrochemical
oxidation,[32] and advanced reduction processes
(e.g., nonthermal plasma,[33] electron beam,[34] and/or ultraviolet-activated catalysts and/or
reductants[35,36]) show promise for PFAS destruction
at the end of a treatment train.For in situ applications, the
injection of an adsorbent or complexing
agent has been evaluated.[37−42] Injected adsorbents are relevant to mitigating PFAS migration within
the saturated zone with much emphasis on subsurface distribution.
For AFFF-impacted source zones (i.e., vadose zone soils), considerable
PFAS mass is likely present within the near surface due to retention
associated with organic matter, mineral phases, and the gas–liquid
interface.[3−5,12,43−50] This renders PFAS within the vadose zone inaccessible to adsorbents
injected within the saturated zone, thus uniquely challenging injected
adsorbents to adequately mitigate PFAS leachability.In situ
stabilization and solidification (S/S) is a well-established
source zone technology for numerous constituents within saturated
and unsaturated impacted media.[51−56] Stabilization uses a chemical amendment to reduce and/or eliminate
contaminant leaching. Solidification encapsulates soils and decreases
the surface area exposed to infiltrating water. S/S is expected to
be a cost-efficient and sustainable management strategy for AFFF-impacted
source zones. As S/S homogenizes geological anisotropy during amendment
addition via soil mixing, it facilitates access to PFAS associated
with low permeable strata or adsorbed at phase interfaces.[57,58] Amendments are not yet available to destroy PFAS, and the current
focus is the mitigation of PFAS leaching. S/S has been shown to decrease
PFAS leaching from AFFF-impacted soils.[21,59−64] Relevant studies have included laboratory-based trials to evaluate
the efficacy of stabilization to decrease PFAS leachability from FTA-specific
or spiked soils[21,59] and to simulate weathering under
controlled conditions.[60−64] These studies consistently demonstrated decreases in PFAS leachability
of greater than 99% (mass basis) using stabilizing amendments such
as biochar, activated carbon, montmorillonite, compost soil, pulverized
zeolite, chitosan, layered double hydroxides (LDHs), aluminum hydroxide,
bentonite, and calcium chloride.[21,59−64] Weathering under field conditions represents a gap in understanding
the long-term performance of S/S for PFAS[60,61] and is the motivation of this study.A standardized method
to evaluate the leaching potential of PFAS
from solid matrices is under development to account for the unique
properties of PFAS. Most of the PFAS-relevant S/S studies equilibrated
stabilizing amendments with AFFF-impacted soil at a prescribed soil-to-liquid
ratio under agitation and then analyzed the liquid for PFAS after
a solid–liquid separation. Kabiri and McLaughlin[62] evaluated USEPA Method 1314 (Leaching Environmental
Assessment Framework [LEAF])[65] and the
Australian Standard Leaching Procedure[66] to represent a practical leachability assessment. The LEAF methods
involve subjecting a predetermined mass of a solid material at a specified
liquid-to-surface-area ratio to successive leaches over time. LEAF
presents a commercially available methodology to realistically evaluate
the leachability of PFAS from solid matrices without imposing biases,
such as particle size reduction[65] or acidic
leaching conditions.[67]The objective
of this study was to evaluate S/S under field conditions
at an AFFF-impacted source zone to understand the magnitude and longevity
of decreased PFAS leachability. Specific technical objectives included
a comparison of commercially available stabilization amendments and
an evaluation of how the concentrations of PFAS in leachate from the
stabilized test pits changed after more than 2 years using a sequential
leaching procedure. To the best of our knowledge, this study provides
the first field-scale evaluation of S/S as a management strategy for
an AFFF-impacted source zone.
Results and Discussion
Baseline Characterization
Results
Soil samples collected
in the vicinity of the test pits had an average percent solids of
approximately 82.5% (n = 30 and σ = 3.1%),
with greater than 90% characterized as coarse sands per classical
geological description, the Udden-Wentworth grain size classification
system, and grain size distribution per American Society for Testing
and Materials (ASTM) D422.Of the polyfluorinated compounds
analyzed, 8:2-fluorotelomer sulfonic acid (FTSA) and perfluorooctane
sulfonamide (PFOSA) were the only compounds quantified above analytical
detection limits (Table S1). Detections
of 8:2-FTSA ranged from 3.3 J micrograms per kilogram (μg/kg)
to 33.6 μg/kg (n = 12; μ = 10.5; and
σ = 9.1). Detections of PFOSA ranged from 0.66 J to 41.6 μg/kg
(n = 19; μ = 7.6; and σ = 10.3). For
all but two results, the highest detections of 8:2-FTSA and PFOSA
were found in the samples at 1.5 m below the ground surface (m bgs).
