Alissandra Pessoa Almeida1,2, Vitor Sousa3, Cristina Matos Silva3.
Abstract
Knowing water and energy consumption patterns sets the baseline for understanding their drivers and assessing the performance of potential measures to increase efficiency and/or reliability. These patterns can vary substantially depending on the building characteristics, on the building users and use, on the cultural, social, economic, environmental context in which the building is located, among many other factors. This article presents a general methodological framework for characterizing water and energy consumption patterns in buildings based on the evaluation of the characteristics of the equipments and appliances, as well as the type of users and the activities developed in each type of room. This allows estimating water and energy use, by end use per square meter and by roomtype. The methodological framework proposed was applied to the buildings of the Paricarana Campus of Federal University of Roraima (UFRR), Brazil, providing one of the few examples in the literature reporting water and energy consumption in university buildings in tropical climates. Universities, in most cases, represent large water and energy consumers with distinctive consumption drivers and patterns which have received limited attention when compared to other types of buildings (e.g., residential). The findings have shown that teaching rooms and administration rooms are the main consumers, representing 48% and 49% of the institution's energy and water consumption, respectively. Air conditioning is the biggest energy consumption (63%), while personal use represents 72% of the total water consumption in a building. The toilets represent a large water consumption in a university building (46.40%). Comparing different building uses, the central library is the highest consumer, due to the longest operating time and the highest occupational density. The methodological proposal intends to be a useful tool to support managers and decision-makers to understand the dynamics of consumption and then propose effective practices to reduce water and energy uses, as well as providing reference data for comparison with other educational institutions.Entities:
Keywords: End use of water and energy; University building; Water and energy consumption
Year: 2021 PMID: 35005287 PMCID: PMC8718938 DOI: 10.1016/j.heliyon.2021.e08642
Source DB: PubMed Journal: Heliyon ISSN: 2405-8440
Figure 1Methodological framework for estimating building water/energy consumption.
Figure 2Methodology for estimating consumption indirectly in buildings.
Figure 3Paricarana Campus buildings.
Figure 4Distribution of the areas (a) and occupation (b) of the type of room of buildings.
Figure 5Area and occupation of buildings on the Paricarana campus.
CE consumption.
| Code | Equipment/Device/Activity | consumption | Unit |
|---|---|---|---|
| EC1 | Air conditioning 12000 BTUS | 763 | kWh/1000h |
| EC2 | Air conditioning 18000 BTUS | 1160 | kWh/1000h |
| EC3 | Air conditioning 24000 BTUS | 1623 | kWh/1000h |
| EC4 | Air conditioning 30000 BTUS | 1820 | kWh/1000h |
| EC5 | Air conditioning 48000 BTUS | 3223 | kWh/1000h |
| EC6 | Air conditioning 60000 BTUS | 3896 | kWh/1000h |
| EC7 | Lighting (2 × 16w) | 40 | kWh/1000h |
| EC8 | Lighting (2 × 32w) | 78 | kWh/1000h |
| PC1 | Computer | 180 | kWh/1000h |
| PC2 | Laptop | 90 | kWh/1000h |
| PC3 | Projector | 300 | kWh/1000h |
| PC4 | Mobile phone/tablet chargers | 5 | kWh/1000h |
| PC5 | Drink | 0.25 | l/use |
| PC6 | Toilet | 6 | l/use |
| PC7 | Urinal | 1.2 | l/use |
| PC8 | Tap (wash hands) | 1.38 | l/use |
| PC9 | Tap (wash teeth) | 1.38 | l/use |
| PC10 | Shower | 35.3 | l/use |
| AC1 | Damp cloth in the floor | 0.32 | l/m2 |
| AC2 | Wash the floor | 1.23 | l/m2 |
Number of CE in the rooms.
