Carlos G Albà1,2, Ismail I I Alkhatib1, Fèlix Llovell2, Lourdes F Vega1. 1. Research and Innovation Center on CO2 and Hydrogen (RICH Center), Chemical Engineering Department, Khalifa University, P.O. Box 127788, Abu Dhabi, United Arab Emirates. 2. Department of Chemical Engineering, ETSEQ, Universitat Rovira i Virgili (URV), Av. Països Catalans 26, 43007 Tarragona, Spain.
Abstract
The use of hydrofluorocarbons (HFCs) as an alternative for refrigeration units has grown over the past decades as a replacement to chlorofluorocarbons (CFCs), banned by the Montreal's Protocol because of their effect on the depletion of the ozone layer. However, HFCs are known to be greenhouse gases with considerable global warming potential (GWP), thousands of times higher than carbon dioxide. The Kigali Amendment to the Montreal Protocol has promoted an active area of research toward the development of low GWP refrigerants to replace the ones in current use, and it is expected to significantly contribute to the Paris Agreement by avoiding nearly half a degree Celsius of temperature increase by the end of this century. We present here a molecular-based evaluation tool aiming at finding optimal refrigerants with the requirements imposed by current environmental legislations in order to mitigate their impact on climate change. The proposed approach relies on the robust polar soft-SAFT equation of state to predict thermodynamic properties required for their technical evaluation at conditions relevant for cooling applications. Additionally, the thermodynamic model integrated with technical criteria enable the search for compatibility of currently used third generation compounds with more eco-friendly refrigerants as drop-in replacements. The criteria include volumetric cooling capacity, coefficient of performance, and other physicochemical properties with direct impact on the technical performance of the cooling cycle. As such, R1123, R1224yd(Z), R1234ze(E), and R1225ye(Z) demonstrate high aptitude toward replacing R134a, R32, R152a, and R245fa with minimal retrofitting to the existing system. The current modeling platform for the rapid screening of emerging refrigerants offers a guide for future efforts on the design of alternative working fluids.
The use of hydrofluorocarbons (HFCs) as an alternative for refrigeration units has grown over the past decades as a replacement to chlorofluorocarbons (CFCs), banned by the Montreal's Protocol because of their effect on the depletion of the ozone layer. However, HFCs are known to be greenhouse gases with considerable global warming potential (GWP), thousands of times higher than carbon dioxide. The Kigali Amendment to the Montreal Protocol has promoted an active area of research toward the development of low GWP refrigerants to replace the ones in current use, and it is expected to significantly contribute to the Paris Agreement by avoiding nearly half a degree Celsius of temperature increase by the end of this century. We present here a molecular-based evaluation tool aiming at finding optimal refrigerants with the requirements imposed by current environmental legislations in order to mitigate their impact on climate change. The proposed approach relies on the robust polar soft-SAFT equation of state to predict thermodynamic properties required for their technical evaluation at conditions relevant for cooling applications. Additionally, the thermodynamic model integrated with technical criteria enable the search for compatibility of currently used third generation compounds with more eco-friendly refrigerants as drop-in replacements. The criteria include volumetric cooling capacity, coefficient of performance, and other physicochemical properties with direct impact on the technical performance of the cooling cycle. As such, R1123, R1224yd(Z), R1234ze(E), and R1225ye(Z) demonstrate high aptitude toward replacing R134a, R32, R152a, and R245fa with minimal retrofitting to the existing system. The current modeling platform for the rapid screening of emerging refrigerants offers a guide for future efforts on the design of alternative working fluids.
Within the context
of sustainable development, climate action is
one of the vital topics in the United Nations’ (UN) goals for
sustainable future, focusing on increased awareness and mobilization
to resist the adverse ecological effects of climate change.[1] The main culprit responsible for the emergence
of this notorious problem was the utilization of highly active ozone
depleting chlorofluorocarbons (CFCs) in the refrigeration and cooling
industries, leading to their global ban with the enacting of the Montreal
Protocol.[2] At that stage, the dire industrial
need for replacements identified third generation refrigerants hydrofluorocarbons
(HFCs) as viable options based on their zero ozone depletion potential
(ODP) compared to their banned predecessors.[3] However, an unforeseeable consequence, further aggravating the climate
change problem, was their high global warming potential (GWP), as
HFCs are potent greenhouse gases, with projected CO2-equivalent
emissions of 6%–9% of total CO2 emissions by 2050.[4] Once again, stricter environmental legislations[5−9] were passed to gradually phase out and restrict the usage of third
generation refrigerants in upcoming years, targeting replacements
with low GWP.Even though environmentally friendly refrigeration
and cooling
technologies are being developed such as absorption refrigeration,[10−12] adsorption refrigeration,[13] and other
novel systems,[14] the cooling industry is
still heavily reliant on the more efficient vapor compression refrigeration
cycles (VCRCs) with fluorinated compounds as working fluids. As such,
in lieu of the current targets of environmental legislations, the
search for alternative refrigerants replacing HFCs for today’s
market is solely dictated by eco-friendly properties such as zero
ODP, low GWP, and moderate safety-related properties (i.e., flammability,
and toxicity), examining a wide array of substances both natural and
synthetic as potential replacements to the currently used third generation
refrigerants. The resurged interest in the use of well-known natural
fluids identified NH3, CO2, n-alkanes, and water as possible working fluids for air-conditioning
applications. However, the commercialization of these natural fluids
is hindered either by their poor safety-related properties or inability
to operate at specific conditions applicable to currently available
refrigeration systems. As such, these options are deemed infeasible
single-component drop-in replacements, entailing additional retrofitting
of refrigeration cycles using third generation refrigerants.[15]Conversely, synthetic fourth generation
refrigerants such as hydrofluoroolefins
(HFOs), hydrochlorofluoroolefins (HCFOs), hydrofluoroethers (HFEs),
and even selected blends with third generation HFCs, have demonstrated
potentiality in replacing currently used third generation working
fluids.[16,17] DuPont and Honeywell developed 2,3,3,3-tetrafluoroprop-1-ene
(R1234yf) as an eco-friendly replacement for 1,1,1,2-tetrafluoroethane
(R134a) and examined its application for mobile air conditions systems
(MAC), identifying its potentiality as a replacement working fluid
satisfying environmental and safety constraints, at the price of a
reduced system efficiency[18] and higher
cost. In spite of these limitations, R1234yf is already used as a
refrigerant for automobile applications in Europe, with a long list
of model vehicles using it, following the implementation of the EU
Directive 2006/40/EC[6] in 2013, banning
the use of R134a for this application. In a similar fashion, trans-1,3,3,3-tetrafluoroprop-1-ene
(R1234ze(E)) was also identified as a viable replacement for R134a
in commercial refrigeration cycles and medium temperature heat pumps
based on its eco-friendly properties,[19] yet with the expense of additional capital costs for retrofitting
systems to maintain a similar level of performance.[20] As opposed to natural refrigerants, a drawback associated
with fourth generation refrigerants such as R1234yf and R1234ze(E),
is their rapid degradation and formation of stable trifluoroacetate
(TFA), potentially contaminating surrounding soil and terminal water