These polyfluorinated compounds will not be discussed further as postsoil
mixing performance monitoring data represent post total oxidiziable
precursor (TOP) assay data, but the data are consistent with observations
in the literature of polyfluorinated compounds being associated with
shallow soils. 8:2-FTSA would be expected to transform into similar-
or shorter-chain perfluorocarboxylic acids,[68−70] (PFCAs) and
PFOSA is a known precursor to perfluorooctane sulfonate[71] (PFOS).The frequency of perfluoroalkyl
acid (PFAA) results above analytical
detection limits in soils deemed relevant for this discussion was
defined as more than 90% of the total samples (n =
30). Those PFAAs classified as infrequently detected include C9 and
C10 perfluorosulfonic acids (PFSAs) and C11 through C14 PFCAs. Considering
postsoil mixing performance monitoring data continued these observations
of infrequently detected PFAAs, these PFAAs are not discussed further
(Table S2). Those PFAAs classified as frequently
detected include C4–C8 PFSAs and C4–C9 PFCAs. However,
on average, perfluorohexane sulfonic acid (PFHxS), PFOS, perfluorohexanoic
acid (PFHxA), and perfluorooctanoic acid (PFOA) comprised 98.2% of
the total PFAS reported (PFHxS and PFOS comprised 95.7%; Table S2).Groundwater samples were analyzed
post TOP assay, and therefore,
no polyfluorinated compounds were detected (Table S3). Similar to the analytical results of the soil, PFHxS,
PFOS, PFHxA, and PFOA represented an average of 89.9% of the total
PFAAs detected in groundwater. The observation of the most detected
PFAAs represented by PFHxS, PFOS, PFHxA, and PFOA was continued through
the postsoil mixing performance monitoring data, and therefore, they
are the focus of the rest of the discussion.The spatial variation
of observed PFAS magnitudes is indicative
of the difficulty to predict the nature of source zone FTAs due to
the release mechanism (i.e., surface infiltration) and varied historical
release. While not definitive, the larger percentage of PFHxS and
PFOS, as well as the frequent detection of PFOSA, may indicate an
electrochemical fluorination as the source of historical AFFF, which
is anticipated to have less polyfluorinated compounds.[49,71]No separate phase hydrocarbon was encountered, and the fraction
of organic carbon (fOC) and target analyte
list (TAL) metals were not confounding (i.e., not at such high concentrations
that they would influence PFAS adsorption). There are reports in the
literature of adsorptive retardation being correlated with natural
organic matter [represented by total organic carbon (TOC)] and clays
(i.e., metal oxide surfaces).[5,44,72] The fOC was quantified to be between
approximately 0.002 and 0.006 (n = 10; μ =
0.003; and σ = 0.001), a moderate concentration comparatively.[73] TAL metal analysis suggests that aluminum, calcium,
iron, magnesium, and sodium comprised 99.2–99.9% (n = 10; μ = 99.7%, and σ = 0.3%) of the detected metals
and that calcium represented 63.8–96.4% (n = 10; μ = 85.4%, and σ = 12.9%). The divalent cationic
speciation of calcium presents an intriguing possibility to serve
as an electrostatic linkage between anionic functional groups common
to PFAAs and is theorized to promote the formation of supramolecular
structures.[74] Aluminum and iron could also
represent charged surfaces (cationic or anionic), which could also
promote electrostatic adsorption.
Laboratory Leaching Analysis
Batch
Testing
The addition of RemBind (RB) and FLUORO-SORB
(FS) resulted in approximately 99.3 and 99.5% decreases (mass basis)
in the sum of detected aqueous PFAS in comparison to the soil-only
control, respectively, regardless of the stabilizer ratio (Table S4), and is consistent with other studies.[21,59−64] In comparison to these larger and consistent decreases, observed
decreases of 35.4–83.0% (mass basis) for LDH and the proprietary
sealant were eliminated from consideration and are not discussed further.
The batch testing identified RB and FS as the field-scale stabilizers.Within the soil-only control, PFOS, PFHxS, and PFHxA comprised
91.8% of the sum of quantifiable PFAS, which is consistent with the
characterization results. A noteworthy observation is the difference
in the magnitude of detected PFAS in groundwater [μ = 1192.4
ng per liter (ng/L); n = 2; and σ = 1.26] versus
that of the soil-only control (μ = 15,855.7 ng/L; n = 2; and σ = 361.5). The difference in magnitude is likely
attributable to the liquid extractant accessing a greater surface
area of the soil over the 48 h agitation for the soil-only control.
PFHxA was observed to leach and increase the leachate concentration
by greater than 400% in the soil-only control, which likely represents
desorbed/dissolved polyfluorinated compounds subsequently transformed
into PFHxA via the TOP assay.Specifically for PFHxS, PFOS,
PFHxA, and PFOA, leachability on
a mass basis was observed to decrease by greater than 99% (Figure ), though detectable
concentrations were observed in both RB and FS trials.
Figure 1
Percentage of PFHxS,
PFOS, PFHxA, and PFOA leached for a soil-only
control in comparison to treatment conditions with 5, 10, and 20%
dry wt FS and RB, respectively, in batch testing.