| Code | AA | BA | LIA | OA | LA | OA | FPA | SA | TA |
|---|---|---|---|---|---|---|---|---|---|
| EC1 | 87 | 0 | 0 | 33 | 29 | 0 | 35 | 14 | 3 |
| EC2 | 99 | 0 | 4 | 141 | 19 | 0 | 12 | 16 | 15 |
| EC3 | 43 | 0 | 1 | 3 | 17 | 0 | 9 | 15 | 60 |
| EC4 | 92 | 0 | 2 | 16 | 71 | 0 | 6 | 19 | 43 |
| EC5 | 34 | 0 | 1 | 7 | 65 | 0 | 2 | 41 | 224 |
| EC6 | 19 | 0 | 42 | 0 | 38 | 0 | 4 | 99 | 46 |
| EC7 | 0 | 671 | 0 | 0 | 0 | 1 | 0 | 0 | 0 |
| EC8 | 1814 | 0 | 589 | 643 | 1813 | 3625 | 226 | 3169 | 3524 |
| PC1 | 611 | 0 | 803 | 563 | 842 | 0 | 0 | 374 | 2003 |
| PC2 | 611 | 0 | 803 | 563 | 842 | 0 | 0 | 374 | 2003 |
| PC3 | 611 | 0 | 803 | 563 | 842 | 0 | 0 | 374 | 2003 |
| PC4 | 611 | 0 | 803 | 563 | 842 | 0 | 0 | 374 | 2003 |
| PC5 | 611 | 0 | 803 | 563 | 842 | 0 | 0 | 374 | 2003 |
| PC6 | 611 | 0 | 803 | 563 | 842 | 0 | 0 | 374 | 2003 |
| PC7 | 611 | 0 | 803 | 563 | 842 | 0 | 0 | 374 | 2003 |
| PC8 | 611 | 0 | 803 | 563 | 842 | 0 | 0 | 374 | 2003 |
| PC9 | 611 | 0 | 803 | 563 | 842 | 0 | 0 | 374 | 2003 |
| PC10 | 611 | 0 | 803 | 563 | 842 | 0 | 0 | 374 | 2003 |
| AC1 | 8421 | 3599 | 2409 | 3177 | 8417 | 14513 | 1517 | 12467 | 15716 |
| AC2 | 8421 | 3599 | 2409 | 3177 | 8417 | 14513 | 1517 | 12467 | 15716 |
Enquiries respondents characteristics.
| Type | Population | Replies | Response rate | Sample error |
|---|---|---|---|---|
| Students | 4400 | 251 | 5.70% | 6.00% |
| Teacher | 562 | 46 | 8.19% | 14.00% |
| Administrative staff | 661 | 63 | 9.53% | 12.00% |
| Total | 5623 | 360 | 6.40% | 5.00% |
Gender and demographic distribution of the respondents.
| Type | Gender | Age (years) | Length of stay (h/day) | |||||
|---|---|---|---|---|---|---|---|---|
| Female | Male | 17–24 | 25–35 | 36–50 | 51–60 | >60 | ||
| Students | 58.17% | 41.83% | 74.90% | 17.13% | 7.17% | 0.40% | 0.40% | 7.51 |
| Teacher | 52.17% | 47.83% | 0.00% | 32.61% | 30.43% | 30.43% | 6.52% | 8.05 |
| Administrative staff | 58.73% | 41.27% | 1.59% | 53.97% | 33.33% | 9.52% | 1.59% | 8.35 |
| Total | 57.50% | 42.50% | 52.50% | 25.56% | 14.72% | 5.83% | 1.39% | 7.73 |
Use frequency of the CE on school days, Saturdays and class breaks.
