Are pathogenic Legionella non-pneumophila a common bacteria in Water Distribution Networks?

Mireya Beatriz Salinas1, Soledad Fenoy1, Angela Magnet1, Lucianna Vaccaro1, Thiago Ds Gomes1, Carolina Hurtado1, Dolores Ollero1, Elizabeth Valdivieso1, Carmen Del Águila1, María José Pozuelo1, Fernando Izquierdo2.   

Abstract

The present study analyzes at the national level, the presence of circulating Legionella in the artificial aquatic systems of different facilities of all of them state-owned centers throughout Spain for 12 months. 1754 water samples from various state-owned centers were collected from January to December 2014. Samples were collected from the cooling towers and evaporative condensers (CTC), and water distribution networks such as domestic hot water (DHW), cold water for human consumption (CW), sprinkler irrigation systems (SIS), fire sprinkler systems (FSS), and water from decorative fountains (DF). All these facilities are considered, according to current regulations, as potential amplifying systems for bacteria and possible sources of infection by the generation of droplets and aerosols. The isolation and counting of Legionella in water samples was carried out using microbiological culture following the international normative UNE-EN-ISO 11,731:2007 (ISO 11,731:1998) and UNE-EN ISO 8199:2008 (ISO 8199:2005).The quantification of Legionella colonization, the annual distribution, and the geographical distribution of the Legionella isolates recovered in the water were analyzed. Besides, molecular techniques were used for the characterization of the Legionella non-pneumophila isolates. Legionella was recovered from 15.79% of the analyzed water samples. High colonization was more frequently detected in water samples from CTC, DHW, CW, and DF. Regarding the geographic distribution, positive samples of Legionella were obtained in 14 of the 18 Spanish locations analyzed. Legionella non-pneumophila was the most prevalent and was isolated from water samples from 13 different geographical locations (72%). Legionella anisa and Legionella jordanis were the most frequently non-pneumophila species isolated. Legionella donaldsonii was isolated for the first time in the water distribution networks in Spain. Legionella pneumophila sg 2-14 was detected in 13 locations and Legionella pneumophila sg 1 in 11 locations. Therefore, our study concludes that the presence of Legionella pneumophila and Legionella non-pneumophila species in these systems can be a potential threat to public health and should be examined thoroughly with complementary techniques, such as molecular techniques as a screen for routine diagnosis.
Copyright © 2021 Elsevier Ltd. All rights reserved.

Entities:  

Keywords:  Air-conditioner cooling towers; Evaporative cooling systems; Legionella non-pneumophila; South of Europe; Water facilities

Mesh:

Substances:

Year:  2021        PMID: 33813251     DOI: 10.1016/j.watres.2021.117013

Source DB:  PubMed          Journal:  Water Res        ISSN: 0043-1354            Impact factor:   11.236


  4 in total

1.  Legionella: A Promising Supplementary Indicator of Microbial Drinking Water Quality in Municipal Engineered Water Systems.

Authors:  Chiqian Zhang; Jingrang Lu
Journal:  Front Environ Sci       Date:  2021-11-10

2.  Legionella and other opportunistic pathogens in full-scale chloraminated municipal drinking water distribution systems.

Authors:  Chiqian Zhang; Ian Struewing; Jatin H Mistry; David G Wahman; Jonathan Pressman; Jingrang Lu
Journal:  Water Res       Date:  2021-08-19       Impact factor: 13.400

3.  Four-Year Environmental Surveillance Program of Legionella spp. in One of Palermo's Largest Hospitals.

Authors:  Ignazio Arrigo; Elena Galia; Teresa Fasciana; Orazia Diquattro; Maria Rita Tricoli; Nicola Serra; Mario Palermo; Anna Giammanco
Journal:  Microorganisms       Date:  2022-04-01

4.  A Tale of Four Danish Cities: Legionella pneumophila Diversity in Domestic Hot Water and Spatial Variations in Disease Incidence.

Authors:  Søren A Uldum; Lars G Schjoldager; Sharmin Baig; Kelsie Cassell
Journal:  Int J Environ Res Public Health       Date:  2022-02-22       Impact factor: 3.390

  4 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.