Percentage of PFHxS,
PFOS, PFHxA, and PFOA leached for a soil-only
control in comparison to treatment conditions with 5, 10, and 20%
dry wt FS and RB, respectively, in batch testing.PFHxS and PFOS were observed in multiple RB and FS trials at concentrations
ranging from 6.3 to 61.5 ng/L, with no discernible trends with respect
to the stabilizer ratio. PFHxA was detected in all but one RB and
FS trials at concentrations ranging from 7.8 to 29.6 ng/L. There was
no discernible trend associated with respect to the RB ratio, but
PFHxA was observed to decrease slightly with higher FS ratios. These
detections represent sizable decreases in comparison to the soil-only
control (PFHxS: n = 2; μ = 2690 ng/L; and σ
= 20; PFOS: n = 2; μ = 10,010 ng/L; and σ
= 290; and PFHxA: n = 2; μ = 1860 ng/L; and
σ = 60).Both RB and FS demonstrated greater than 40%
decreases in perfluorobutanoic
acid (PFBA) leachability; however, PFBA proved to be the most difficult
PFAA to stabilize. PFBA was detected in multiple RB and FS trials
at concentrations ranging from 23.5 to 103 ng/L, with no discernible
trend with respect to the stabilizer ratio. PFBA is characterized
by only three fluorine-saturated carbons within its alkyl chain and
often presents a challenge to adsorptive media (both hydrophobic and
electrostatic adsorption) given its miscibility.[75,76] Batch-testing PFAS analysis was performed post TOP assay, and the
TOP assay is expected to convert polyfluorinated compounds into PFCAs.[72] Consistent detections of PFHxA and PFBA for
RB and FS trials could, however, suggest that polyfluorinated compounds
were less effectively stabilized.Given the apparent decreases
in PFAS leachability associated with
the addition of RB and FS seemingly insensitive to the stabilizer
ratio, the 20% wt ratio was eliminated from consideration based on
cost. The 5 and 10% wt stabilizer ratios for RB and FS were selected
for the intact core testing and the field-scale soil mixing.
Intact
Core Testing
5% wt Portland cement (PC) was
determined to develop adequate unconfined compressive strength (UCS)
as confirmed by 28-day peak stress testing (approximately 415 kPa)
and a hydraulic conductivity of 6 × 10–5 cm
per second (cm/s). While 5% wt addition to FS trials developed a similar
UCS, RB trials did not, and therefore, higher percentages of PC were
necessary in RB trials (Tables S5 and S6). A lower UCS in the presence of RB used for this work was observed
previously.[60] The added PC corresponded
to an order of magnitude lower hydraulic conductivity (10–6 cm/s vs 10–5 cm/s for the PC control and FS trials).All PFASs (post TOP assay) within the T48h and T63d leachates (see Materials and Methods) were below analytical detection
limits for RB and FS trials (Table S7).
Perfluorononanoic acid (PFNA) was consistently detected in pre TOP
assay only T63d leachate at concentrations ranging from 3.95 to 11
ng/L. These detections are likely associated with laboratory bias
(PFNA detection in the laboratory blank sample of 9.7 ng/L) as PFNA
was not detected in analysis post TOP assay.T48h leaching concentrations
for the 5% PC control were at least
1 order of magnitude lower than batch testing results for the soil-only
control, suggesting that the PC may have mitigated some PFAS leachability,
if only by decreasing the hydraulic conductivity. Of the six distinct
PFAAs detected in the pre TOP assay, T48h leachate concentration for
the 5% PC control, PFHxS, PFOS, PFHxA, and PFOA represented 90% of
the sum of PFAAs. Increases in PFBA and PFHxA in PFAS analysis post
TOP assay again indicate some degrees of leachable polyfluorinated
compounds. Other observations of leachable polyfluorinated compounds
include 6:2-FTSA (13.1 ng/L) and PFOSA (14.9 ng/L) detected in PFAS
analysis pre TOP assay T48h leachate data from the 5% RB trial and
the 10% FS trial, respectively. For all RB and FS trials, pre and
post TOP assay T48h and T63d leaching concentrations for PFHxS, PFOS,
PFHxA, and PFOA were below analytical detection limits.
Field-Scale
Leaching Analysis
The T48h leaching results
from all sampling events (SEs) are presented for PFHxS, PFOS, PFHxA,
and PFOA (post TOP assay) per mass of soil leached, where the concentration
leached from soil has been corrected to remove the added amendment
mass (Figure ). Test
Pit 1 is the 5% PC control, Test Pit 2 is 5% PC/10% FS, Test Pit 3
is 5% PC/5% FS, Test Pit 4 is 15% PC/10% RB, and Test Pit 5 is 10%
PC/5% RB and SEs were conducted 5, 12, 16, 22, and 28 months postsoil
mixing.
Figure 2
Scatter plots of all T48h leachate results for PFHxS, PFOS, PFHxA,
and PFOA from Test Pits 2 through 5 vs Test Pit 1. Data are presented
as nanomole PFAA per kg soil. The 1:1 line is the Test Pit 1 plotted
against Test Pit 1. One-half of the analytical detection limit was
used when results were below the analytical detection limits.