| Cod | AA | BA | LIA | OA | LA | OTA | FPA | SA | TA |
|---|---|---|---|---|---|---|---|---|---|
| EC1 | 8.00 | 0.00 | 12.00 | 6.00 | 6.00 | 0.00 | 8.00 | 4.00 | 8.00 |
| EC2 | 8.00 | 0.00 | 12.00 | 6.00 | 6.00 | 0.00 | 8.00 | 4.00 | 8.00 |
| EC3 | 8.00 | 0.00 | 12.00 | 6.00 | 6.00 | 0.00 | 8.00 | 4.00 | 8.00 |
| EC4 | 8.00 | 0.00 | 12.00 | 6.00 | 6.00 | 0.00 | 8.00 | 4.00 | 8.00 |
| EC5 | 8.00 | 0.00 | 12.00 | 6.00 | 6.00 | 0.00 | 8.00 | 4.00 | 8.00 |
| EC6 | 8.00 | 0.00 | 12.00 | 6.00 | 6.00 | 0.00 | 8.00 | 4.00 | 8.00 |
| EC7 | 8.00 | 4.00 | 12.00 | 6.00 | 4.00 | 4.00 | 8.00 | 4.00 | 8.00 |
| EC8 | 8.00 | 4.00 | 12.00 | 6.00 | 4.00 | 4.00 | 8.00 | 4.00 | 8.00 |
| PC1 | 6.13 | 0.00 | 1.04 | 2.65 | 1.04 | 0.00 | 0.00 | 1.04 | 6.13 |
| PC2 | 0.72 | 0.00 | 1.97 | 0.36 | 1.97 | 0.00 | 0.00 | 1.97 | 0.72 |
| PC3 | 0.00 | 0.00 | 0.18 | 0.78 | 0.18 | 0.00 | 0.00 | 0.18 | 0.00 |
| PC4 | 0.88 | 0.00 | 1.93 | 0.45 | 1.93 | 0.00 | 0.00 | 1.93 | 0.88 |
| PC5 | 4.95 | 0.00 | 4.50 | 5.00 | 4.50 | 0.00 | 0.00 | 4.50 | 4.95 |
| PC6 | 2.98 | 0.00 | 2.55 | 2.72 | 2.55 | 0.00 | 0.00 | 2.55 | 2.98 |
| PC7 | 0.67 | 0.00 | 0.68 | 0.83 | 0.68 | 0.00 | 0.00 | 0.68 | 0.67 |
| PC8 | 4.52 | 0.00 | 3.50 | 3.91 | 3.50 | 0.00 | 0.00 | 3.50 | 4.52 |
| PC9 | 0.49 | 0.00 | 0.72 | 0.42 | 0.72 | 0.00 | 0.00 | 0.72 | 0.49 |
| PC10 | 0.09 | 0.00 | 0.09 | 0.02 | 0.09 | 0.00 | 0.00 | 0.09 | 0.09 |
| AC1 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| AC2 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EC1 | 0.00 | 0.00 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
| EC2 | 0.00 | 0.00 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
| EC3 | 0.00 | 0.00 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
| EC4 | 0.00 | 0.00 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
| EC5 | 0.00 | 0.00 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
| EC6 | 0.00 | 0.00 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
| EC7 | 0.00 | 0.00 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
| EC8 | 0.00 | 0.00 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
| PC1 | 0.00 | 0.00 | 0.35 | 0.88 | 0.35 | 0.00 | 0.00 | 0.35 | 0.35 |
| PC2 | 0.00 | 0.00 | 0.66 | 0.12 | 0.66 | 0.00 | 0.00 | 0.66 | 0.66 |
| PC3 | 0.00 | 0.00 | 0.06 | 0.26 | 0.06 | 0.00 | 0.00 | 0.06 | 0.06 |
| PC4 | 0.00 | 0.00 | 0.64 | 0.15 | 0.64 | 0.00 | 0.00 | 0.64 | 0.64 |
| PC5 | 0.00 | 0.00 | 1.50 | 1.67 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 |
| PC6 | 0.00 | 0.00 | 0.85 | 0.91 | 0.85 | 0.00 | 0.00 | 0.85 | 0.85 |
| PC7 | 0.00 | 0.00 | 0.23 | 0.28 | 0.23 | 0.00 | 0.00 | 0.23 | 0.23 |
| PC8 | 0.00 | 0.00 | 1.17 | 1.30 | 1.17 | 0.00 | 0.00 | 1.17 | 1.17 |
| PC9 | 0.00 | 0.00 | 0.24 | 0.14 | 0.24 | 0.00 | 0.00 | 0.24 | 0.24 |
| PC10 | 0.00 | 0.00 | 0.03 | 0.01 | 0.03 | 0.00 | 0.00 | 0.03 | 0.03 |