bodies.[21,22] However, recent studies established that
the expected concentrations of these degradation products will have
a negligible impact on the ecosystem.[22,23] Thus, far,
finding a single-component refrigerant encompassing all desirable
properties remains an elusive and difficult feat.Although the
previous examples demonstrate the potentiality of
some fourth generation synthetic refrigerants with regard to environmental
and safety-related properties in line with environmental regulations,
the lingering question to be answered is whether these alternatives
can satisfy the technical (and safety) demand of the market for different
cooling applications. Ascertaining the potentiality of these alternative
refrigerants on technical facets is relevant but given a secondary
priority as opposed to the more urgent environmental facets, hence
their limited availability in the literature.[20,24−30] Replacing the current commercially used third generation refrigerants
with a low GWP alternative is not straightforward and might lead to
retrofitting the existing system, resulting in a trade-off, often
overlooked, between meeting environmental constraints and incurring
additional costs or compromising system performance.[31−34] To blame for this is the lack of experimental data on the physicochemical
properties of alternative refrigerants, essential for their accurate
technical evaluation and projection on industrial scale.[35] This is expected as experimentally obtaining
all relevant properties is quite taxing in temporal and monetary terms,
given the number of different properties, varying operating conditions,
and possible working fluids.As such, pragmatic and robust computational
tools provide a possible
remedy to overcome this hurdle, with the capability of rapidly determining
potential HFCs replacements, satisfying environmental and technical
requirements. With the rise of thermodynamic modeling approaches and
computational power, such paradigms have been successfully developed
for varying applications such as screening of materials for CO2 capture[36−40] and solvents for other separation processes.[41−44] The success of these paradigms
is entirely dependent on the accuracy and robustness of the chosen
thermodynamic model.[24] In this regard,
molecular-based equations of state (EoSs) such as those routed on
the statistical associating fluid theory (SAFT)[45] have become indispensable tools in modeling the thermodynamic
behavior of complex fluids. These models have rigorous physical basis
from statistical mechanics, enabling them to accurately capture the
effect of intermolecular interactions (i.e., dispersive, associating,
polar) on macrolevel phenomena. This is an added edge over conventional
EoSs, that are incapable of explicitly modeling polar interactions
governing the behavior of third and fourth generation refrigerants
and other green substances of polar nature.[46−48] The adoption
of SAFT-based models as a central pillar for screening tools has been
steadily growing,[49−53] holding the promise of similar success when applied to screening
alternative eco-friendly refrigerants as drop-in replacements under
the same operating conditions and technical criteria. This is fueled
by the demonstrated success of our group in accurately modeling the
holistic thermodynamic behavior of third and fourth generation refrigerants.[54−58] On another front, the physical basis of SAFT-based models can enable
the extraction of microlevel tendencies linked with observable physicochemical
properties and technical performance. This fundamental level knowledge
can effectively guide future efforts on the search of promising low
GWP alternative refrigerants.Other molecular-based approaches
have also been employed for predicting
the thermodynamic behavior of fourth generation refrigerants, such
as the series of contributions by Raabe and Maginn[59−65] on the use of molecular simulations for determining thermodynamic
properties of these compounds. Although molecular simulations provide
a good detail of physical insights, the required computational time
to fully characterize any refrigerant and blends with the required
properties for implementing them in cooling applications solely with
molecular simulations becomes prohibit expensive. Alternatively, molecular-based
EoSs use a coarse-grained approach, preserving the key features of
the molecular structure, including their polar nature, with very modest
computational requirements. Hence, they have proven to be a successful
platform for the assessment of potential low GWP alternative working
fluids, primarily due to very limited computational requirements when
compared with molecular simulations, while showing excellent extrapolative
and predictive power.[54−58]In this contribution, we present for the first time a robust
framework
for rapidly assessing the feasibility of replacing single-component
third generation refrigerants HFCs with low GWP fourth generation
refrigerants HFOs and HCFOs, connecting features of their molecular
structure to their performance. The framework is built on the use
of a molecular-based EoS, namely, polar soft-SAFT,[66] for the holistic thermodynamic characterization of the
investigated refrigerants. Once the accuracy of the model is established
through comparison with available experimental data, the compatibility
of third generation refrigerants with their low GWP fourth generation
replacements is determined through a drop-in analysis with the objective
of minimal retrofitting to the existing system. This analysis is done
using technical criteria computed from properties predicted by the
thermodynamic model. In addition to these technical criteria, the
compatibility of refrigerants is examined in terms of molecular characteristics
obtained from the model.
Methodology
Selected Technical Criteria
for the Drop-in Assessment
Taking third generation refrigerants
as benchmarks, it is granted
that their fourth generation replacement should satisfy imposed environmental
criteria[7] including low GWP (<150),
non- or very low ODP < 0.01, null toxicity (A), and either non-
or midflammability (1 or 2 L). These constraints are applicable to
all fourth generation refrigerants examined in this work, with the
exception of R1243zf, being highly flammable (2), as provided in Table
S1 in the Supporting Information (SI).Toward assessing the compatibility of fourth generation drop-in replacements,
several technical criteria can be included, granted that the technical
assessment is done under the same refrigeration cycle and operating
conditions. The performance of third generation HFCs and their fourth
generation replacements HFOs and HCFOs is assessed in this work using
a vapor compression refrigeration cycle as the showcase, displayed
in Figure . The cooling
process is comprised of a single-stage compressor, condenser, evaporator,
and thermostatic expansion valve (TXV). The cycle starts with the
isentropic compression of the refrigerant (1–2), with the superheated
vapor flowing through the condenser, and releasing its sensible (2–3)
and latent (3–4) heats to surrounding air to reach the saturation
temperature at the condenser’s pressure (2–4). Subsequently,
the saturated liquid is expanded resulting in two phase vapor–liquid
mixture, with the TXV regulating the refrigerant mass flow rate (4–5),
routed to the isobaric evaporator with the refrigerant reaching its
saturated vapor phase (5–1). The implementation of the VCRC
requires assumptions on the process conditions such as, steady-state
flow, fixed evaporator temperature (Tevap = 270 K), fixed condenser temperature (Tcond = 300 K), negligible heat transfer in piping, negligible superheating
and subcooling effects, zero pressure drop and isobaric conditions
in both condenser and evaporator, ideal isentropic efficiency in the
compressor, and isenthalpic flow across the TXV, in a manner consistent
with our previous work.[67] These conditions
were chosen to simulate a cooling cycle with a medium evaporation
temperature (i.e., in the range of 268–283 K)[68] and a lift temperature of 30 K[69] to prevent heat cross between external heat sink and the corresponding
heat source.[70]
Figure 1
Process flow diagram
of the vapor compression refrigeration cycle
(VCRC) studied in this work.