Scatter plots of all T48h leachate results for PFHxS, PFOS, PFHxA,
and PFOA from Test Pits 2 through 5 vs Test Pit 1. Data are presented
as nanomole PFAA per kg soil. The 1:1 line is the Test Pit 1 plotted
against Test Pit 1. One-half of the analytical detection limit was
used when results were below the analytical detection limits.The data demonstrate comparative decreases in PFHxS,
PFOS, PFHxA,
and PFOA leachability from Test Pits 2 through 5 compared to Test
Pit 1 under relevant field-scale weathering conditions for greater
than 2 years. The sustained decreases in PFAS leachability via the
T48h leachate (post TOP assay) suggest that S/S could be a pragmatic
approach to manage AFFF-impacted source zones. An apparent exception
to this observation is PFHxA from Test Pits 2 and 3 for two data points
from SE 12mo; however, these data are all below analytical detection
limits (Table S8), and these data points
are suspected to be unrepresentative of Test Pit 1.Over the
28-month monitoring period, the summation of PFAS in the
T48h leachate from Test Pit 1 ranged from 195.7 to 15,645.7 ng/L (n = 13; μ = 5436.4 ng/L; and σ = 3842). The
average SE 12mo T48h leachate from Test Pit 1 is 95.7% different than
the average T48h leachate from Test Pit 1 for all other SEs. Geochemical
indicator parameters [pH and specific conductivity (SC)] collected
from sample cores TP-1-4 and TP-1-5 (Figure S1 and Table S9) suggest lower average pH and SC when compared
to the other 10 sampling grids (data not shown). The data from SE
12mo are not discarded as outliers and rather serve as a demonstration
of the importance of homogeneous mixing for S/S to be a successful
long-term PFAS source zone management strategy. The comparatively
low PFAS result of SE 12mo is contrasted with the comparatively high
PFAS result of SE 28mo, where the T48h leachate concentration from
TP-1-10 (Figure S1 and Table S9) was 15,645.7
ng/L, which was higher than any other total PFAS result from SEs and
is comparable to the soil-only control (n = 2; μ
= 15,855.7; and σ = 361.5) from the batch testing.The
PFASs detected in the T48h leachate from Test Pit 1 suggest
that PC alone was marginally effective in comparison to the soil-only
control from batch testing at mitigating PFAS leachability (Figure ).
Figure 3
Percentage of PFHxS,
PFOS, PFHxA, and PFOA leachability observed
after SE 5mo, 12mo, 16mo, 22mo, and 28mo after soil mixing/stabilizer
amendment addition. The soil-only control from batch testing data
is repeated for comparison purposes. The percentage leached is calculated
using one-half of the analytical detection limit when results were
below the analytical detection limits.
Percentage of PFHxS,
PFOS, PFHxA, and PFOA leachability observed
after SE 5mo, 12mo, 16mo, 22mo, and 28mo after soil mixing/stabilizer
amendment addition. The soil-only control from batch testing data
is repeated for comparison purposes. The percentage leached is calculated
using one-half of the analytical detection limit when results were
below the analytical detection limits.PFHxS, PFOS, PFHxA, and PFOA represented 78.3% (n = 13 and σ = 10.9%) of the detected PFAS in T48h leachate
from Test Pit 1, which is comparatively lower than the characterization
and laboratory testing. Leaching data associated with Test Pit 1 show
consistent detections of PFCAs [specifically, PFBA, perfluoropentanoic
acid (PFPeA), and perfluoroheptanoic acid (PFHpA)] throughout the
SEs, which represented 57.5% (n = 13 and σ
= 13.8%) of the detected PFAS. The higher percentage of PFCAs detected
in post TOP assay T48h leachate from Test Pit 1 is likely an indication
of polyfluorinated compound leachability.For Test Pit 2 (5%
PC/10% FS), all T48h leachate concentrations
of PFHxS, PFOS, and PFOA were below analytical detection limits (n = 12). Detected PFAAs included PFBA, PFPeA, and PFHxA,
suggesting a potential for polyfluorinated compounds to leach from
Test Pit 2; however, the concentrations were an order of magnitude
less than those from Test Pit 1 (specifically for PFPeA and PFHxA),
demonstrating some degrees of mitigation of such leaching. The highest
magnitude PFAA detected was PFHxA (n = 10; μ
= 216.3 ng/L; and σ = 96.9) and was significantly less than
Test Pit 1 [one-tailed Student t-test (p = 0.0002)]. The sum of all detected PFAS concentrations in the T48h
leachate represents 95.7 and 98.5% decreases in detectable PFAS leachability
(mass basis) as compared to Test Pit 1 and the soil-only control,
respectively.For Test Pit 3 (5% PC/5% FS), there were detections
of PFOS (31
ng/L) and PFOA (15 J and 127 ng/L) during SE 5mo and SE 22mo. There
were no detections of PFHxS above analytical detection limits. Like
Test Pit 2, PFCAs (PFBA, PFPeA, and PFHxA) were detected, with PFHxA
being of the largest magnitude (n = 13; μ =
127 ng/L; and σ = 169). PFHxA detected in T48h leachate from
Test Pit 3 was significantly less than that from Test Pit 1 [one-tailed
Student t-test (p = 0.00002)]. T48h
leachate results from TP-3-1 (Figure S1 and Table S9) collected during SE 5mo had the greatest number of PFAA
detections (6), represented the only PFOS detection, and represented
the highest PFBA, PFHxA, and PFOA detections. Geochemical indicator
parameters (pH and SC) from sample core TP-3-1 were comparatively
lower than those from the other 15 samples (TP-3-2–TP-3-12,
plus duplicates; data not shown). The summation of the detected PFAAs
from TP-3-1 was 1341 ng/L compared to an average of 122 ng/L for all
other samples (n = 12 and σ = 72). These observations
may suggest that the location represented by sample TP-3-1 was poorly
mixed. The results from TP-3-1 and the J-flagged estimate of PFOA
during SE 22mo represent the only observed differences between the
10 and 5% wt FS stabilizer ratios. If the TP-3-1 sample represents
poor soil mixing and FS distribution, this would suggest that there
is no added benefit between 5 and 10% wt stabilizer ratios, and further
optimization of lower-stabilizer ratios may be possible. The sum of
all detected PFAS concentrations in the T48h leachate represents 96.7
and 98.9% decreases in detectable PFAS leachability (mass basis) as
compared to Test Pit 1 and the soil-only control, respectively.For Test Pits 4 and 5 (15% PC/10% RB and 10% PC/5% RB), all PFAAs
in T48h leachate were below analytical detection limits except for
SE 28mo results from Test Pit 5, which demonstrated J-flagged detections
of PFPeA and PFHxA. There is insufficient data to reliably infer if
the SE 28mo detections of PFCAs represent a similar potential for
polyfluorinated compound leachability; however, the similarity of
the detected PFAAs to Test Pits 1 through 3 seems to suggest this.
