Giuseppina Moccia1, Francesco De Caro1, Concetta Pironti1,2, Giovanni Boccia1, Mario Capunzo1, Anna Borrelli2, Oriana Motta1.
Abstract
Background and objectives: Ozone has been one of the most investigated and discussed sanitization methods. This paper reports a procedure to sanitize air hospital environments, in particular chirurgical surgery rooms that require high levels of disinfection. The purpose of this work was the development and implementation of a cleansing and sanitizing procedure for critical clinical settings with ozone, to prevent hospital infections by the elimination of all toxic and harmful microorganisms in the air, and ensure safe use for operators and patients. Materials andEntities:
Keywords: air treatment; contamination; human health; ozone; public health; sanitization
Mesh:
Substances:
Year: 2020 PMID: 33143010 PMCID: PMC7694113 DOI: 10.3390/medicina56110578
Source DB: PubMed Journal: Medicina (Kaunas) ISSN: 1010-660X Impact factor: 2.430
Reference parameters to standard disinfection test.
|
|
|
|
| |
| CFU/plate | 0–25 | 26–50 | over 50 | |
|
|
|
|
|
|
| CFU/m3 | <1 | 10 | 100 | 200 |
Total microbial load estimated on sampling performed in the air (CFU/m3) and on different surfaces (CFU/plate) in an office (results are averaged on 10 measurements).
| AIR and Surface Analysed | Sabouraud Pre-Treatment | SD | Sabouraud Post Treatment | SD | (PCA) Pre-Treatent | SD | (PCA) Post Treatment | SD |
|---|---|---|---|---|---|---|---|---|
| AIR (CFU/m3) | 0 | 0 | 105 | ±4 | 1 | ±1 | ||
| DESK (CFU/plate) | 10 | ±1 | 5 | ±1 | 35 | ±3 | 5 | ±1 |
| TABLE (CFU/plate) | 10 | ±2 | 5 | ±1 | 18 | ±2 | 2 | ±2 |
| PRINTER (CFU/plate) | 14 | ±1 | 7 | ±2 | 10 | ±1 | 3 | ±1 |
| Air-conditioning (CFU/plate) | 10 | ±1 | 7 | ±1 | 12 | ±2 | 4 | ±1 |
| White coats (CFU/plate) | 0 | 0 | 36 | ±1 | 1 | ±1 |
Total microbial load estimated on sampling performed in the air (CFU/m3) and on different surfaces (CFU/plate) in a surgery theatre (results are averaged on 10 measurements).
| AIR and Surface Analysed | Sabouraud Pre-Treatment | Sabouraud Post Treatment | (PCA) Pre-Treatment | (PCA) Post Treatment |
|---|---|---|---|---|
| AIR (CFU/m3) | 0 | 0 | 5 | 1 |
| DESK (CFU/plate) | 0 | 0 | 2 | 0 |
| TABLE (CFU/plate) | 0 | 0 | 0 | 0 |
| Furniture (CFU/plate) | 0 | 0 | 1 | 0 |
Figure 1O3 concentration measured during treatment by the ozone sensor.