The aim of this study was to determine the operating parameters of bioethanol burners used in the so-called bioethanol fireplaces, mainly in terms of their actual heat output. The method used to determine the actual heat output was designed considering procedures from the standard EN 16647 fireplaces for liquid fuel. Experiments were carried out on eight different types of burners with two different types of fuels. The measurements demonstrated a difference of up to 19% in the maximal heat output among individual fuels and a difference of up to 16% in the average heat output when comparing identical burners over approximately 60 min of operation. The average heat outputs of the burners during the measurements reached approximately 41-62% of the heat output declared by the manufacturers. The measured values were used to create graphs of the dependency of the burner opening size on its average heat output based on the fuel type. Two-chambered burners reached a higher average heat output than single-chambered burners with the same burner opening area of above ∼6000 mm2. The positions of the regulation damper (75 and 50%) increased the burning time by 21 and 86%, respectively.
The aim of this study was to determine the operating parameters of bioethanol burners used in the so-called bioethanol fireplaces, mainly in terms of their actual heat output. The method used to determine the actual heat output was designed considering procedures from the standard EN 16647 fireplaces for liquid fuel. Experiments were carried out on eight different types of burners with two different types of fuels. The measurements demonstrated a difference of up to 19% in the maximal heat output among individual fuels and a difference of up to 16% in the average heat output when comparing identical burners over approximately 60 min of operation. The average heat outputs of the burners during the measurements reached approximately 41-62% of the heat output declared by the manufacturers. The measured values were used to create graphs of the dependency of the burner opening size on its average heat output based on the fuel type. Two-chambered burners reached a higher average heat output than single-chambered burners with the same burner opening area of above ∼6000 mm2. The positions of the regulation damper (75 and 50%) increased the burning time by 21 and 86%, respectively.
While building or reconstructing
a house or an apartment, the method
of ensuring the necessary amount of heat to maintain a comfortable
ambient temperature is one of the most important areas. Because the
construction of low-energy and passive houses with steadily decreasing
heat consumption is becoming increasingly common, customers are also
becoming more aware of equipment with relatively low heat output.
One of the representatives of this heat source category is the so-called
bioethanol fireplaces. They are combustion appliances composed of
two main parts, the fireplace body and the burner. The whole installation
consists of one or more burners placed in the fireplace body. The
fireplace body can be constructed as freestanding, wall-mounted, built-in
(to the wall), or table. The fireplace body usually has only a decorative
function; however, in the case of appropriate construction, it can
accumulate part of the heat released from the combustion process.[1]The fuel used for this type of appliance
is called bioethanol (renewable
source of energy).Bioethanol fireplaces have been available
in the market for more
than 10 years, and they have mainly been considered as design elements
in houses. However, because of the non-negligible heat output of the
burners (on the order of kW), which can cover a significant part of
house heat losses, especially in the case of low energy demand houses,
they can be classified into the category of heat sources together
with conventional stoves and others.Earlier studies regarding
bioethanol fireplaces examined these
appliances in terms of the safety of their operation in connection
with possible accidents resulting in burns to people.[2,3]According to operating manuals, the fuel for bioethanol fireplaces
is pure (denatured) ethanol. Ethanol combustion is a complicated process
that can occur in different chemical reactions, as described in the
research of Millán-Merino et al.[4,5] Therefore,
the combustion products of complete combustion are CO2 and
H2O. In the case of an incomplete combustion process (caused,
e.g., by an inappropriate construction of the fireplace body from
the amount of combustion air point of view), products from incomplete
combustion (e.g., CO and OGC) can occur in the flue gas.Substances
caused by a complete combustion process (CO2 and H2O) occur in home interiors naturally. The main
production of CO2 in homes results from the breathing of
people and animals. Previous studies focused on the quality change
of unventilated indoor environments during the operation of bioethanol
fireplaces in terms of volume concentration of pollutants arising
from the combustion of ethanol.[6,7] The results showed a
significant impact, for example, increases in the volume concentrations
of CO2, CO, and OGC up to values that can influence human
health.[1,8,9]From
the point of view of ethanol burning safety, there are studies
describing the parameters of energy balance [e.g., mass loss rate
(g/s) and heat release rate (kW)] based on pool fire testing. The
methodology and equipment of these measurements are designed primarily
for fire safety description and are unrelated to the possibility of
heating houses by open fire from ethanol burning in small-scale bioethanol
burners.[10−12]A previous study showed the possibility of
a bioethanol–water
mixture as a suitable fuel for cooking in developing countries such
as Madagascar. For this purpose, a special stove was designed, manufactured,
and tested with satisfactory results of thermal efficiency, safety,
and other parameters.[13] The actual operating
parameters (especially the behavior of heat output over time) of the
heat source for bioethanol fireplaces have not been examined yet.Because of the principle of function, a manually filled bioethanol
fireplace cannot deliver heat over a long period because it is forbidden
to add fuel to a burner during its operation or to a burner that has
not cooled down (the time before it is possible to refill the fuel
and start a new operating cycle after the previous one is defined
in the manual). This means that these fireplaces cannot be comfortably
used as a primary heat source. However, they are commonly recommended
by project architects as an alternative to typical solid fuel fireplaces
for houses with very low heat losses (especially for houses with a
recuperative air exchange unit, which can ensure sufficient air exchange
in the room). For this reason, it is essential to know the mentioned
operating parameters to prevent undesirable local overheating of rooms.
