Numerical evaluation of the performances of the ventilation system in a blast furnace casthouse.

Hui Wang1,2,3, Tianying Wang4,5,6, Liuchan Liu7, Zhengwei Long7, Pu Zhang4,5,6.   

Abstract

The blast furnace casthouse is a typical heavy-polluting factory building of a steel enterprise. During the tapping process and the taphole opening, the dust concentration in the factory building's workroom can reach tens of thousands mg/m3. Over time, the air pollutants in the workplace can have unwanted consequences on employees' health. This paper selected a typical blast furnace tapping workshop. The flow, temperature, and soot concentration fields in the workshop are measured on site during tapping, and the distribution characteristics are obtained. The performance of the tapping smoke exhaust system is analyzed based on computational fluid dynamics. The findings are as follows: the concentration of PM2.5 in most of the work area was 80μg/m3, but the concentration reached 1mg/m3 near the slag ditch, which was heavy pollution. Because the opening and closing of doors and windows was unreasonable, it was difficult for the particulate matter to accumulate in the deep and middle of the plant discharge. The PMV of the worker's work area is about 3, and the waste heat removal efficiency is 4.2. Hence, this article's finding provides a scientific basis for optimizing the air distribution in the blast furnace cast house's workplace.

Keywords:  Blast furnace cast house; Concentration distribution; Dust; Field test; Industrial ventilation; Numerical simulation

Year:  2021        PMID: 33966163     DOI: 10.1007/s11356-021-14215-8

Source DB:  PubMed          Journal:  Environ Sci Pollut Res Int        ISSN: 0944-1344            Impact factor:   4.223


  1 in total

1.  Study on contaminant distribution in a mobile BSL-4 laboratory based on multi-region directional airflow.

Authors:  Yan Wang; Jian-Tao Miao; Jian-Bo Chen; Hua-Yi Chai; Chun-Yu Zhu; Hong-An Tang; Yi Gan