Wideband Self-Calibration Method of Inductive CTs and Verification of Determined Values of Current and Phase Errors at Harmonics for Transformation of Distorted Current.

Ernest Stano1, Michal Kaczmarek1.   

Abstract

Self-calibration of a designed wideband inductive current transformer (CT) was carried out in the ampere-turns condition. This method does not require a reference transducer. The values of current and phase errors at the harmonics of frequencies from 100 Hz to 5 kHz were determined for the distorted primary current of the rated main frequency equal to 50 Hz. These results were verified based on the comparison of values measured between two CTs and calculated as the difference between values obtained from their calibration. Moreover, from vectorial diagrams drawn for transformation of the higher harmonics, the source of the change in the values of current and phase errors with frequency is explained. Furthermore, the method for calculation of the values of the corresponding harmonics of the current associated with the active power losses in the core and the magnetization current is presented.

Entities:  

Keywords:  ampere-turns; composite error; current and phase errors; distorted current; equivalent circuit; harmonics; inductive current transformer; power quality; vectorial diagram

Year:  2020        PMID: 32290417      PMCID: PMC7218722          DOI: 10.3390/s20082167

Source DB:  PubMed          Journal:  Sensors (Basel)        ISSN: 1424-8220            Impact factor:   3.576


  1 in total

1.  Impact of DC Transient Disturbances on Harmonic Performance of Voltage Transformers for AC Railway Applications.

Authors:  Palma Sara Letizia; Davide Signorino; Gabriella Crotti
Journal:  Sensors (Basel)       Date:  2022-03-15       Impact factor: 3.576

  1 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.