In the case where a bioethanol fireplace is installed in a house with
higher heat losses as an alternative to a local solid fuel heating
appliance, it is also essential to know its operating parameters to
comfortably meet the heat requirement in the given space.[14]Unlike standard combustion appliances,
appliances of this kind
do not require any certification (standard EN 16647 fireplaces for
liquid fuels[15] are not harmonized in the
EU), which would, for example, determine the average and maximum values
of the achieved heat output during operation based on the initial
dose of fuel before lighting the burner. The sales of this product
on individual markets can be restricted by local laws in individual
countries. For example, while introducing products of this type to
the market in Czech Republic, the manufacturer has to comply with
act no. 102/2001 Coll., on General Product Safety, which sets the
requirement to provide products with labeling and accompanying documentation
including an assessment of risks associated with the use of the product.
The manufacturer is also required to abide by provisions of Section
9 of act no. 634/1992 Coll., Consumer Protection Act, which require
the seller to inform the consumer about the properties of the sold
products. Section 10 of this act further requires that the seller
provides visible and comprehensible marking of the product, which
means identification of the manufacturer, the name of the product,
data on weight or size, and/or other data required about the nature
of the product for its identification and use. Similar regulations
are also in force in other countries of the EU.[16−18]The information
provided to customers by the manufacturers of bioethanol
fireplaces is mostly insufficient, incomplete, and inaccurate for
the new area of focus of these appliances (i.e., heating).Each
burner should come with a manual or technical data sheet with
basic information about the fuel consumption and the average heat
output of the combustion appliance based on the amount of fuel dosed
before lighting.This study focused on observing the heat output
of bioethanol fireplaces
including different, purposely induced operating states that can occur
during their normal operation in households. The novelty of our research
is based on unexplored real possibilities of bioalcohol burners in
terms of their usage as secondary or tertiary heat sources for house
heating. The added value of the research is in changing the view of
bioalcohol burners from a design element to a potential heat source.
The study provides unpublished information that will lead to the appropriate
bioethanol burner choice during the design of household energy systems
and will also lead to sophisticated usage of the mentioned devices
by their users.This study does not assess the economic aspect
of this heating
method. This study is aimed only at manually filled burners; automatically
filled burners were not included in this research.The comparison
of measured values with those of other authors is
not possible because no scientific article has addressed this topic.
Results and Discussion
Effect of the Type of Fuel
on the Heat Output
of Individual Burners
The differences in the remaining fuel
weight in the burners between 1 minute intervals were used to determine
the heat output of the burners according to the known lower heating
values (LHVs) of the fuels. The series of heat outputs were then used
to determine the maximum heat output (as the highest output achieved
during the test) and the average heat output (the average value of
the heat outputs over the whole period of burning the fuel). The flame
temperatures were recorded as 1 minute averages of the measured values.
The values in Tables and 2 represent the highest achieved 1 minute
averages of the temperature at the given point and the average values
of measured temperatures at the given point during the whole test
duration. These values are given here as accompanying data to refine
the description of the performed measurement. The flame temperature
changed significantly during each test because the flames were not
directed strictly to any flue gas duct. The combustion took place
in an open space, so the movement of the flame was quite unstable
(same situation as that during standard home usage of a bioethanol
fireplace). For this reason, the results are not comparable with other
studies strictly aimed at these values.[19]
Table 1
Measurement Results of All Burners
While Burning “Fuel 1” (Standard Test—Approximately
60 min of Operation)a,b
burner designation [—]
fuel dose [g]
LHV [MJ/kg]
actual test duration [hh:mm]
maximum heat output—highest achieved [kW]
fuel consumption* [kg/h]
average heat output in operation [kW]
average fuel consum. [kg/h]
absolute air pressure during test [hPa]
relative air humidity during test [%]
maximum flame temp. (5 cm) [°C]
average flame temp. (5 cm) [°C]
maximum
flame temp. (10 cm) [°C]
average flame temp. (10 cm) [°C]
ambient air temp. during test
[°C]
burner 1
121.0
24.6
1:07
0.94 ± 0.01
0.138
0.73 ± 0.01
0.107
979.1
34.6
593.5
394.7
330.6
218.1
24.0
burner 2
209.6
24.6
0:51
2.22 ± 0.07
0.324
1.65 ± 0.07
0.242
978.0
33.7
478.5
323.1
346.8
218.2
24.3
burner 3
302.7
24.6
1:06
2.79 ± 0.07
0.408
1.85 ± 0.07
0.271
972.7
40.2
362.7
195.2
213.6
104.5
24.6
burner 4
120.6
24.6
0:59
1.15 ± 0.00
0.168
0.82 ± 0.01
0.121
980.8
37.4
394.3
184.0
261.2
160.8
23.6
burner 5
217.5
24.6
1:04
1.93 ± 0.07
0.282
1.37 ± 0.07
0.201
978.0
33.7
478.5
323.1
346.8
218.2
24.3
burner 6
324.8
24.6
0:58
2.83 ± 0.07
0.414
2.26 ± 0.07
0.330
972.7
40.2
362.7
195.2
213.6
104.5
24.6
burner 7
501.4
24.6
1:12
3.73 ± 0.15
0.546
2.82 ± 0.07
0.412
973.6
41.1
538.5
329.9
387.8
204.4
25.4
burner 8
131.5
24.6
1:05
1.27 ± 0.7
0.186
0.82 ± 0.07
0.120
981.9
36.5
692.1
498.5
567.7
367.9
23.0
The heat outputs
specified by the
manufacturers of individual burners are shown in Table .