Process flow diagram
of the vapor compression refrigeration cycle
(VCRC) studied in this work.The chosen technical criteria for evaluating compatibility of drop-in
replacements include volumetric cooling capacity (VCC), and coefficient
of performance (COP). The VCC refers to the amount of cooling per
unit volume of the vapor refrigerant at the evaporator outlet, computed
aswhere RE is the refrigeration effect as the
difference between the enthalpies of the refrigerant at evaporator
outlet and inlet, while ρV is the density of the
saturated vapor exiting the evaporator, otherwise known as suction
density.Conversely, the COP quantifies the overall efficiency
of the refrigeration
cycle, expressed as the cooling effect produced per unit of work,
aswhere wc is the
actual compressor work, wcs is the specific
work required by the compressor, and η is the real compressor
efficiency, which in this work is assumed to be ideal (i.e., η
= 1.0). The computations of these criteria require pressure-enthalpy
(PH), and temperature-entropy (TS) diagrams and physicochemical properties
predicted using polar soft-SAFT for all studied refrigerants, under
the imposed conditions of the cooling cycle.Refrigerants are
deemed compatible if the values of their VCC are
similar, denoting equivalent refrigerant volume handled by the compressor
without need for compressor retrofitting. Additionally, the replacement
refrigerant should possess either a similar or higher COP value compared
to the refrigerant to be replaced, denoting either a similar or higher
cycle efficiency. For the most compatible refrigerants, other properties
with impact on technical performance are examined to gain additional
insight on other possible technical trade-offs. These properties include
normal boiling point (NBP), condenser pressure (Pcond), suction density (ρV), liquid specific
heat (c), and refrigeration effect (RE).
The normal boiling point measures the ease of vaporizing the refrigerant
upon absorbing heat, which should be minimized for low-medium temperature
applications, as high NBP would require operating the compressor at
low pressures or even vacuum to facilitate vaporization, at the expense
of higher operating costs. Similarly, the condenser pressure should
also be minimized to reduce the compression power and the operating
costs, while the suction density relates to the density of the saturated
vapor exiting the evaporator, which should be maximized to reduce
the size of the compressor and required capital costs. The specific
heat of the refrigerant at liquid state represents the amount of
heat required to increase the temperature of the refrigerant by one
temperature unit (e.g., 1 K), with lower specific
heat being preferred as it reduces the amount of heat required to
change the temperature of the refrigerant. This is defined as the
enthalpy difference of the saturated liquid leaving the condenser
at Tcond (Hcond,out) and the subcooled liquid leaving the condenser at (Tcond – 1 K) (Hcond,out–1) at isobaric conditions.Lastly, the refrigeration
effect is a measure of the amount of
latent heat absorbed in the evaporator, corresponding to the cooling
capacity of the refrigerant, which should be maximized to ensure higher
extracted heat or lower refrigerant mass flow rates.It is important
to remark that all systems discussed in this contribution
require the use of polyolester (POE)-based lubricant oils, more precisely
pentaerythritol esters (PECs), to ensure miscibility, lubricity, and
chemical stability of the resulting refrigerant–PEC oil pair.
All of the examined drop-in replacements are compatible with PEC;
otherwise, a thorough refrigerant–PEC oil compatibility analysis
would be required.[67]
Polar Soft-SAFT
Equation
All thermophysical properties
of the selected refrigerants considered in this work have been modeled
using the polar soft-SAFT Equation of State (EoS),[66] an extension of the original soft-SAFT equation.[71,72] Within the framework of polar soft-SAFT,[66] the residual Helmholtz energy (ares)
of a pure fluid is represented as the sum of various microscopic contributions
accounting for its different molecular features, expressed asThe reference term (aref) denotes
the contribution arising from repulsive and
dispersive interactions between individual segments of the reference
fluid (a Lennard-Jones (LJ) intermolecular potential). The chain term
(achain) refers to the contribution resulting
from the formation of chains through connectivity of individual segments,
while the association term (aassoc) takes
into account the highly directional and short-range interactions such
as hydrogen-bonding. Lastly, the polar term (apolar) explicitly accounts for the contribution from multipolar
interactions such as a permanent dipole or quadrupole. The reader
is referred to the original contributions for additional details on
the expressions of soft-SAFT and its polar extension.[46,47,66,71−73]The application of polar soft-SAFT to molecular
systems entails
describing a pure fluid using a coarse-grained representation of its
key structural and energetic features, captured through a specific
set of molecular parameters. Generally, the model contains a maximum
of seven molecular parameters to describe pure fluids, although in
most of the cases three or five molecular parameters are used, depending
on the governing intermolecular interactions. The most essential parameters
required for any pure chain-like fluid include the chain length (m), LJ segment diameter (σ), and LJ segments dispersive energy (ε). Two additional parameters are needed to model
fluids capable of hydrogen bonding, one related to the volume (κα–β, HB) and a second one taking into account
the energy of association (εα–β, HB). Alternatively, modeling
fluids with dipolar or quadrupolar interactions requires, in addition
to m, σ, and ε, two extra
parameters, which are the dipole/quadrupole moment (μ/Q), and the fraction of segments affected by the polar moment
(x). Typically, these polar molecular
parameters are either fixed a priori based on physical
arguments or regressed to the saturated liquid density and vapor pressure
of the pure fluid. Hence, for polar compounds, such as those studied
in this work, only m, σ, and ε are fitted to experimental data, usually vapor–liquid
equilibria.In this work, a total of 18 different pure refrigerants
were studied,
provided in Table . The studied refrigerants include 10 of the most commonly used single-component
third generation refrigerants, along with eight fourth generation
refrigerants with demonstrated potential as low GWP alternatives.
Although other fourth generation refrigerants have been recently synthesized,
some of their environmental and safety properties and thermodynamic
properties required for molecular model parametrization are missing,
hence, their exclusion from the current work.
Table 1
Summary
of Refrigerants Modeled in
This Work, with Their Commercial Name in Bold and CAS No. in Italic
The polar soft-SAFT coarse-grained
molecular model of these fluids
represents them as homonuclear nonassociating LJ chain-like fluids
with explicit consideration of their dipole moment, with three representative
examples from each family provided in Figure . The polar treatment is required due to
the presence of halogen atoms (i.e., fluorine, chlorine) in these
molecules, leading to the formation of permanent dipole moments arising
from the asymmetrical charge distribution. Such explicit treatment
is paramount as it ensures high predictive accuracy in modeling pure
polar fluid properties and their multicomponent mixtures as demonstrated
for other polar fluids in our earlier contributions.[46,47,66,73] It should be noted that the association term was not included, as
the dipolar nature of these refrigerants is far more influential on
their thermodynamic behavior.