This would represent the only minor difference between 5 and 10% wt
RB stabilizer ratios, suggesting that there was no added benefit to
10% versus 5% wt for this specific demonstration study. With respect
to Test Pit 4, 100.0% decrease in detectable PFAS leachability (mass
basis) was observed as compared to Test Pit 1 and the soil-only control.
With respect to Test Pit 5, the sum of all detected PFAS concentrations
represents 99.9 and 100.0% decreases in detectable PFAS leachability
as compared to Test Pit 1 and the soil-only control, respectively.
Attempted Mass Balance
The attempted mass balance is
presented in Table S10, and masses are
calculated from PFAS analysis performed post TOP assay. The attempted
mass balance was performed on sample cores collected during SE 12mo
and is a comparison of the soil analysis for PFAS prior to leaching
(M1) to the summation of the soil analysis
for PFAS after leaching (M3) and a composite
analysis of the nine sequential leaches (M2).The differences in M1 and M3 do not appear to be entirely associated with
PFAS leaching from the soil. The differences (M3 – M1) range from −50,301.7
to 27,542.5 ng and are far greater in magnitude than any M2 reported for Test Pits 2 through 5. This may suggest
that analytical limitations could better explain the observed differences.
The PFASs were extracted from soil using a triple methanol rinse,
and sonication or other extraction methods may have been more appropriate.[77] While this challenges the precise interpretation
of the mass balance, a comparison on an order of magnitude basis showing
105 ng total PFAS associated with the pre- and postleached
soil versus 102–103 ng total PFAS observed
in the composite leachates strongly suggests that chemical stabilization
decreases PFAS leachability into groundwater as well as extractability
with methanol rinse. The calculated percentage of PFHxS, PFOS, PFHxA,
and PFOA leachability demonstrates that in comparison to the soil-only
control from the batch testing, stabilizers reduced the leachability
of these PFAAs (Figure ).The magnitude of the PFAS mass associated with Test Pit
1 is most
likely an underrepresentation, based on the previously discussed differences
in T48h leaching results in comparison to other SEs. The mass of PFAS
leaching from Test Pit 1 based on the T48h leaching results from SEs
5mo, 16mo, 22mo, and 28mo ranges from 1474.9 to 6430.4 ng (n = 11; μ = 2623 ng; and σ = 1401.8). This range
and average of T48h leachate mass are similar to Test Pit 1 M1 and M3; however,
based on data from the other test pits, they should not be similar.
The mass of PFAS within the T48h leachate for Test Pits 2 through
5 from all SEs ranges from 43.7 to 583.5 ng (n =
52; μ = 114.5 ng; and σ = 84.6) and is 3–4 orders
of magnitude less than the corresponding M1 and M3. Despite the underrepresented
magnitude of PFAS mass from Test Pit 1, the largest percent difference
(Table S10) between M1 and the summation of M2 and M3 is expected and consistent with the higher
T48h leachate concentrations observed during other SEs. The greatest
percent leaching being associated with Test Pit 1 is also expected
as only PC was added to this test pit, and a comparison of the percent
of PFAS leaching between Test Pit 1 and Test Pits 2 through 5 supports
that stabilization amendments influenced PFAS leachability.