* indicates maximal heat output
at 20 °C using density according to the manufacturer’s
data.
Table 2
Measurement
Results of All Burners
While Burning “Fuel 2” (Standard Test—Approximately
60 min of Operation)a
burner designation
[—]
fuel dose [g]
LHV [MJ/kg]
actual test duration [hh:mm]
maximum heat output—highest achieved [kW]
fuel consumption* [kg/h]
average heat output
in operation [kW]
average fuel consum. [kg/h]
absolute air pressure
during test [hPa]
relative air humidity
during test [%]
maximum flame temp. (5 cm) [°C]
average
flame temp. (5 cm) [°C]
maximum flame temp. (10 cm) [°C]
average flame temp. (10 cm) [°C]
ambient
air temp. during test [°C]
burner 1
124.8
26.6
1:04
1.11 ± 0.01
0.15
0.85 ± 0.01
0.115
982.9
35.1
543.2
39.6
491.3
318.5
24.1
burner 2
209.6
26.6
0:49
2.48 ± 0.08
0.336
1.86 ± 0.08
0.252
982.7
33.8
474.6
338.7
350.5
235.6
24.3
burner 3
303.0
26.6
1:02
3.32 ± 0.08
0.45
2.13 ± 0.08
0.289
984.1
33.1
390.8
179.2
355.3
171.5
24.0
burner 4
120.7
26.6
1:00
1.37 ± 0.08
0.186
0.88 ± 0.01
0.119
982.9
35.3
521.9
303.3
314.0
179.2
23.7
burner 5
217.3
26.6
1:02
2.08 ± 0.08
0.282
1.53 ± 0.08
0.207
982.5
35.1
494.1
239.8
371.8
184.8
24.0
burner 6
324.9
26.6
1:02
3.06 ± 0.08
0.414
2.28 ± 0.08
0.309
982.1
35.4
535.7
285.4
391.8
208.7
24.2
burner 7
502.6
26.6
1:12
4.07 ± 0.16
0.552
3.05 ± 0.08
0.413
974.0
43.0
542.0
334.8
406.5
220.3
25.4
burner 8
131.4
26.6
1:03
1.37 ± 0.08
0.186
0.91 ± 0.01
0.123
982.6
34.9
613.5
410.3
344.0
205.1
23.8
The heat outputs specified by the
manufacturers of individual burners are shown in Table .
* indicates maximal heat output
at 20 °C using density according to the manufacturer’s
data.
The heat outputs
specified by the
manufacturers of individual burners are shown in Table .
Table 4
Basic Information About the Tested
Burners
burner designation
[—]
burner weight [g]
burner opening area [mm2]
expected heat output (manufacturer’s data)
[kW]
burner 1
1174
3464
1.5
burner 2
2524
7000
3.0
burner 3
3500
11200
3.5
burner 4
1528
4161
2.0
burner 5
2033
6390
3.0
burner 6
2540
8560
4.0
burner 7
3042
9950
6.0
burner 8
861
2730
1.5
* indicates maximal heat output
at 20 °C using density according to the manufacturer’s
data.The heat outputs specified by the
manufacturers of individual burners are shown in Table .* indicates maximal heat output
at 20 °C using density according to the manufacturer’s
data.The dosed fuel was
sufficient for 40 min of operation according
to the expected heat output specified by the manufacturers of individual
burners and was almost always sufficient for approximately 60 min
of operation. It is apparent from this initial information that the
heat output specified by the burner manufacturer is significantly
different from the average heat output measured over the whole test
duration.The curves (shown in Figures and 2) reflecting
the heat
outputs of each tested burners as a function of time for different
fuels are always very similar in shape (the same burner, the same
fuel dose, but different fuel), with the difference being that higher
average and maximum outputs were achieved with fuel 2 (higher LHV).