Figure 2
Selected pure refrigerants modeled in this work,
with their molecular
structure and corresponding polar soft-SAFT coarse-grained molecular
model. The beige spheres denote the segments affected by the dipole
moment, needed to estimate the fraction of dipolar segments (x).
Selected pure refrigerants modeled in this work,
with their molecular
structure and corresponding polar soft-SAFT coarse-grained molecular
model. The beige spheres denote the segments affected by the dipole
moment, needed to estimate the fraction of dipolar segments (x).For the required polar molecular parameters, the dipole moment
(μ) was fixed to the experimental value in vacuum, while the
fraction of dipolar segments (xp) was
determined a priori based on a physical argument
taking into account the molecular charge distribution.[46,66] With this approach, the robustness of the model is preserved, as
only three parameters (i.e., σ, m, ε) need to be fitted to pure refrigerant experimental saturated
liquid density and vapor pressure. Subsequently, these parameters
can be used to predict thermodynamic properties required for technical
evaluation and even extended to obtain phase equilibria and properties
of their multicomponent mixtures. The parametrization of the pure
refrigerants has been done using the soft-SAFT proprietary software
developed and validated over the past two decades.[74]
Results and Discussion
Polar Soft-SAFT Characterization
of HFCs, HFOs, and HCFOs
Toward assessing the compatibility
of low GWP refrigerants as drop-in
replacements, their thermodynamic behavior needs to be characterized,
which has been done in this work using polar soft-SAFT EoS. As previously
highlighted, the CG molecular models of the examined refrigerants
explicitly account for dipolar interactions governing their
macroscopic behavior. The optimized polar soft-SAFT parameters for
the examined pure refrigerants are provided in Table , using the parametrization approach highlighted
in the methodology section. Notice that these are nonassociating fluids;
hence, aassoc in eq is neglected in all calculations.
Table 2
Polar Soft-SAFT Molecular Parameters
for HFCs, HFOs, and HCFOs Studied in This Work
Compound
m
σ (Å)
ε/kB (K)
μ × 10–30 (C m)a
xp
AADPb (%)
AADρc (%)
T range (K)
HFCs
R41
1.371
3.400
180.3
6.17427
0.50
1.494
0.763
200–280
R32
1.376
3.506
164.5
6.59790
0.75
0.565
0.255
200–316
R23
1.397
3.610
147.9
5.50047
0.90
1.327
0.155
200–270
R161
1.577
3.693
232.3
6.47014
0.33
1.374
0.414
200–340
R152a
1.662
3.754
202.3
7.54522
0.50
0.993
0.792
200–356
R134a
1.813
3.770
169.5
6.86475
0.70
1.443
0.389
200–344
R125
1.887
3.790
165.1
5.21360
0.90
1.618
0.274
200–310
R245fa
2.479
3.675
197.1
5.16690
0.80
1.593
0.596
230–395
R236fa
2.056
4.012
172.4
6.61124
0.90
2.410
0.554
270–370
R227ea
2.131
4.033
190.7
4.85669
1.00
4.224
0.260
230–345
HFOs
R1123
1.527
3.760
175.3
5.73730
0.80
2.963
0.199
230–300
R1243zf
1.904
3.880
170.0
8.16890
0.50
1.092
0.295
270–345
R1234yf
1.740
4.082
191.6
6.70790
0.70
1.150
0.314
250–331
R1234ze(E)
2.044
3.821
204.0
4.80330
0.75
3.016
0.555
250–351
R1225ye(Z)
2.077
3.845
172.4
6.03750
0.80
1.018
0.260
250–355
R1336mzz(Z)
1.806
4.430
195.6
10.6406
0.60
3.287
0.565
325–415
HCFOs
R1233zd(E)
2.331
3.819
232.6
3.81190
0.80
2.936
0.506
250–400
R1224yd(Z)
2.278
3.899
202.4
5.63720
0.85
1.358
0.237
280–375
Experimental dipole moments.[54,61,75−78]
Experimental vapor pressure from
refs (75, 79−84).
Experimental saturated
densities
from refs (75, 79, 80, 82, 84−87).
Experimental dipole moments.[54,61,75−78]Experimental vapor pressure from
refs (75, 79−84).Experimental saturated
densities
from refs (75, 79, 80, 82, 84−87).The adequacy of these
regressed parameters can be established through
comparing polar soft-SAFT calculations for coexisting densities and
vapor pressure against experimental data[75,79−87] used in the parametrization procedure, as provided in Figure , for selected fourth generation
refrigerants (HFOs and HCFOs). These parameters accurately capture
the experimental trends for these properties with an average deviation
for saturated liquid density (AAD% ρLSat.) below 0.80% in all cases, while for vapor pressure,
the average absolute deviation (AAD% PSat.) is below 2% in most cases, with some few exceptions that are within
an acceptable 4.5%. It should be noted that in the vicinity of the
critical region, polar soft-SAFT overestimates the critical properties
of the pure fluids, due to the mean-field formulation of the theory.
This limitation is shared by all SAFT-based EoSs and can be solved
through the addition of the crossover term,[88] which is outside the scope of this work. Similar model performance
was obtained for third generation HFCs, with their polar soft-SAFT
computed coexisting densities and vapor pressure included in Figure
S1 in the SI
Figure 3
Coexisting densities
(top) and vapor pressure (bottom) of pure
HFOs and HCFOs studied in this work, with polar soft-SAFT calculations
using parameters from Table (solid lines) compared to experimental data (symbols). References
for the experimental data are provided in Table .
Coexisting densities
(top) and vapor pressure (bottom) of pure
HFOs and HCFOs studied in this work, with polar soft-SAFT calculations
using parameters from Table (solid lines) compared to experimental data (symbols). References
for the experimental data are provided in Table .
Effect of Refrigerants Molecular Features on Their Physicochemical
Properties
The advantage of the previously optimized parameters
is their physical meaning, related to the size and energy of the molecule,
allowing extraction of molecular features, and understanding their
effect on macrolevel properties. This is of paramount importance as
it helps in guiding experimental efforts in the synthesis of alternative
refrigerants with desirable physicochemical properties affecting the
technical efficacy of the working fluids in their intended applications.The change in the liquid density of the studied refrigerants, predicted
at T = 250 K, is closely related to the volume occupied
by the molecule (mσ3) as provided
in Figure . The increase
in molecular volume results in lower liquid molar densities, which
also means higher vapor molar densities. This change is dependent
on structural features such as the number of carbons in the chain,
number and type of halogenated atoms, and the type of carbon–carbon
bonds, with varying degrees of contribution. The most notable structural
features with distinct impact on the size of the molecule are the
carbon number and degree of halogenation, with their increase leading
to increased magnitude for molecular volume, as seen in the case of
the single carbon R41, R32, and R23, with increasing fluorine atoms,
as well as for increasing number of carbons seen in case of R32 and
R152a (both with two fluorine atoms).