Non-T48h
PFAS Leaching Evaluation
To evaluate any bias
imposed by using the T48h leachate, composite samples of the T2h–T24h
and T5d–T63d leaches were analyzed from Test Pits 1, 3, and
5 during SE 28mo (Table S11). These test
pits were selected because Test Pit 1 was the control and Test Pits
3 and 5 both represented the lowest stabilizer ratio (5% wt FS and
RB).The most notable PFAS leaching was observed in T2h–T24h
and T5d–T63d composites from Test Pit 1 and was predominantly
composed of PFHxS, PFOS, PFHxA, and PFOA. In comparison to the composite
leachate from the mass balance (detected PFAS ranging from 15.2 to
183 ng/L; Table S12), the concentrations
of detected PFAS within the T2h–T24h and T5d–T63d composite
leachates were more aligned with the expected results (10.2 J to 8890
ng/L). The associated leached PFAS masses for T2h–T24h, T48h,
and T5d–T63d from Test Pit 1 were approximately 7290 ng, μ
= 3192 ng (n = 3 and σ = 5574), and 48,815
ng, respectively. A PFAS mass leaching rate can also be approximated
based on the leaching durations of each composite (7290 ng/d for T2h–T24h,
3192 ng/d for T48h, and 800 ng/d for T5d–T63d). While these
are expected results given the skepticism of PC to facilitate chemical
stabilization, it does suggest that more PFASs leached from cores
collected from Test Pit 1 that were not adequately represented by
the T48h leachate.Composite leachates T2h–T24h and T5d–T63d
from Test
Pit 3 show detections of PFBA, PFHxA, and PFOS that are comparable
to the composite leachate from the mass balance. Similar PFAS leachability
over approximately 16 months provides some perspective that an equilibrium
was established at Test Pit 3, which is supportive of the long-term
leachability reduction associated with stabilization. The mass of
PFAS leached for Test Pit 3 specific to samples collected during SE
5 was approximately 199 ng in T2h–T24h, 159 ng in T48h, and
858 ng in T5d–T63d, with associated PFAS mass leaching rates
of 199, 159, and 14 ng/d, respectively.Composite leachates
T2h–T24h and T5d–T63d from Test
Pit 5 show estimated detections of PFBA and PFOS, which is comparable
to the composite leachate from the mass balance and implies a similar
observation of established equilibrium as Test Pit 3. The mass of
PFAS leached from Test Pit 5 specific to samples collected during
SE 5 was approximately 125 ng in T2h–T24h, 123 ng in T48h,
and 382 ng in T5d–T63d, with associated PFAS mass leaching
rates of 125, 123, and 6.3 ng/d, respectively.In comparison
to the composite leachate analysis from Test Pit
1, composite leachability results from Test Pits 3 and 5 are notably
less. This is an expected result due to the chemical stabilization
of the FS and RB and is consistent with the comparison of T48h leachate
data throughout the other SEs. This evaluation confirms that some
leachable PFASs were missed by selecting T48h leachate; however, the
magnitude of PFAS mass leaching rates between T2h–T24h, T48h,
and T5d–T63d suggests that T48h may suffice as a qualitative
comparison of PFAS leaching for the purposes of assessing the long-term
leachability decreases associated with stabilization.
Implications
and Future Work
The data presented here
strongly suggest that PFAS leaching can be mitigated via chemical
stabilization and should be considered as an effective alternative
for AFFF source zone management. While the stabilizers used here (FS
and RB) resulted in significant decreases in PFAS leachability compared
to a PC control, discrete sample data throughout the test pits reinforce
the importance of uniformity in stabilizer distribution via proper
soil mixing. Unpublished work to optimize the stabilizer ratio suggests
that lower ratios (e.g., 2–3% wt) may achieve targeted leachability
goals assuming homogeneous distribution. The stabilizer ratio can
be a considerable cost for larger AFFF source zones, and predesign
optimization testing is recommended. Where immediate load bearing
capacity is not necessary, mechanical compaction of stabilized soil
may eliminate the need for PC to further optimize costs. Homogeneous
distribution of stabilizers is essential to reliably optimize S/S
to balance the risk of PFAS leaching as the amendment ratios are refined.Collectively, these data demonstrate a net reduction of PFAS leachability
from stabilized test pits. However, the mechanism of retention is
unknown and could involve surface adsorption, complexation, fluorophilic
interactions, and/or chemisorption. Future work should utilize more
advanced microscopic and/or spectroscopic methods specifically to
probe these molecular interactions. Additional SEs to evaluate PFAS
leachability at the subject site may be considered and would strengthen
the defensibility of S/S as a long-term remedial solution.
Materials
and Methods
Investigation Site
The FTA selected for demonstration
is in the southeastern United States at an Air Force installation
that was previously the subject of a high-resolution site characterization.
Site selection was based on a well-established conceptual site model,
a shallow groundwater aquifer, low total dissolved solids/salinity
and TOC, coarse-grained lithology with a relatively flat hydraulic
gradient, and concentrations of PFAS in soil and groundwater in the
μg/kg and micrograms per liter (μg/L) range, respectively.
Historical firefighting training included burning fuels and other
flammable/combustible liquids within an unlined, earth-bermed circular
pit, followed by extinguishment with dilute AFFF.