The use of fuel with a higher LHV (fuel 2) ensured that the average
heat output of the burners increased by approximately 1–16%
(depending on the type of burner) and the maximum achieved heat output
increased by approximately 7–19% as well. The test duration
did not differ by more than 4 min in the same weight of fuel dose.
The initial rapid increase of heat output in the first minutes after
ignition was almost identical for both fuels.
Figure 1
Behavior of the heat
output of individual burners while burning
“fuel 1”. The heat output specified by the manufacturer
is burner 1—1.5 kW; burner 2—3 kW; burner 3—3.5
kW, burner 4—2 kW; burner 5—3 kW; burner 6—4
kW; burner 7—6 kW; and burner 8—1.5 kW. The weight for
each burner is the initial weight of the dosed fuel before lighting
the burner.
Figure 2
Behavior of the heat output of individual burners
while burning
“fuel 2”. The heat output specified by the manufacturer
is burner 1—1.5 kW; burner 2—3 kW; burner 3—3.5
kW; burner 4 – 2 kW; burner 5—3 kW; burner 6—4
kW; burner 7—6 kW; and burner 8 – 1.5 kW. The weight
for each burner is the initial weight of the dosed fuel before lighting
the burner.
Behavior of the heat
output of individual burners while burning
“fuel 1”. The heat output specified by the manufacturer
is burner 1—1.5 kW; burner 2—3 kW; burner 3—3.5
kW, burner 4—2 kW; burner 5—3 kW; burner 6—4
kW; burner 7—6 kW; and burner 8—1.5 kW. The weight for
each burner is the initial weight of the dosed fuel before lighting
the burner.Behavior of the heat output of individual burners
while burning
“fuel 2”. The heat output specified by the manufacturer
is burner 1—1.5 kW; burner 2—3 kW; burner 3—3.5
kW; burner 4 – 2 kW; burner 5—3 kW; burner 6—4
kW; burner 7—6 kW; and burner 8 – 1.5 kW. The weight
for each burner is the initial weight of the dosed fuel before lighting
the burner.The measured 1 minute values of
heat output are shown in Figures and 2. The values confirming
the results are given in Tables and 2.The maximal heat
output during the tests was usually reached between
20 and 40 min after ignition. In this time range, the burners showed
a relatively uniform heat output. After the stable time, a decrease
in heat output occurred. The decreasing trend remained until a complete
burnout of the fuel during the tests with single-chambered burners.
During the tests with two-chambered burners, approximately 5 min before
burnout, a small peak of heat output occurred. With the increase in the burner opening
area of the two-chambered burners, the mentioned peaks became less
significant. For burner 4, this peak represents the highest recorded
heat output for the whole testing period.The measurement results
were also used to create graphs of dependency
of the burner opening size on its average heat output during the test
(shown in Figure ).
It is apparent from the graphs that the average heat output of a burner
increases together with the increase in the burner opening area. A
closer look at the comparison of the two burner design types (single-chambered—burners
1, 2, 3, and 8 vs two-chambered—burners 4, 5, 6, and 7) makes
it apparent that the trend of the above-mentioned dependency rises
slowly in the case of single-chambered burners with the fuel area
being completely filled with mineral wool than it does in the case
of two-chambered burners. The two-chambered burners achieved a higher
average heat output at higher areas of the burner opening (approximately
above 6000 mm2 depending on the fuel type). This trend
is valid for test periods of approximately 60 min. Research on the
influence of the degree of fuel filling into the burner on this trend
is not part of this work.
Figure 3
Dependence of the average heat output of burners
on their opening
area sorted according to the fuel. The upper plot is sorted according
to the individual burners, and the bottom plot is sorted according
to the burner design type.
Dependence of the average heat output of burners
on their opening
area sorted according to the fuel. The upper plot is sorted according
to the individual burners, and the bottom plot is sorted according
to the burner design type.
Effect of Ambient Temperature on the Heat
Output of Burner 1
The main motivation for this test arises
from the common usage of bioethanol burners by gamekeepers in watchtowers
and by cottage owners during winter. The combustion test performed
using burner 1 to simulate cold ignition and the start of heating
in a cooled room, where the burner and fuel were stored in an environment
with a temperature around zero degree Celsius, did not prove a noteworthy
effect of the burner temperature, fuel temperature, and ambient air
temperature on the overall behavior of the burner heat output. The
test was performed outside the building (during a cold autumn night)
to ensure such low ambient temperature. Another phenomenon was observed
during the test. Despite the apparent windless conditions and the
fact that the burner was sheltered by wind protection walls from three
sides, the flame apparently flickered more intensely (this manifested
sudden major changes in the flame height and caused the flame to move
in all directions, which occurred twice during the test—at
26 and 41 min). This phenomenon results in a higher average and maximum
achieved heat output and thus faster burning out of the fuel. The
more intense burning was probably caused by the minimal wind coming
from the unprotected front side.The 1 minute values of heat
output are shown in Figure . The values confirming the results are given in Table .