Figure 4
Effect of molecular volume on predicted
molar liquid density at T = 250 K for refrigerants
using polar soft-SAFT. Notice
that the size of the sphere reflects the molecular volume as shown
in the heat scale.
Effect of molecular volume on predicted
molar liquid density at T = 250 K for refrigerants
using polar soft-SAFT. Notice
that the size of the sphere reflects the molecular volume as shown
in the heat scale.Less noticeable effects
are associated with the presence of double
bonds vs single bonds, the type of halogen atom, and their position
in the molecule. The presence of double bonded carbons marginally
reduces the molecular size as opposed to single-bonded carbons, due
to their lower bond length, as seen for the unsaturated R1225ye(Z)
compared to the saturated R245fa. In similar notions, the presence
of chlorine marginally increases the molecular size due to its larger
atomic radius compared to the fluorine atom, observed for the R1234ze(E)
HFO and its counterpart R1233zd(E) HCFO.On the basis of these
trends, and in view of the objective of maximizing
the suction density of the refrigerant (vapor phase), it can be expected
that larger refrigerants such as R227ea can be an adequate refrigerant
judging solely by this criterion, reflective of smaller compressor
sizing.It should be noted that, for practical applications,
the analysis
can be done on the basis of liquid mass densities, with similar results
albeit reversed trends, with refrigerants with lower molecular volumes
having lower liquid mass densities consistent with their lower molecular
weights.To better elucidate the importance of explicitly accounting
for
the polarity of the refrigerants investigated herein, the relative
contribution of the different terms (i.e., LJ reference, chain, and
polar) to the residual Helmholtz free energy (eq ) were predicted from the thermodynamic model
at T = 250 K and P = 0.1 MPa, as
provided in Figure .
Figure 5
Relative contribution of the various terms (LJ reference, chain,
and polar) to the residual Helmholtz energy (ares) in the CG models for HFCs (top), HFOs, and HCFOs (bottom)
predicted from polar soft-SAFT at T = 250 K and P = 0.1 MPa.
Relative contribution of the various terms (LJ reference, chain,
and polar) to the residual Helmholtz energy (ares) in the CG models for HFCs (top), HFOs, and HCFOs (bottom)
predicted from polar soft-SAFT at T = 250 K and P = 0.1 MPa.For the majority of the
refrigerants, the polar contribution to
the Helmholtz energy has a large impact in the range of 25%–67%,
with the exception for R1233zd(E) and R161, clearly demonstrating
the importance of explicitly including the effect of dipolar interactions
in their CG molecular models. These predictions can help in understanding
the relative importance of the different intermolecular interactions
on the physicochemical properties, similar to the aforementioned case
with density. For saturated HFCs with similar carbon number such as
R161, R152a, R134a, and R125 (all with two carbon atoms), the increasing
degree of fluorination is accompanied with increased contribution
of dipolar interactions compared to dispersive, provided in Figure (top). This is distinctly
seen moving from R161 (1 F) and R152a (2 F) to R134a (4 F), associated
with the assumed increase in molecular segments influenced by the
dipole moment (mxp). Notice that the move
from R134a (4 F) to R125 (5 F) resulted in a reduction in the polar
contribution attributed to the reduced dipole moment of the latter
owing to the effect of the additional fluorine atom on making the
charge distribution more symmetrical. The same trends were also observed
for HFCs with one carbon atom (i.e., R41, R32, and R23), and three
carbon atoms (i.e., R245fa, R236fa, and R227ea).Shifting the
focus on the effect of the carbon number with similar
degrees of halogenation, R41 vs R161 (1 fluorine atom) and R32 vs
R152a (two fluorine atoms), it is observed that the polar contribution
decreases with increasing carbon chain length, as the increased size
of the molecule (Figure ) reduces the portion of the molecule influenced by the dipole moment,
irrespective of its magnitude. This behavior has also been previously
observed for the 2-ketones family.[66]The effect of the degree of fluorination is quite different in
the case of unsaturated HFOs and HCFOs, shown in Figure . For HFOs with a similar carbon
number (i.e., three carbons) such as R1243zf, R1234yf, R1234ze(E),
and R1233zd(E), the polar contribution is reduced with increasing
the degree of fluorination. This can be associated with the higher
polarizability of the double bonded carbons compared to single-bonded
carbons, leading to a more symmetrical charge distribution, dampening
the effect of the dipole moment. The type of halogen atom also has
an influence on the polar contribution, with HCFOs having a lower
impact compared to their HFOs counterparts (i.e., R1233zd(E) vs R1234ze(E)),
consistent with the lower electronegativity of chlorine compared to
fluorine. Also, notice the effect of the position of fluorine atoms
seen in the case of R1234yf vs R1234ze(E), with the increased polar
contribution of R1234yf due to the proximity of the isolated fluorine
to the fully fluorinated carbon, increasing the overlapping electrostatic
potential and, consequently, the polarity of the molecule.These
molecular tendencies will manifest on properties such as
vapor pressure and enthalpy of vaporization. For example, the low
vapor pressure for R1336mzz(Z) is due to its high dipole moment resulting
in the highest polar contribution (Figure ). Still, it remains quite difficult to distinctly
isolate the effect of polar interactions on these properties as they
are affected by the combined contribution of structural effects and
intermolecular interactions. Note that the contributions reported
in Figure are relative
rather than absolute, normalized to each refrigerant’s residual
energy.
Validation of Refrigerant Coarse-Grained Molecular Models
The strength of using molecular-based EoSs, even if some limited
experimental data are needed for parametrization, is that once the
CG molecular models are developed, they can be used in a fully predictive
manner to obtain other thermodynamic properties not included in the
parametrization. These predictions typically serve as another layer
of reliability and accuracy testing, especially in the case of first
and second order derivative properties, due to their heightened sensitivity
to errors in modeling the vapor–liquid equilibria (VLE) of
the pure fluid.[89,90] Additionally, explicit inclusion
of dipole–dipole interactions in the model is paramount for
accurate predictions of these derivative properties, as demonstrated
in other contributions.[48,66]The additional
predicted properties for the modeled refrigerants, include enthalpy
of vaporization (ΔHvap), single-phase
density, isobaric heat capacity (CP),
and speed of sound (ω), as provided in Figure , for selected fourth generation refrigerants,
R1234yf, R1234ze(E), and R1233zd(E), while those for the remaining
refrigerants can be found in Figures S2–S5 in the SI. It should be noted that predictions for the
isobaric heat capacity require the inclusion of the ideal gas isobaric
heat capacities (CpIG), obtained
from available literature data.[75,91] The agreement between
polar soft-SAFT predictions and experimental data[75,92−94] is excellent (AAD = 1.5%) for enthalpy of vaporization,
single-phase density, and speed of sound, while the deviations for
predicted isobaric heat capacity are within an acceptable 5%, further
attesting the accuracy and predictive capability of the equation in
modeling refrigerants. The enthalpy of vaporization is another measure
for the strength of the intermolecular interactions, with higher values
reflective of stronger intermolecular interactions, as seen in the
case of R1233zd(E), with its larger dipole moment and higher dipolar
molecular segments compared to the others, requiring more energy to
transition the molecule from liquid to vapor phase. Additionally,
the change in single-phase densities for the three refrigerants is
consistent with their molecular volumes (Figure ), with R1233zd(E) having the lowest single-phase
density due to its larger molecular volume compared to the former
two.