Baseline Data
Collection
In February 2018, baseline
soil and groundwater samples were collected throughout the FTA from
10 locations (DPT-01 through DPT-10). The groundwater table was determined
to be approximately 1.5 m bgs. The soil borings were advanced to a
depth of approximately 6 m bgs, and three soil samples (approximately
1.5, 3, and 4.6 m bgs) were collected from each boring (30 soil samples
total). One groundwater sample was collected from each boring. Soil
and groundwater analyses were conducted by SGS AXYS in Canada and
SGS Accutest Orlando in Florida (Tables S13 and S14). All PFAS analyses associated with the work summarized
herein were done in accordance with quality protocols specified in
the Department of Defense/Department of Energy Consolidated Quality
Systems Manual (QSM).[78]Soil was
composited in two 18.9 L plastic Department of Transportation-rated
buckets. Approximately 9.5 L of site groundwater was collected into
a plastic container. The composited soil and the container of groundwater
were shipped to the Arcadis Treatability Laboratory (ATL) in Durham,
North Carolina for bench-scale testing.
PFAS Analytical Quality
Assurance and Quality Control
For liquid and solid PFAS analysis
performed at SGS Accutest Orlando,
all analyses followed modified USEPA Method 537 with quality protocols
specified in QSM 5.3. For pre TOP analysis performed at SGS AXYS in
Canada, analysis essentially followed modified USEPA Method 537 (SGS
Method MLA-110), which meets or exceeds quality protocols specified
in QSM 5.3. For post TOP analysis performed at SGS AXYS in Canada,
analysis was performed according to SGS Method MLA-111, which similarly
meets or exceeds quality protocols from QSM 5.3 but is not Department
of Defense accredited as no accreditation is available for post TOP
analysis. All methods use isotope-dilution high-performance liquid
chromatography with tandem mass spectrometry after solid-phase extraction.
Procedural blanks and ongoing precision and recovery quality control
samples were included. PFASs detected above the analytical detection
limit but below the limit of quantification were assigned “J”
flags, indicating that the value is detected but with a degree of
increased uncertainty.
Bench-Scale Testing
Amendment Selection
Five potential stabilizers were
considered to varying extents during the bench-scale testing: RB,
FS, pyrolyzed cellulose, an LDH, and an unnamed proprietary product.
RB is a powdered reagent composed of a proprietary blend of clays,
aluminum hydroxide (as pseudoboehmite) and carbons, and it was obtained
from Ziltek.[79] FS is a modified bentonite
clay, and it was obtained from CETCO.[80] The LDH was hydrotalcite (CAS number 11097-59-9), and it was obtained
from Sigma-Aldrich and was included based on promising performance
in previous trials in Australia.[81] Pyrolyzed
cellulose was not included in the bench-scale testing because, at
the time (2018), it was not cost feasible if selected. A proprietary
sealant was included at a commercial request. PC was selected as the
solidifying amendment.
Sample Preparation
Soil was stored
under ambient laboratory
temperature (approximately 23 °C), while groundwater was refrigerated
(<4 °C) until further use. Duplicate subsamples of air-dried
soil were analyzed for PFAS, TOC, TAL metals, and grain size. Groundwater
was analyzed for PFAS, total TAL metals plus major cations, TOC, nitrate,
nitrite, and alkalinity. A subsample of groundwater was filtered and
submitted for dissolved TAL metals plus major cations. Analysis for
PFAS incorporated the TOP assay.[82]100 g of wet soil (gravimetric moisture
content 11.6% and 88.4 g dry soil), targeted dry soil weight amendment
ratios, and 200 mL of groundwater were placed in 250 mL polypropylene
centrifuge tubes with polyethylene caps and thoroughly shaken by hand
(Table S15). The centrifuge tubes were
then placed on a roller table for 48 h to provide continuous agitation.
After 48 h, the tubes were centrifuged (Sorvall Instruments Model
RC3C; 30 min; and ∼3700 relative centrifugal force) to separate
the stabilized soil from groundwater and then sacrificially sampled.
Two 60 mL high-density polyethylene bottles were filled from each
centrifuge tube and submitted for aqueous-phase PFAS analysis, including
the TOP assay.[82] The pH of each tube was
measured using an Accumet pH electrode.
Intact Core Testing
While solidification (i.e., intentional
permeability reduction via PC addition) was not the focus of this
work, due to a sensitive ecological receptor at the selected site,
some degrees of rapid load-bearing capacity were required. Therefore,
strength development testing evaluated various PC/soil ratios to develop
an acceptable UCS. Each test mix was packed into a series of approximately
5 cm diameter by 10 cm long plastic geotechnical molds. After the
molds were filled, they were placed into plastic Ziploc bags to retain
humid/moist conditions and left to cure at ambient laboratory temperature.