Figure 4
Behavior of burner 1
heat outputs while burning each of the tested
fuels, including a cold environment test. The heat output specified
by the manufacturer is burner 1—1.5 kW. The weight for each
burner is the initial weight of the dosed fuel before lighting the
burner.
Table 3
Results of Measurements
of Burning
Fuel 1 (Special Tests)a,b
burner designation [—]
fuel dose
[g]
LHV [MJ/kg]
actual test duration [hh:mm]
maximum heat output—highest achieved
[kW]
fuel consumption* [kg/h]
average heat output in operation [kW]
average fuel consum. [kg/h]
absolute air pressure during test [hPa]
relative air humidity during test [%]
ambient air temp. during test [°C]
regulation damper opening [%]
fuel storage tank filling [%]
burner 1 (simulation of cold
start)
120.6
24.6
0:58
1.64 ± 0.07
0.24
0.84 ± 0.01
0.123
987.9
27.1
1.7
100
burner 2
209.9
24.6
1:36
1.19 ± 0.07
0.174
0.89 ± 0.01
0.130
983.9
35.2
24.0
50
cca 50
burner 2
209.9
24.6
1:02
1.76 ± 0.07
0.258
1.39 ± 0.07
0.203
988.3
45.4
22.4
75
cca 50
burner 2
300.3
24.6
1:05
2.42 ± 0.07
0.354
1.89 ± 0.07
0.285
987.4
44.8
22.3
100
75
burner 2
400.2
24.6
1:24
2.42 ± 0.07
0.354
1.95 ± 0.07
0.282
987.4
44.8
22.3
100
100
The heat outputs specified by the
manufacturers are provided in Table .
* indicates
maximal heat output
at 20 °C using density according to the manufacturer’s
data.
Behavior of burner 1
heat outputs while burning each of the tested
fuels, including a cold environment test. The heat output specified
by the manufacturer is burner 1—1.5 kW. The weight for each
burner is the initial weight of the dosed fuel before lighting the
burner.The heat outputs specified by the
manufacturers are provided in Table .* indicates
maximal heat output
at 20 °C using density according to the manufacturer’s
data.
Effect
of the Initial Fuel Dose and Degree
of the Regulation Damper Closure on the Behavior of Burner 2 Heat
Output
The effect of the amount of initial fuel dose was
observed to determine the change in the maximum and average heat output
and to compare the duration of each combustion phase of the combustion
process. Combustion tests with different fuel doses performed by using
burner 2 showed an increase in the maximal heat output (by approximately
9%) and an increase in the average heat output (by approximately 17%)
while increasing the fuel dose from 50% of the maximal fuel dose (approximately
209.6 g of fuel) to 75% of the maximal fuel dose (300.3 g of fuel)
and 100% of the maximal fuel dose (400.2 g of fuel). The increase
in the average heat output was caused by a more stable operation of
the burner, that is, especially by the burner remaining in the vicinity
of the maximum achieved heat output for a longer time. This state
is shown in Figure as II. phase—heating.
Figure 5
Dependency of released heat energy by
burner 2 on time after ignition.
The heat output specified by the manufacturer is burner 2—3
kW.
Dependency of released heat energy by
burner 2 on time after ignition.
The heat output specified by the manufacturer is burner 2—3
kW.It is obvious from the mentioned
graph that I. phase—preheating
took almost the same amount of time (approximately 15 min) for all
the four mentioned tests (209.6 g of fuel 1, 300.3 g of fuel 1, 400.2
g of fuel 1, and 209.6 g of fuel 2), regardless of the amount of initial
fuel dose in the range from 50 to 100% of the maximal fuel dose. II.
phase—Heating is almost linear with almost the same slope for
the tests with fuel 1 and with a steeper slope for the test with fuel
2. The duration of this part of the combustion test depends on the
initial fuel dose weight. III. phase—Burn out was the same
for the tests with fuel 1 and not dependent on the initial fuel dose
weight. III. phase—Burn out of the combustion test with fuel
2 was slightly shorter than that of others.The effect of partial
closure of the regulation damper was observed
to determine the change in the maximum and average heat output in
comparison to a fully opened burner. The combustion tests with partial
closure of the regulation damper performed with burner 2 indicated
this method of heat output regulation to be applicable. When the regulation
damper was closed so that the burner opening area was 75% of the fully
open burner opening area, the maximum achieved heat output was 84%
of the value initially measured during a combustion test with the
same initial fuel dose. The average heat output during this test was
80% of the initially measured value. When the regulation damper was
closed so that the burner opening area was 50% of the fully open burner
opening area, the maximum achieved heat output, as well as the average
heat output, was 54% of the values initially measured during a combustion
test with the same initial fuel dose. This regulation may affect the
actual heat output, for example, according to the current heat demand
of the house and avoid overheating.The 1 minute values of heat
output are shown in Figure . The values confirming the
above results are given in Table .