Figure 6
Thermodynamic properties of low GWP refrigerants, including (a)
enthalpy of vaporization, (b) single-phase density, (c) isobaric heat
capacity, and (d) speed of sound, for R1234ze(E), R1234yf, and R1233zd(E),
with polar soft-SAFT predictions (solid lines) compared to experimental
data[75,92−94] (symbols).
Thermodynamic properties of low GWP refrigerants, including (a)
enthalpy of vaporization, (b) single-phase density, (c) isobaric heat
capacity, and (d) speed of sound, for R1234ze(E), R1234yf, and R1233zd(E),
with polar soft-SAFT predictions (solid lines) compared to experimental
data[75,92−94] (symbols).The last demonstration of the accuracy of the model in capturing
the effect of dipolar interactions is demonstrated through predicting
the VLE for binary mixtures of dipolar + nonpolar fluids. In this
manner, the ability of the model to correctly approximate the contribution
of dipole–dipole interactions can be isolated, as dipole interactions
have a larger effect on the nonideality of their VLEs with nonpolar
fluids.[46,47] For this end, binary mixtures of dipolar
refrigerants with nonpolar n-alkanes (modeled as
a chain-like LJ fluid, using parameters included in Table S2 in the SI)[74] were predicted
from the thermodynamic model for mixtures including ethane with R23
or R1234ze(E) and n-butane with R32, R152a, R134a, and R1234yf as
dictated by available experimental data.[95−100] Indeed, the agreement between the experimental VLE data and model
predictions is excellent with AADs = 1.0%, as seen in Figure , merely from the accurate
representation of the behavior of the pure refrigerants.
Figure 7
Predicted VLE
for binary mixtures of (a) ethane + R23, (b) ethane
+ R1234ze(E), (c) n-butane + R134a or R1234yf at T = 323 K, and (d) n-butane + R32 or R152a
at T = 293 K. In all cases, polar soft-SAFT predictions
(solid lines) are compared to experimental data[95−100] (symbols).
Predicted VLE
for binary mixtures of (a) ethane + R23, (b) ethane
+ R1234ze(E), (c) n-butane + R134a or R1234yf at T = 323 K, and (d) n-butane + R32 or R152a
at T = 293 K. In all cases, polar soft-SAFT predictions
(solid lines) are compared to experimental data[95−100] (symbols).These behaviors can also be better
explained from the microlevel
insights provided in Figure . For binary mixtures with ethane, the prominent polar contribution
of R23 resulted in the formation of a distinct azeotropic mixture
at nearly equimolar concentrations, while the lower polar contribution
of R1234ze(E) due to its larger molecular volume resulted in an almost
ideal VLE behavior. Conversely, the formation of azeotropes at high
refrigerant concentrations was seen for all binary mixtures with n-butane, with the degree of nonideality associated with
the magnitude of the polar contributions of the refrigerant. For saturated
R134a, its high polarity compared to R1234yf resulted in a more distinct
positive azeotrope, due to the increased asymmetrical energy scale
between the stronger polarity of R134a with the nonpolar n-butane. Notice, both refrigerants possess relatively similar dipole
moments and fraction of polar segments; however, the larger molecular
volume of R1234yf contributes to reducing its overall dipolar interactions.
A similar observation is seen in the case of R32 and R152a, with a
higher deviation from nonideal behavior for mixture with R32 manifested
in the form of a larger spread for the VLE. Even though the magnitude
of the dipole moment of R152a is higher than R32, still its larger
size reduces the portion of the molecule influenced by the dipole
moment.
Drop-In Assessment for Low GWP Refrigerants
In this
section, we present results on the drop-in assessment for the most
compatible low GWP fourth generation refrigerants as replacements
for the currently used third generation refrigerants. The assessment
is done employing the technical criteria highlighted in the methodology
for the examined VCRC systems. The PH- and TS-diagrams for all the
pure refrigerants as predicted from polar soft-SAFT EoS, under the
imposed operating conditions for the VCRC, for all the examined refrigerants
are shown in Figures S6 and S7 in the SI. The values for the ideal gas enthalpy (HIG), and entropy (SIG) required for these
predictions from the thermodynamic model were taken from literature.[75] Moreover, all other physicochemical properties
needed to complete the assessment were also obtained from polar soft-SAFT
in a predictive manner.The most convenient criterion for analyzing
compatibility of drop-in replacements would be merely using VCC under
the same VCRC operating conditions, as currently implemented in most
works on searching for alternative refrigerants.[83,101,102] Similar VCC values between benchmark
third generation refrigerant, and low GWP fourth generation replacement
signifies their compatibility without the need to retrofit units in
existing refrigeration cycle, in particular the compressor.[103]Prior to implementing this criterion,
it is worthwhile to test
the validity of VCC predictions using polar soft-SAFT EoS (eq ). This is done through
linearly correlating predicted VCC values with the critical properties
(i.e., critical temperature and pressure) of the pure refrigerants,[104] indicating the accuracy of the predicted VCC
values. The critical properties for each refrigerant were obtained
from the literature,[75,81−83,105−108] while VCC were directly predicted from polar
soft-SAFT. As provided in Figure , the predicted VCC values and critical properties
of the studied refrigerants indeed followed a linear correlation (R > 0.997), with the exception
of R23. This outlier was expected as the critical temperature of R23
(Tc = 299.29 K) is very close to the condenser
operating temperature for the VCRC (Tcond = 300 K). It should be noted that a refrigerant with a low-critical
temperature such as R23 most likely would require the use of a transcritical
cycle if operated at medium-temperature conditions.[109] Notwithstanding, this simple test affirms the accuracy
and predictive power of polar soft-SAFT in capturing the behavior
of key technical criterion for evaluating the compatibility of drop-in
replacements.
Figure 8
Correlation for polar soft-SAFT predicted VCC values of
refrigerants
examined in this work and their experimental critical properties from
the literature.[75,81−83,105−108]
Correlation for polar soft-SAFT predicted VCC values of
refrigerants
examined in this work and their experimental critical properties from
the literature.[75,81−83,105−108]Highlighted in Figure are the most compatible fourth generation refrigerants with
the 10 third generation single-component refrigerants (HFCs) as benchmarks.