| AC1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| AC2 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| EC1 | 8.00 | 0.00 | 12.00 | 0.00 | 6.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EC2 | 8.00 | 0.00 | 12.00 | 0.00 | 6.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EC3 | 8.00 | 0.00 | 12.00 | 0.00 | 6.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EC4 | 8.00 | 0.00 | 12.00 | 0.00 | 6.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EC5 | 8.00 | 0.00 | 12.00 | 0.00 | 6.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EC6 | 8.00 | 0.00 | 12.00 | 0.00 | 6.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EC7 | 8.00 | 0.00 | 12.00 | 0.00 | 4.00 | 4.00 | 0.00 | 0.00 | 0.00 |
| EC8 | 8.00 | 0.00 | 12.00 | 0.00 | 4.00 | 4.00 | 0.00 | 0.00 | 0.00 |
| PC1 | 6.13 | 0.00 | 0.00 | 2.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
| PC2 | 0.72 | 0.00 | 0.00 | 0.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 |
| PC3 | 0.00 | 0.00 | 0.00 | 0.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
| PC4 | 0.88 | 0.00 | 0.00 | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1.93 |
| PC5 | 4.95 | 0.00 | 0.00 | 5.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
| PC6 | 2.98 | 0.00 | 0.00 | 2.72 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
| PC7 | 0.67 | 0.00 | 0.00 | 0.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
| PC8 | 4.52 | 0.00 | 0.00 | 3.91 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 |
| PC9 | 0.49 | 0.00 | 0.00 | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
| PC10 | 0.09 | 0.00 | 0.00 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
| AC1 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| AC2 | 0.00 | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
The CE by type of room of the Buildings of the Paricarana Campus.
| Code | AA | BA | LIA | OA | LA | OTA | FPA | SA | TA |
|---|---|---|---|---|---|---|---|---|---|
| EC1 | 78276 | 0 | 0 | 32553 | 21950 | 0 | 7306 | 5845 | 1835 |
| EC2 | 135419 | 0 | 12606 | 211459 | 21864 | 0 | 3809 | 10156 | 13948 |
| EC3 | 82295 | 0 | 4409 | 6295 | 27370 | 0 | 3996 | 13322 | 78060 |
| EC4 | 197445 | 0 | 9889 | 37648 | 128186 | 0 | 2988 | 18922 | 62733 |
| EC5 | 129219 | 0 | 8756 | 29168 | 207819 | 0 | 1764 | 72309 | 578717 |
| EC6 | 87289 | 0 | 444555 | 0 | 146864 | 0 | 4264 | 211057 | 143660 |
| EC7 | 0 | 1369 | 0 | 0 | 0 | 12 | 0 | 0 | 0 |
| EC8 | 166847 | 0 | 124815 | 64842 | 140283 | 84146 | 4823 | 135258 | 220337 |
| PC1 | 180680 | 0 | 36528 | 76000 | 38302 | 0 | 0 | 17013 | 106114 |
| PC2 | 10611 | 0 | 34596 | 5191 | 36277 | 0 | 0 | 16113 | 100502 |
| PC3 | 0 | 0 | 10537 | 37283 | 11049 | 0 | 0 | 4908 | 30610 |
| PC4 | 720 | 0 | 1883 | 358 | 1974 | 0 | 0 | 877 | 5470 |
| PC5 | 203 | 0 | 220 | 199 | 230 | 0 | 0 | 102 | 638 |
| PC6 | 2928 | 0 | 2985 | 2600 | 3130 | 0 | 0 | 1390 | 8673 |
| PC7 | 132 | 0 | 159 | 159 | 167 | 0 | 0 | 74 | 463 |
| PC8 | 1021 | 0 | 942 | 860 | 988 | 0 | 0 | 439 | 2738 |
| PC9 | 111 | 0 | 194 | 92 | 203 | 0 | 0 | 90 | 563 |
| PC10 | 543 | 0 | 634 | 135 | 664 | 0 | 0 | 295 | 1841 |
| AC1 | 722 | 0 | 207 | 272 | 614 | 1245 | 111 | 1069 | 1147 |
| AC2 | 466 | 1297 | 133 | 176 | 0 | 803 | 159 | 690 | 870 |
Use intensity of the CE by type of rooms.