At 28 days of curing, UCS testing was conducted on one mold per test
mix (ASTM D1633).Stabilizer and PC ratios (based on dry weight)
identified as the best performers were then combined into intact core
leach testing (Table S5). Soil was blended
with appropriate quantities of stabilizers, PC, and water in a stainless-steel
bowl using a Hobart model HL-200 planetary mixer. After thoroughly
blending, test mixes were packed into a series of 5 cm diameter by
10 cm long plastic geotechnical molds and cured similarly to the UCS
development testing. At 7 days of curing, one mold from each test
mix was submitted for UCS testing. At 28 days of curing, molds from
each test mix were submitted for UCS testing and tested for hydraulic
conductivity (ASTM D5084). At 34 days of curing, one mold from each
mix was sized (5 cm diameter by 8.9 cm long) and shipped for monolithic
leachability evaluation by LEAF USEPA Method 1315.[83] During the leaching procedure, samples were placed into
2 L plastic wide-mouth jars and exposed to scheduled 1.8 L leachate
exchanges (∼9.9 mL/cm2). Leachate samples from the
third (T48h; 2 days) and ninth (T63d; 63 days) leaching intervals
were collected and submitted for the analysis of PFAS concentrations
(pre and post TOP assay), TAL metals, and TOC. Leachates from T63d
were also analyzed for SC and pH. T48h was selected to qualitatively
match the 2-day batch testing, and T63d was selected to conservatively,
yet cost-effectively, assess leaching, given the highly asymmetric
elution tailing observed for select PFAS (e.g., PFOS) during transport
studies.[84]
Field-Scale Demonstration
Soil
Mixing
Field-scale implementation used two distinct
stabilizer ratios per selected commercial product (RB and FS) and
PC ratios according to UCS testing results (Table S6). Five approximately 3 m long by 3 m wide by 3 m deep test
pits (approximately 28 m3) to an approximate depth of 4.5
m bgs were mixed in July 2018 (Figure S1). Approximately 1.5 m of overburden soil was temporarily removed
from each test pit to create room for anticipated bulking. A process
pass using an excavator loosened the soil within the test pits. Stabilizers
(FS and RB) and PC were measured and mixed into the soil in situ with
a bucket mixer and/or rotary mixer. The site was graded using the
excess overburden soil. Slump tests were completed on test pits to
verify the consistency after mixing. No sample cores were collected
immediately following the completion of soil mixing (i.e., no zero-time
soil samples).
Performance Monitoring
SEs were
conducted 5-, 12-,
16-, 22-, and 28-month post mixing from July 2018 through October
2020 to assess PFAS leachability (Table S9). A 12-area grid was created for each test pit (Figure S1). A total of 65 sample cores were collected during
the approximate 28-month duration, including five duplicate samples
(Table S9). Sample cores were collected
from the middle portion of the test pit grids, biased to the most
uniformly mixed intervals. Intervals that were noticeably friable
(i.e., crumbly) or appeared to be poorly mixed via visual inspection
were avoided. Due to intentionally targeting a low UCS, sample cores
were poorly formed and were inappropriate for intact core leaching.
Therefore, granular sequential leaching was used for analysis.Each test pit sample core was sent to the ATL for processing into
granular samples prior to packaging for shipment to Eurofins Test
America. Eurofins Test America packed the granular samples into 7.6
cm molds provided by the ATL before performing LEAF Method 1315 analysis.
Nine sequential leachate samples (T2h through T63d) of approximately
411 mL (equivalent to 9 ± 1 mL/cm2 leaching surface
area as specified in USEPA Method 1315) each were produced per granular
sample, and the leached sample mass ranged from 260 to 527 g of soil.
Wet chemistry data (pH, oxidation reduction potential, and SC) were
collected for each leachate sample as well as the blank laboratory
water used for the analysis. Leachate from the T48h interval and the
method blank was analyzed for PFAS (post TOP assay) and for metals
and TOC. For SE 12mo and SE 28mo, leachates were composited (SE 12mo:
all nine leachates composited together and SE 28mo: T2h–T24h
and T5d–T63d; Table S9).
Mass Balance
Sample cores collected during SE 12mo
(Table S9) were analyzed for PFAS soil
concentrations (post TOP assay) pre- and post-leaching. Additionally,
the T2h-T63d leaches were composited together and analyzed for PFAS
(post TOP assay).
Theory/Calculation
The percentage
of PFAS leached during
the batch testing was calculated after Kabiri and McLaughlin[62] as followswhere Ctotal is
the PFAS concentration in soil (μg/g) and Cw (μg/g) is the concentration of the PFAS leached,
calculated as followswhere C (μg/L) is the
concentration of PFAS in the leachate, V (L) is the
volume of the leachate, and m (g) is the mass of
the soil leached. The corresponding mass of the amendments was subtracted
from the mass of the soil leached to eliminate dilution concerns.
Where data were reported to be less than the analytical detection
limit, one-half of the reported detection limit was used for calculation
purposes.The attempted mass balance is a comparison of the
soil analysis for PFAS prior to leaching (M1) to the summation of the soil analysis for PFAS after leaching (M3) and a composite analysis of the nine sequential
leaches (M2) calculated as followsThe percent difference was calculated
as followsStatistical one-tailed Student t-tests were
performed
via Microsoft Excel.
Authors: Mark L Brusseau; Naima Khan; Yake Wang; Ni Yan; Sarah Van Glubt; Kenneth C Carroll Journal: Environ Sci Technol Date: 2019-08-29 Impact factor: 9.028
Authors: Brian R Pinkard; Shreyas Shetty; Derek Stritzinger; Christopher Bellona; Igor V Novosselov Journal: Chemosphere Date: 2021-05-18 Impact factor: 7.086