It can be seen that for some distinct cases, such as those for replacing
R32, R152a, R134a, and R245fa, fourth generation refrigerants are
nearly compatible as drop-in replacements using working fluids such
as R1123, R1234yf, and R1224yd(Z), with their VCC values being within
10% of those for the benchmark refrigerants to be replaced. Conversely,
other refrigerants are available, such as replacing R41 or R23 with
R1123; however, the low VCC value of R1123 indicates that the refrigeration
cycle needs to be retrofitted. These dissimilar VCC values require
an increase in the compressor size for equivalent volumes of compressor-displaced
refrigerant. In this aspect, rational design of refrigerant blends
might prove efficient for the replacement of those refrigerants without
compatible low GWP single refrigerants. This assessment has also been
done at different evaporator and condenser temperatures to evaluate
their impact, as included in Figure S8 in the SI, yielding relatively similar outcomes to the most compatible
fourth generation drop-in replacements. Notice the effect of increasing
the lift temperature on decreasing the corresponding VCC values.
Figure 9
Compatibility
test for replacing third generation refrigerants
with fourth generation refrigerants based on polar soft-SAFT predicted
VCC shown in Figure . The dashed line denotes similar VCC for third generation benchmark
and its fourth generation drop-in replacement.
Compatibility
test for replacing third generation refrigerants
with fourth generation refrigerants based on polar soft-SAFT predicted
VCC shown in Figure . The dashed line denotes similar VCC for third generation benchmark
and its fourth generation drop-in replacement.On the basis of the previous compatibility assessment, we further
investigate drop-in replacements for R32, R152a, R134a, and R245fa,
inclusive of other technical criteria often overlooked. This is done
through estimating the corresponding trade-off between COP versus
VCC as well as a thorough review of their main thermophysical properties.
The drop-in assessment is performed considering potential drop-in
replacements with VCC and COP values within 25% of the reference refrigerant
to be replaced. It should be mentioned that for R1336mzz(Z) and R1224yd(Z),
the COP is predicted as an average based on available experimental
data under similar conditions,[110,111] due to the nonavailability
of isothermal ideal gas entropies needed to compute the TS-diagrams
involved in the COP calculations. The COP values for these refrigerants
are within those obtained for highly efficient refrigerants R1233zd(E)
and R245fa. Moreover, the outcome of this evaluation has been done
at arbitrary conditions, which may not be optimal for each refrigerant.
However, the results established the benefit associated with the evaluation
platform developed in this work for the rapid assessment of drop-in
replacement refrigerants, allowing a more targeted evaluation and
optimization for the most promising ones.The initial focus
for the detailed drop-in analysis was on R134a,
shown in Figure , being the most widely used working fluid in a diverse range of
applications such as domestic refrigerators, commercial chillers,
stationary refrigeration equipment, and medium temperature mobile
air conditioning systems, with the urgent need to find a suitable
replacement.[6,7,112,113] Among the examined possible replacements,
R1234yf and R1243zf, as well as R1234ze(E) and R1225ye(Z) to a lesser
extent, emerged as attractive options solely based on their technical
performance with nearly similar VCC values, albeit more reduced COP.
This might demonstrate that their usage has the possibility of not
incurring additional capital cost associated with altering the design
of the compressor but on the expense of reduced system efficiency,
which can be acceptable (performance drop inferior to 3.2% in all
cases) considering their significantly lower GWP. Judging by additional
technical criteria, R1234yf is indeed an attractive technical option
with the limited need for adjusting the design of the compressor as
supported by its NBP, its suction density being higher than that for
R134a, and relatively similar condenser operating pressure and liquid
specific heat. Briefly, it might seem that the incurred costs might
be mainly operational due to the higher energy demand for compression,
as demonstrated from its lower RE. On another front, especially with
the inclusion of the flammability of these options, it is established
that R1225ye(Z) might prove a better option owing to its safer operation
due to its nonflammable nature (similar to that of R134a) as opposed
to the mildly flammable R1234yf (though more technically compatible)
or the highly flammable R1243zf, which would be reflected on the cost
needed for the installation of additional safety layers. This exemplifies
the difficulty in finding a single-component refrigerant encompassing
environmental/safety requirements and technical performance.
Figure 10
Drop-in analysis
for replacing R134a based on VCC and COP benchmarked
to R134a (left), including other technical criteria relative to R134a
for promising replacements (right). See text for details.
Drop-in analysis
for replacing R134a based on VCC and COP benchmarked
to R134a (left), including other technical criteria relative to R134a
for promising replacements (right). See text for details.Recent publications[32,114] on searching for replacements
for R134a (GWP = 1300)[115] indicated the
promising use of the third generation refrigerant R152a (GWP = 138)[115] for oil-free automotive air conditioning, guided
by its lower GWP, low cost, and minimal equipment change. Nonetheless,
its highly flammable nature is a concern; hence, based on the outcome
of the analysis in this work, R1225ye(Z) (GWP = 3[115] and with nonflammability 1) is a more competent alternative
to replace R134a, as opposed to R152a. The required modifications
might include enlarging the compressor rotation speed or use of an
internal heat exchanger (IHX) to ensure similar operation to cycles
using R134a.[116] Other hardware modifications
can be included such as tuning the TXV (Figure ) and setting up a variable displacement
compressor control valves, which cannot be exceedingly expensive if
compared to a complete system redesign.[26] It is worth remarking that for drop-in replacements with higher
flammability such as the case for R1234yf, safe operation can be ensured
through reducing the refrigerant load in the cooling cycle.[117]In line with the previous analysis, the
ability of drop-in replacements
for other third generation refrigerants R32, R152a, and R245fa is
included in Figure , to demonstrate the flexibility of the approach proposed in this
work. In the current market, R32 (GWP = 677)[115] is used as a medium-GWP drop-in replacement to R410A (GWP = 2088),[115] which will also be phased out soon. The most
compatible drop-in replacement for R32 proved to be R1123, with a
relatively similar VCC value, albeit an 8.2% reduction in its COP.
Although other fourth generation refrigerants have similar COPs to
R32, their significantly lower VCCs indicated the need to fully retrofitting
systems operating with R32. Notwithstanding, the prospect analysis
of using R1123 as a drop-in replacement for R32 in terms of other
KPIs showed that the only concerning factors would be the higher condenser
pressure and lower RE of R1123, translated to increased operating
costs. Moreover, the nonflammability of R1123 would not require any
adjustments in the pre-existing risk control measures.
Figure 11
Drop-in analysis
for replacing R32, R152a, and R245fa with fourth
generation refrigerants, based on VCC and COP benchmarked to each
refrigerant (left), including other technical criteria relative to
each refrigerant (right). See text for details.
