Literature DB >> 33765264

Dust and microbial filtration performance of regular and antimicrobial HVAC filters in realistic conditions.

Aurélie Joubert1, Safaa Abd Zaid Abd Ali2, Miora Frossard2, Yves Andrès2.   

Abstract

Two polypropylene HVAC electret filters: a regular filter and an antimicrobial filter containing zinc pyrithione (ZPT), were compared for filtration performance. The study was conducted over 7 months in realistic conditions with semi-urban outdoor air. Several parameters were monitored over the study period: the average temperature was about 20 °C and relative humidity about 60%, the average inlet concentration of cultivable microorganisms was 50 CFU m-3, the average inlet concentration of particles was 10 μg m-3, the filter pressure drop increased moderately by about 30 Pa, and the particle collection efficiency of soda fluorescein (median diameter 0.35 μm) decreased in the first half of the study period by about 30% and then stabilized. The microbial concentration on the filters was quantified every 2 months using an innovative methodology based on media coupons in conjunction with microorganism quantification by CFU counting, with 5 culture media favorable to bacteria and/or fungi growth. The microbial concentrations on the filters were between 100 and 2000 CFU cm-2. The antimicrobial effect of zinc pyrithione was confirmed by the fungi cultivated with DRBC agar: no effects in the level of filter clogging were revealed in the range studied. The high statistical deviation in the results regarding the inhibiting effect of zinc pyrithione on bacteria prevents any conclusion.
© 2021. The Author(s), under exclusive licence to Springer-Verlag GmbH Germany, part of Springer Nature.

Entities:  

Keywords:  Air cleaning; Antimicrobial filter; Electret filter; Filtration performance; HVAC Fibrous filter; Indoor air quality; Microbial aerosol; Zinc pyrithione

Year:  2021        PMID: 33765264     DOI: 10.1007/s11356-021-13330-w

Source DB:  PubMed          Journal:  Environ Sci Pollut Res Int        ISSN: 0944-1344            Impact factor:   4.223


  1 in total

1.  Solar energy optimization in solar-HVAC using Sutterby hybrid nanofluid with Smoluchowski temperature conditions: a solar thermal application.

Authors:  Wasim Jamshed; Mohamed R Eid; Rabia Safdar; Amjad Ali Pasha; Siti Suzilliana Putri Mohamed Isa; Mohammad Adil; Zulfiqar Rehman; Wajaree Weera
Journal:  Sci Rep       Date:  2022-07-07       Impact factor: 4.996

  1 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.