| Code | AA | BA | LIA | OA | LA | OTA | FPA | SA | TA |
|---|---|---|---|---|---|---|---|---|---|
| EC1 | 9.14 | 0.00 | 0.00 | 10.20 | 2.73 | 0.00 | 6.84 | 0.44 | 0.12 |
| EC2 | 15.81 | 0.00 | 5.23 | 66.24 | 2.71 | 0.00 | 3.57 | 0.77 | 0.90 |
| EC3 | 9.61 | 0.00 | 1.83 | 1.97 | 3.40 | 0.00 | 3.74 | 1.01 | 5.02 |
| EC4 | 23.05 | 0.00 | 4.11 | 11.79 | 15.92 | 0.00 | 2.80 | 1.44 | 4.04 |
| EC5 | 15.08 | 0.00 | 3.63 | 9.14 | 25.80 | 0.00 | 1.65 | 5.49 | 37.25 |
| EC6 | 10.19 | 0.00 | 184.54 | 0.00 | 18.24 | 0.00 | 3.99 | 16.01 | 9.25 |
| EC7 | 0.00 | 0.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EC8 | 19.48 | 0.00 | 51.81 | 20.31 | 17.42 | 5.67 | 4.52 | 10.26 | 14.18 |
| PC1 | 21.09 | 0.00 | 15.16 | 23.81 | 4.54 | 0.00 | 0.00 | 1.29 | 6.83 |
| PC2 | 1.24 | 0.00 | 14.36 | 1.63 | 4.30 | 0.00 | 0.00 | 1.22 | 6.47 |
| PC3 | 0.00 | 0.00 | 4.37 | 11.68 | 1.31 | 0.00 | 0.00 | 0.37 | 1.97 |
| PC4 | 0.08 | 0.00 | 0.78 | 0.11 | 0.23 | 0.00 | 0.00 | 0.07 | 0.35 |
| PC5 | 0.02 | 0.00 | 0.09 | 0.06 | 0.03 | 0.00 | 0.00 | 0.01 | 0.04 |
| PC6 | 0.34 | 0.00 | 1.24 | 0.81 | 0.37 | 0.00 | 0.00 | 0.11 | 0.56 |
| PC7 | 0.02 | 0.00 | 0.07 | 0.05 | 0.02 | 0.00 | 0.00 | 0.01 | 0.03 |
| PC8 | 0.12 | 0.00 | 0.39 | 0.27 | 0.12 | 0.00 | 0.00 | 0.03 | 0.18 |
| PC9 | 0.01 | 0.00 | 0.08 | 0.03 | 0.02 | 0.00 | 0.00 | 0.01 | 0.04 |
| PC10 | 0.06 | 0.00 | 0.26 | 0.04 | 0.08 | 0.00 | 0.00 | 0.02 | 0.12 |
| AC1 | 0.08 | 0.00 | 0.09 | 0.09 | 0.08 | 0.08 | 0.10 | 0.08 | 0.07 |
| AC2 | 0.05 | 0.39 | 0.06 | 0.06 | 0.00 | 0.05 | 0.15 | 0.05 | 0.06 |
Figure 6Water and energy consumption of the buildings.