Drop-in analysis
for replacing R32, R152a, and R245fa with fourth
generation refrigerants, based on VCC and COP benchmarked to each
refrigerant (left), including other technical criteria relative to
each refrigerant (right). See text for details.The working fluid R152a is currently deployed in cascade refrigeration
configurations with transcritical CO2; however, even though
its GWP is within acceptable environmental requirements, its high
flammability is a concern, requiring its immediate replacement.[118−120] In the case of drop-in replacement for R152a, several options are
available including R1234yf, R1243zf, R1234ze(E), and R1225ye(Z),
with comparable VCCs and nearly 6.0% reduction in COPs. Although R1234yf
seemed like a good option judging solely on its VCC and safety concerns,
other technical criteria showed a reduced performance compared to
R152a. On the other hand, a better compromise on COP, liquid specific
heat, and condenser pressure is achieved when employing R1234ze(E)
and R1225ye(Z) as drop-in replacements.Lastly, R245fa is considered
as the reference working fluid for
high-temperature heat pumps and organic Rankine cycles.[121] For replacing R245fa, high-NBP fourth generation
refrigerants such as R1224yd(Z) and R1233zd(E) were found to be appropriate,
along with demonstrated enhanced COP. These refrigerants are more
applicable to high-temperature air condition applications or systems
operating under low-pressure centrifugal configurations, due to their
similar saturated vapor pressures and critical properties, promising
high efficiency and reduced VCCs.[25,109] The most
compatible option would be R1224yd(Z) owing to its improved COP and
suction density resulting in enhanced cooling cycle efficiency, while
reducing the mass flow rate of the working fluid in the compressor
line. Moreover, R1224yd(Z) as a drop-in replacement maintains relatively
similar VCC, condenser pressure, RE, and normal boiling point, without
incurring any costs for system retrofitting. Larger improvements are
gained with this drop-in replacement owing to its low GWP, along with
its nonflammable nature and lower toxicity. Similar findings were
demonstrated by Mateu-Royo et al.[101] reinforcing
the potentiality of R1224yd(Z) as an attractive replacements for R245fa.
Notice that for R245fa drop-in assessment, the NBP performance is
computed with reference to its maximization owing to its use in high-temperature
applications, as opposed to the low-medium temperature application
of the aforementioned cases when finding replacements for R134a, R32
and R152a.All these possible alternatives can be rationalized
in view of
their microlevel features. Notice that the replacements of a third
generation with a fourth generation refrigerant is possible for those
with similar structural characteristics such as carbon number and
degree of fluorination. For example, compatibility of R134a and R152a
with R1234yf is due to them being within the same molecular space
in terms of carbon number and degree of fluorination, with a fine
balance between structure and energy affecting the thermodynamic properties.
Their similar VCC values relative to R134a or R152a are due to the
reduced vapor density of the replacements (owing to their slightly
larger molecular volume), compensated with their increased enthalpy
due to their higher polarity. Shifting farther from these structural
features, such as seen in the case of the larger and less polar HCFOs
such as R1224yd(Z) and R1233zd(E), skewed the fine balance of molecular
features on their properties compatible with R134a or R152a. Furthermore,
they proved to be compatible with R245fa due to similar structural
characteristics.The outcome of this analysis clearly demonstrates
not only the
power of polar soft-SAFT as a robust and predictive thermodynamic
model enabling the systematic evaluation of next generation refrigerants
but also its capability of providing molecular level insight on the
influence of structure and interactions on the compatibility of drop-in
replacements. As such, future efforts on the synthesis of alternative
replacements should build on the molecular features of the refrigerant
to be replaced, by ensuring that the replacement maintains relatively
similar features within the same molecular space.
Conclusions
In this work, polar soft-SAFT molecular-based equation of state
was used as a platform to rapidly assess the suitability of fourth
generation refrigerants over their third generation counterparts from
their technical performance, taking into account the influence of
their molecular structure on their performance, while also considering
their compatibility with current environmental legislations. The evaluation
framework accounted for an extensive number of technical criteria
for the utilization of these low GWP refrigerants as drop-in replacements
in a vapor compression refrigeration cycle, as a showcase. Toward
the implementation of the technical evaluation, the polar soft-SAFT
EoS established itself as a crucial thermodynamic model by fully characterizing
thermodynamic properties of 18 different third and fourth generation
refrigerants. The explicit inclusion of the dipolar interactions of
these refrigerants ensured a highly accurate and robust model as demonstrated
from predicted first and second order thermodynamic derivative properties
of the refrigerants, along with accurate representation of binary
mixtures of refrigerants with n-alkanes. The physical
basis of the model enabled the extraction of molecular characteristics
of the studied refrigerants and their effect on the physicochemical
properties impacting their technical efficacy.The subsequent
drop-in assessment established that R32, R152a,
R134a, and R245fa, some of the most commonly commercialized working
fluids, could be potentially replaced with lower GWP fourth generation
refrigerants, without incurring on additional capital cost associated
with compressor modifications. The most viable replacements included
R1123, R1225ye(Z), R1234ze(E), and R1224yd(Z); however, the expected
downfall might be the additional operating costs associated with required
compression energy. After establishing the relationship between their
molecular features and their performance, it can be concluded that
the compatibilities of these replacements with their predecessors
are attributed to their relatively similar molecular features. Additionally,
for the remaining third generation refrigerants (R41, R23, R161, R125,
R236fa, R227ea), although no suitable replacement was found, rational
design of blended refrigerants might prove feasible for their replacement,
entailing a detailed blend analysis expected in future contributions.The collective results presented herein not only demonstrate the
ability of the proposed approach, built on molecular modeling, but
also assists in rapidly examining the inherent trade-offs or possible
issues in selecting next generation sustainable drop-in replacements.
It should be noted that an important factor remains missing in this
drop-in analysis, which is the cost of the replacement refrigerants.
However, as the current market is shifting toward deploying alternative
compounds in line with environmental laws, it can be expected that
the production costs of these emerging refrigerants will become cheaper
with increased productivity.
Authors: Keith R Solomon; Guus J M Velders; Stephen R Wilson; Sasha Madronich; Janice Longstreth; Pieter J Aucamp; Janet F Bornman Journal: J Toxicol Environ Health B Crit Rev Date: 2016-06-28 Impact factor: 6.393
Authors: Mark H Russell; Gerco Hoogeweg; Eva M Webster; David A Ellis; Robert L Waterland; Robert A Hoke Journal: Environ Toxicol Chem Date: 2012-07-24 Impact factor: 3.742
Authors: Mark O McLinden; J Steven Brown; Riccardo Brignoli; Andrei F Kazakov; Piotr A Domanski Journal: Nat Commun Date: 2017-02-17 Impact factor: 14.919
Authors: Marcus D Hanwell; Donald E Curtis; David C Lonie; Tim Vandermeersch; Eva Zurek; Geoffrey R Hutchison Journal: J Cheminform Date: 2012-08-13 Impact factor: 5.514
Authors: Ismail I I Alkhatib; Carlos G Albà; Ahmad S Darwish; Fèlix Llovell; Lourdes F Vega Journal: Ind Eng Chem Res Date: 2022-05-18 Impact factor: 4.326