Guozhen Lin1, Shiyu Zhang2, Yi Zhong3, Lin Zhang4, Siqi Ai2, Kuibiao Li5, Wenzhe Su5, Lan Cao5, Yuteng Zhao6, Fei Tian2, Jinrong Li7, Yinglin Wu2, Chongshan Guo3, Rongfei Peng8, Xinwei Wu9, Pingsheng Gan8, Wei Zhu10, Hualiang Lin2, Zhoubin Zhang11.
Abstract
BACKGROUND: Nine COVID-19 (Corona Virus Disease, 2019) cases were observed in one community in Guangzhou. All the cases lived in three vertically aligned units of one building sharing the same piping system, which provided one unique opportunity to examine the transmission mode of SARS-CoV-2.Entities:
Keywords: COVID-19; China; Community outbreak; Transmission through air
Year: 2020 PMID: 33235537 PMCID: PMC7677092 DOI: 10.1016/j.atmosenv.2020.118083
Source DB: PubMed Journal: Atmos Environ (1994) ISSN: 1352-2310 Impact factor: 4.798
Fig. 1Floor structure of the study building.
(a) The planar structure of Floor 2 to Floor 28. (b) The planar structure of Floor 29. (c) The planar structure of Floor 29 after modification. (d) The structure of the drain pipe, sewer pipe and exhaust pipe before and after the modification.
Fig. 2Piping system structure of the study building.
Fig. 3Description of the nine cases.
(a) Onset and quarantine date for the nine cases. (b) The relationship between the nine cases. Each case was labeled with one letter and number, the number represented the family, and the letter represented sequence of the infection in each family.
Fig. 4Phylogenetic tree of Spike gene sequences of patients in Guangzhou(▲).
Distribution of cases and non-cases by Unit b and non-Unit b.
| Cases | Non-cases | Total | |
|---|---|---|---|
| Unit b | 4 (14.3%) | 24 (85.7%) | 28 |
| Non-Unit b | 0 (0.0%) | 55 (100.0%) | 55 |
| Total | 4 | 79 | 83 |
Fig. 5The time of elevator usage by Family 1, 2 and 3.
Wind speed at the bathtub draina.
| Flush the toilet: #15-b | Flush the toilet: #23-b | ||||
|---|---|---|---|---|---|
| Background at the | Wind speed at the | Differences | Wind speed at the | Differences | |
| #15-b | 0.12 | 0.36 | 0.24 | 0.20 | 0.08 |
| #16-b | 0.01 | 0.29 | 0.28 | 0.46 | 0.45 |
| #25-b | 0.22 | 0.51 | 0.29 | 0.66 | 0.44 |
| #26-b | 0.02 | 0.30 | 0.28 | 0.77 | 0.75 |
| #27-b | 0.04 | 0.23 | 0.19 | 0.15 | 0.11 |
Instrument used for detection: Testo-425; # Residential apartment.
Wind speed at the floor draina.
| Flush the toilet: #15-b | Flush the toilet: #23-b | ||||
|---|---|---|---|---|---|
| Background at the | Wind speed at the | Differences | Wind speed at the | Differences | |
| #15-b | 0.06 | 0.22 | 0.16 | 0.20 | 0.14 |
| #16-b | 0.01 | 0.45 | 0.44 | 0.58 | 0.57 |
| #25-b | 0.10 | 0.33 | 0.23 | 0.19 | 0.09 |
| #26-b | 0.02 | 0.12 | 0.10 | 0.13 | 0.11 |
| #27-b | 0.63 | 1.19 | 0.56 | 0.90 | 0.27 |
Instrument used for detection: Testo-425; # Residential apartment.
Simulations of transmission via sewer pipes in field experimenta.
| Apartment | Room | Time | Chloroform | Carbon tetrachloride | Field observation |
|---|---|---|---|---|---|
| #8-b | Master Bathroom | background | 0.00 | 0.00 | Dry floor drains |
| 30 | 0.00 | 0.00 | |||
| 60 | 0.00 | 0.00 | |||
| Guest Bathroom | background | 0.00 | 0.00 | ||
| 30 | 0.00 | 0.00 | |||
| 60 | 0.00 | 0.00 | |||
| #21-b | Master Bathroom | background | 0.00 | 0.00 | Water seal in the floor drains |
| 30 | 0.00 | 0.00 | |||
| 60 | 0.00 | 0.00 | |||
| Guest Bathroom | background | 0.00 | 0.00 | ||
| 30 | 0.00 | 0.00 | |||
| 60 | 0.00 | 0.00 | |||
| #26-b | Master Bathroom | background | 0.00 | 0.00 | Dry floor drains |
| 30 | 0.12 | 0.26 | |||
| 60 | 0.074 | 0.13 | |||
| Guest Bathroom | background | 0.00 | 0.00 | ||
| 30 | 0.087 | 0.17 | |||
| 60 | 0.096 | 0.14 | |||
| #27-b | Master Bathroom | background | 0.00 | 0.00 | Water seal in the floor drains |
| 30 | 0.00 | 0.00 | |||
| 60 | 0.00 | 0.0025 | |||
| Guest Bathroom | background | 0.00 | 0.00 | ||
| 30 | 0.00 | 0.00 | |||
| 60 | 0.00 | 0.0024 |
Instrument used for detection: Agilent 7890A GC; # Residential apartment.