Kristin G King1, George L Delclos2, Eric L Brown2, Susan Tortolero Emery2, Jose Miguel Yamal2, Robert J Emery3.
Abstract
BACKGROUND: With healthcare shifting to the outpatient setting, this study examined whether outpatient clinics operating in business occupancy settings were conducting procedures in rooms with ventilation rates above, at, or below thresholds defined in the American National Standards Institute/American Society of Heating, Refrigerating and Air-Conditioning Engineers/American Society for Health Care Engineering Standard 170 for Ventilation in Health Care Facilities and whether lower ventilation rates and building characteristics increase the risk of disease transmission.Entities:
Keywords: Air changes per hour; Air flow; Physician office; Transmission risk
Mesh:
Year: 2021 PMID: 33485924 PMCID: PMC8052498 DOI: 10.1016/j.ajic.2021.01.011
Source DB: PubMed Journal: Am J Infect Control ISSN: 0196-6553 Impact factor: 2.918
ANSI/ASHRAE/ASHE standard 170 for ventilation in health care facilities
| Function of space | Minimum total air changes per hour (ACH) | Pressure relationship to adjacent areas |
|---|---|---|
| General examination room | 4 | No requirement |
| Treatment room | 6 | No requirement |
| Procedure room | 15 | Positive |
| Bronchoscopy, sputum collection, and pentamidine administration | 12 | Negative |
ACH, air changes per hour; ANSI, American National Standards Institute; ASHE, American Society for Health Care Engineering; ASHRAE, American Society of Heating, Refrigerating and Air-Conditioning Engineers.
room used for clinical exam and vitals.
exam room used for additional function (treatment or procedure).
not restricted environment but sterile instruments or field used.
Clinic rooms (n = 105)
| n | Median ACH | 25th percentile | 75th percentile | |
|---|---|---|---|---|
| Exam | 25 | 6.8 | 4.7 | 11.6 |
| Treatment | 57 | 6.9 | 4.9 | 10.2 |
| Procedure | 23 | 7.6 | 4.4 | 11.3 |
| Aerosol-generating | 63 | 7.0 | 5.1 | 9.9 |
| Minor surgical | 17 | 5.6 | 4.3 | 12.4 |
| Medical office building | 45 | 7.6 | 5.0 | 11.5 |
| Shopping center | 30 | 5.9 | 4.3 | 7.9 |
| Stand-alone | 30 | 6.8 | 5.1 | 14.4 |
ACH, air changes per hour.
Percentage of clinic rooms meeting the ANSI 170 standard by room and procedure type
| Air changes per hour | ||||||
|---|---|---|---|---|---|---|
| n | >4 | 4-6 | 6-12 | 12-15 | <15 | |
| Exam | 25 | 16% | 32% | 32% | 8% | 12% |
| Treatment | 57 | 9% | 24% | 51% | 2% | 14% |
| Procedure | 23 | 8% | 35% | 39% | 9% | 9% |
| Aerosol-generating | 63 | 9% | 21% | 55% | 2% | 13% |
| Minor surgical | 17 | 6% | 53% | 17% | 12% | 12% |
| 105 | 10% | 29% | 44% | 5% | 12% | |
ANSI, American National Standards Institute.
Fig 1Transmission risk models based on measured ACH and calculated by the Gammaitoni-Nucci model (ANSI healthcare ventilation standards for exam, treatment, aerosol-generating procedures (AGP) and procedure rooms demarked vertically).