Figure 6
Behavior of burner 2 heat outputs while burning each of
the tested
fuel, including tests with a partially closed regulation damper and
with different fuel doses. The heat output specified by the manufacturer
is burner 2—3 kW.
Behavior of burner 2 heat outputs while burning each of
the tested
fuel, including tests with a partially closed regulation damper and
with different fuel doses. The heat output specified by the manufacturer
is burner 2—3 kW.
Values
Specified by the Manufacturer and the
Actual Parameters
The measurement results show that it is
not possible to operate the burners at the heat output declared by
the manufacturer during the 60 min tests with the fuels used. At ordinary
interior conditions, the burners achieved approximately 57–95%
of the heat output declared by the manufacturer (i.e., the maximum
measured heat output, as the average value of outputs in 1 min). In
terms of interior heating, the maximal achieved heat output is not
crucial if the appliance can only sustain it during a fraction of
the operating time, but the average heat output based on the total
operating time is important. The average heat output reached approximately
41–62% of the declared heat output while considering the total
test duration. Both the average and the maximal heat outputs of the
burners increased during longer operation with a larger fuel dose
(as ascertained by experiments with burner 2). Nonetheless, the average
heat output of the burners with a completely filled fuel area would
not have reached their respective declared values, even if taking
this deviation into account. The burners with the lowest difference
between the heat output declared by the manufacturer and the maximal
measured heat output were burner 3, burner 8, and burner 2. These
three burners could, with their fuel area completely filled and while
using fuel 2, achieve the heat output declared by the manufacturer
with their maximal heat output for a short time. This fact has not
been experimentally verified.The above-mentioned standard EN
16647[15] describes measuring the heat output
as an average value during the test of a completely filled burner.
However, in actual use, the user does not have to completely fill
the fuel area with fuel, especially because premature extinguishing
leads to intense evaporation of ethanol into the air. There is no
mechanical measure to prevent this phenomenon. Because of the large
difference between the measured values and values given by the producer,
it seems that the chosen burners were not tested according to the
mentioned standard.The results of the flame temperature measurements
were very unexpected,
primarily because of the very irregular and unpredictable movement
of the flame (even moving completely away from the thermocouples),
as well as because of the very quick dispersal of flue gas into the
environment. The flame from the burners was very sensible to any movement
(and consequent air waves) in the surroundings.
Conclusions
The aim of this paper was to determine the actual
behavior of the
heat output of bioethanol burners.A series of measurements
were performed to meet the objective of
the research. The combustion tests were performed with regard to the
procedures provided by the standard EN 16647[15] (the mentioned standard is only recommended and the manufacturer
is not obligated to test or certify the appliance according to this
EU standard). The situation can be changed by the legislation of individual
countries.It is possible to estimate the total burning time
and the heat
output of the burner beforehand while using the appropriate fuel dose.
By knowing the burning time beforehand, the use can prevent undesirable
fuel losses and an undesirable smell, resulting from premature extinguishing
of the flame and evaporation of ethanol into the air.The average
heat outputs of the burners during the measurements
(60 min tests) reached approximately 41–62% of the heat output
declared by the manufacturers. The average heat output of the burners
may vary depending on the quality (purity) of the fuel used, up to
16%. The combustion tests with partial closure of the regulation damper
performed with burner 2 indicated this method of heat output regulation
to be applicable even for standard home operation. A comparison between
two burner construction types in terms of the dependence of average
heat output on the burner opening area showed that two-chambered burners
reached a higher average heat output than single-chambered burners
with the same burner opening area above ∼6000 mm2, according to the fuel type. The reduced temperature of the burner,
fuel, and ambient air did not show a remarkable effect on the burner
heat output. Increasing the initial fuel rate in the tests with burner
2 (from 60 min tests) to the maximum allowed value resulted in an
increase of approximately 17% in the burner’s average heat
output. The average measured heat output of the tested burners ranged
from approximately 0.73 to 3.05 kW, which can represent a noteworthy
auxiliary heat source giving low heat losses in households. However,
it is necessary to keep in mind the operating safety of such a source
and ensure a sufficient supply of combustion air and removal of its
combustion products. It is an appliance where the combustion air from
the surroundings of the appliance is used and the flue gas also flows
to the surroundings of the appliance.Because of the necessity
of air exchange in the room while using
this type of combustion appliance, it is necessary to ventilate the
room intensely (to completely exchange the air) according to the instructions
for use, which causes significant losses of the gained thermal energy.