Energy and water consumption results in Paricarana campus buildings.
| Calculated | Measured | Difference (%) | |
|---|---|---|---|
| Energy (MWh/year) | 5002 | 5205 | 4.06% |
| Water (m³/year) | 3994 | 4389 | 9.89% |
Figure 7Energy consumption by type of rooms and end-use (a) and water consumption type of rooms and end-use (b).
Consumption intensity per end-use by type of room.
| Code | AA | BA | LIA | OA | LA | OTA | FPA | SA | TA |
|---|---|---|---|---|---|---|---|---|---|
| ECAC | 84.30 | 0.00 | 199.35 | 99.81 | 65.82 | 0.00 | 15.90 | 26.60 | 55.93 |
| ECL | 19.81 | 0.38 | 51.81 | 20.41 | 16.67 | 5.80 | 3.18 | 10.85 | 14.02 |
| ECE | 22.80 | 0.00 | 34.68 | 37.40 | 10.41 | 0.00 | 0.00 | 3.12 | 15.44 |
| COE | 5.15 | 0.02 | 11.60 | 6.40 | 3.77 | 0.24 | 0.77 | 1.65 | 3.47 |
| TEC | 132.07 | 0.40 | 297.44 | 164.02 | 96.66 | 6.03 | 19.86 | 42.22 | 88.85 |
| WCP | 0.59 | 0.00 | 2.13 | 1.27 | 0.64 | 0.00 | 0.00 | 0.19 | 0.95 |
| WCC | 0.14 | 0.36 | 0.14 | 0.14 | 0.07 | 0.14 | 0.18 | 0.14 | 0.13 |
| OWC | 0.07 | 0.04 | 0.22 | 0.14 | 0.07 | 0.01 | 0.02 | 0.03 | 0.11 |
| TWC | 0.80 | 0.40 | 2.50 | 1.55 | 0.78 | 0.16 | 0.20 | 0.37 | 1.18 |
Comparison of water and energy consumption in the current study with other authors.
| Reference | Location/climate | Type variable | (kWh/m2/year) | (kWh/hab/year) | (m³/m2/year) | (m³/hab/year) |
|---|---|---|---|---|---|---|
| This study | ||||||
| ( | Chine/Cfa | Disciplines/nature | 37–10 | 400–1480 | 0.8–3.5 | 38–176 |
| ( | Canada/ET | Building type | 40–500 | 1000–104.340 | 0–16 | 0–110 |
| ( | Mexico/Cwa | Room type | 18.15–95.83 | - | - | - |
| ( | Accidental Macedonia/Dfb | General | 150–240 | 1 | ||
| ( | France/Cfb | Room type | 25–123 | - | 0.17–3.99 | - |
| ( | England/Cfb | Building type | 155–426 | |||
| ( | Korea/Dfa unive | General | 211–252.63 | 3888.88–4444.44 | ||
| ( | Thailand/Cfa | General | 79.98–87.57 | |||
| ( | USA/Cfa | Building type | 252.3–567.7 | 1758.5–7913.24 | ||
| ( | Brazil/Cfa | General | 243–554 | |||
| ( | Brazil/Af | General | 9.782 | |||
| ( | Poland/Cfb | General | 6.5–8.95 | |||
| (L. | Chine/Cfa | General | 707.27–1415.70 | |||
| ( | Chine/Cfa | General | 1 097 | 94 | ||
| ( | Ireland/Cfb | General | 145–187 | 1480–1590 | ||
| ( | France/Cfb | Building type | 52.40–362.7 (pe) | |||
| ( | England/Cfb | Building type | 240–339 | 2492–9187 | ||
| ( | Australia/Cfb | Building type | 136–164 | |||
| ( | Taiwan/Am | Nature | 63.8–90.4 | 927–2889 |