Because of the large volume of combustion products, it is not possible
to omit the intense ventilation without risking health problems in
people present in the room. The available manuals for this type of
appliance make no mention of the use of heat recovery ventilation
units, which could significantly decrease heat losses caused by ventilation
and, at the same time, provide a sufficient supply of fresh air over
the whole period of fuel combustion. The manufacturers of the tested
burners make no recommendation to use carbon dioxide and carbon monoxide
detectors to ensure increased personal safety.Further research
will focus on the operating safety of these appliances
in terms of the impact of contaminants resulting from the combustion
of ethanol on the quality of indoor environment.
Materials
and Methods
A total of eight bioethanol burners from three
different manufacturers
were selected to objectively determine their operating parameters.
Apart from the manufacturer, the burners also differed in the fuel
area volume, design type, burner opening area, and thus the expected
heat output (the manufacturer does not state whether the heat output
is the maximum reached, the average considering the whole test period,
or other—the current legislation does not force manufacturers
to specify it). The basic information about the burners is provided
in Table .In terms of the design, apart from the dimensions,
the burners
mainly differed in the layout of the internal part of the fuel area.
Burners 1, 2, 3, and 8 had their fuel area completely filled with
ceramic wool (hereafter referred to as single-chambered). This type
of burner is shown in Figure . Burners 4, 5, 6, and 7 were divided into two chambers (hereafter
referred to as two-chambered). This type of burner is shown in Figure . The first chamber,
used to dose fuel, was empty. There was a partition separating the
first and second chambers. The partition contained opening areas,
a 13 mm high gap along the whole width of the fuel area in the bottom
part, and a series of circular orifices in the upper part (their number
differed depending on the burner type). The second chamber was completely
filled with ceramic wool. Because of this, the fuel is not poured
directly into the ceramic wool while filling the burner, as this can
cause uneven saturation by the fuel, but is poured into the first
chamber, where the fuel creates a layer and subsequently gradually
(along the whole width) saturates the ceramic wool in the second chamber.
Figure 7
Model
of a single-chambered bioethanol burner and its section:
1—burner body, 2—regulation damper, and 3—ceramic
wool.
Figure 8
Model of a two-chambered bioethanol burner and
its section: 1—burner
body, 2—regulation damper, 3—ceramic wool (second chamber),
4—empty space (first chamber), 5—partition between the
chambers, and 6—circular orifice in the partition between the
chambers.
Model
of a single-chambered bioethanol burner and its section:
1—burner body, 2—regulation damper, and 3—ceramic
wool.Model of a two-chambered bioethanol burner and
its section: 1—burner
body, 2—regulation damper, 3—ceramic wool (second chamber),
4—empty space (first chamber), 5—partition between the
chambers, and 6—circular orifice in the partition between the
chambers.The volatile combustible substance
in this type of burner is then
released not only from the fuel layer in the first chamber but also
from the ceramic wool in the second chamber, which has the visual
result of flame burning from the circular orifices in the partition.
Burners 1, 2, and 3 were equipped with a double casing on the bottom
of the burner to increase operating safety.Ignition of the
fuel in both burner construction types takes place
by the approach of a flame (by a lighter or a matchstick) to the burner
opening. After ignition of ethanol vapors, the fuel burns continuously
according to the several difficult processes (simplified according
to eqn. ).[4,5] Part of the released heat is transported to the surroundings by
convection (hot flue gases are mixed with ambient air) and part is
transported by radiation. Part of the heat transported by radiation
affects the temperature of the whole burner and thereby affects the
intensity of ethanol evaporation. When the ethanol in the burner reaches
78.3 °C, it starts to boil (at normal pressure pN = 101,325 Pa) and then the quantity of ethanol vapors
is the highest.[20]Simplified combustion
equation of ethanol:
Fuel
Bioethanol is ethyl alcohol
(hereafter just ethanol) and its composition is identical to the composition
of potable alcohol. Ethanol could be produced via the synthesis of
hydrocarbons (which cannot be used for bioethanol production) or via
the synthesis of biomass. All fermentable sugars (e.g., glucose and
sucrose) contained in biomass can be transformed into ethanol by fermentation.
Ethanol is a transparent liquid with a density of 0.7893 kg·m–3. According to law, ethanol not intended for drinking
must be denaturized by specific substances, which can vary in different
countries.[21,22]Bioethanol can be bought
as a fuel intended specifically for bioethanol fireplaces at different
levels of purity (different levels of water contamination). Bioalcohol
fuel in the form of a gel (mixture of ethanol and xanthan gum) may
also be used, if the burner permits it.[21,23]Two
liquid fuels were used for the tests (fuel 1 and fuel 2).Fuel
1 contains ethanol with a low mass fraction of water (0.025–0.04
[—] according to the producer’s information) as its
majority component. The LHV stated in the safety data sheet of fuel
1 is LHVethanol = 26.9 MJ·kg–1.
This value is the LHV of pure ethanol according to the manufacturer,
that is, without taking the water mass fraction in the fuel into consideration.
The density of the fuel according to the safety data sheet is ρFuel_1 = 0.80–0.82 kg·dm–3 at
20 °C.Fuel 2 contains ethanol with almost zero mass fraction
of water
as its majority component. The LHV of the fuel stated in the safety
data sheet is also LHVethanol = 26.9 MJ·kg–1. The density of the fuel according to the safety data sheet is ρFuel_2 = 0.789 kg·dm–3 at 20 °C.
Verifying the Heating Values of the Fuels
Measurements to determine the actual heating values of the fuels
were performed using a calorimeter (LECO AC600). The oxidation reaction
occurs in the calorimeter bomb, and heat is released and subsequently
absorbed by the bomb and water. The measured values of the higher
heating value (HHV) for each fuel are HHVFuel_1 = 27.423
MJ·kg–1 and HHVFuel_2 = 29.381 MJ·kg–1. The values were calculated as the average from at
least five measurements.The measurements established a difference
in the HHV of the tested fuels. Because the water vaporized from the
fuel and the water created from the combustion of hydrogen do not
condense in the room (condensation is not desirable), it is necessary
to consider the LHV, not the HHV, while calculating the heat output.
The conversion from HHV to LHV was performed according to the respective
standard.[24]The mass fraction of
hydrogen in anhydrous fuel was determined
according to the molar weight of individual chemical elements in ethanol
and its value is H2r = 13.1%. In the case of fuel 1, the mass fraction of water
according to the data provided by the manufacturer was considered
for the calculation.The resulting calculated LHVs are LHVFuel_1 = 24.68
MJ·kg–1 and LHVFuel_2 = 26.68 MJ·kg–1.
Measurement Methodology
Based on
the measured decrease of fuel weight, the heat input of chemical energy
bound in the fuel was determined taking into account the methods provided
in standard EN 16647 fireplaces for liquid fuel.[15] Because of the flow of flue gas into the heated room and
the combustion appliance being located directly in the heated room,
it is possible to consider the heat input of the appliance as its
heat output (the losses caused by the unburned gas residue and unburned
fuel in the solid residue were disregarded; the radiative heat loss
and the heat loss from the sensible heat of flue gas are considered
as a gain instead of a loss).A calibrated XS BL 6001 scale
was used for the measurements. Between the scale and the tested burner
(only the burner without any fireplace body), a heat insulation plate
was inserted to prevent the damage. The amount of dosed fuel was for
approximately 40 min of operation according to the expected heat output
of the burners (according to the manufacturer’s data). The
fuel dosing method was selected to ensure that the mineral wool was
saturated as evenly as possible along the width of the burner opening.
A funnel was used to achieve this in the case of burners 4, 5, 6,
and 7. There was a 10 min time delay before lighting the burner to
allow the fuel to saturate the ceramic wool.The initial value
of the fuel weight in the burner was noted down
just before lighting the burner, after which the burner was ignited
using a lighter supplied by the seller of the burners. The actual
(remaining) weight of the fuel was recorded at every elapsed minute
after igniting the burner.Along with the heat output measurements,
the maximum flame temperature
was measured 5 and 10 cm above the burner level using a type K thermocouple
during selected tests. The ends of these thermocouples were positioned
at the center of the burner opening in terms of both the length and
the width of the burner opening.While performing the combustion
tests on burner 2 with a partially
closed regulation damper, the burner opening was opened to 21 mm (75%
open) and 14 mm (50% open) of the 28 mm total width of the burner
opening width. The other rules and the procedure were the same as
in the case of other measurements.During the combustion tests
with burner 2 using different fuel
doses, two volumes of fuel were used (approximately 500 mL and approximately
375 mL). The higher one was defined by the manufacturer as the maximum
recommended volume.The combustion test performed by using burner
1 to simulate heating
at low ambient temperature of flue gas was done after stabilizing
the temperature of the burner and the fuel at −11.5 °C.
The ambient temperature was 1.7 °C. The test was performed in
an outdoor environment using wind protection walls from three sides.The atmospheric pressure, the relative air humidity, and the ambient
temperature during all the tests were recorded.The uncertainties
of determination of time, LHV, and fuel consumption
were included in the uncertainty determination of the average and
maximal heat output of the burners. The resulting uncertainty was
determined according to the EA-4/02 document.
Authors: Florian Neubrech; Jurij Kiefer; Volker J Schmidt; Amir K Bigdeli; J Frederick Hernekamp; Thomas Kremer; Ulrich Kneser; Christian Andreas Radu Journal: Burns Date: 2015-10-27 Impact factor: 2.744